U - 140/150/170/190/210 CW

ECOi-W Heat Pump Chiller

Cooling capacity: 125,4 to 195,4kW.

Heating capacity: 143,7 to 217,6kW.

Heat pump chiller series with powerful operation by 4 scroll compressors. Maximum water outlet temperature in heating is up to 55°C 1). Defrost limiting design ensures to provide stable hot water even at low ambient conditions.


1) Special condition apply. Please contact an authorized Panasonic dealer in the case of condition >50°C.
· Smart defrost: Defrost limiting design to ensure a constant water outlet temperature even at very low temperatures
· High seasonal efficiency in cooling and heating
· Eurovent certified
· Ambient temperature operating range: -10 to +50°C in cooling, -17 to +20°C in heating
· Water outlet temperature range: -10 to +18°C in cooling, +20 to +50°C in heating
· Super quiet operation
· Victaulic water connections
· Optimized design for service and maintenance
· Simple user friendly control as standard
· Modbus RTU as standard
· Modbus TCP/IP as standard

Technical focus.
· Chiller type: heat pump
· Compressor type (number of compressors): Scroll compressors (4)
· Refrigerant type: R410A
· Refrigerant circuit: 2
· Fan type (number of fans): axial fan (4)
· Heat exchanger: stainless steel plate heat exchanger
· Flow switch, water safety & air purge valves included
· Water filter included (mandatory to be installed on site)
· Night mode setting to save energy and reduce noise level
· Water compensation curve control
· Bluefin anti-corrosion coating
· Optional hydraulic kit
· Optional finned coil treatment
· Optional gauges hydraulic and refrigerant
· Optional BACnet
· Remote LAN connection as standard

The reasons to choose Panasonic as your partner

Explore the new range of fan coils

Specifications

See all
U - 140/150/170/190/210 CW THREE PHASE
128.3 kW 142.1 kW 163.9 kW 177.5 kW 207.9 kW
Model standard without buffer tank U-140CWNB U-150CWNB U-170CWNB U-190CWNB U-210CWNB
Model with buffer tank U-140CWBL U-150CWBL U-170CWBL U-190CWBL U-210CWBL
Power supply (Voltage) V 400 400 400 400 400
Power supply (Phase) Three phase Three phase Three phase Three phase Three phase
Power supply (Frequency) Hz 50 50 50 50 50
Cooling capacity (1) kW 128,3 142,1 163,9 177,5 207,9
Input power cooling (1) kW 43,2 47,7 54,7 61,3 69,7
Total EER 100% (1) 2,97 2,98 2,99 2,90 2,98
SEER (2) (3) 4,39 4,36 4,31 4,23 4,28
ηs,c (2) (3) % 173 171 169 166 168
Heating capacity (4) kW 144,0 154,0 170,0 195,0 218,0
Input power heating (4) kW 45,7 50,3 55,5 67,4 78,3
SCOP (3) (5) 3,30 3,33 3,30 3,28 3,23
ηs,h (3) (5) % 129 130 129 128 126
Startup type Direct Direct Direct Direct Direct
Maximum operating current A 108,0 119,0 136,0 153,0 170,0
Startup current without softstarter A 251 262 324 341 396
Startup current with softstarter A 130 141 161 178 201
Sound power (with standard fans) dB(A) 85,4 85,4 87,0 88,1 88,1
Sound pressure (with standard fans) (6) dB(A) 53,4 53,4 55,0 56,1 56,1
Dimension (with standard fans) without buffer tank (Height) mm 2.295 2.295 2.295 2.295 2.295
Dimension (with standard fans) without buffer tank (Width) mm 2.856 2.856 2.856 2.856 2.856
Dimension (with standard fans) without buffer tank (Depth) mm 2.210 2.210 2.210 2.210 2.210
Dimension (with standard fans) with buffer tank (Height) mm 2.295 2.295 2.295 2.295 2.295
Dimension (with standard fans) with buffer tank (Width) mm 3.666 3.666 3.666 3.666 3.666
Dimension (with standard fans) with buffer tank (Depth) mm 2.210 2.210 2.210 2.210 2.210
Weight (with 1 pump) without buffer tank kg 1.570 1.580 1.680 1.750 2.020
Weight (with 1 pump) with buffer tank kg 1.700 1.710 1.810 1.880 2.150
Refrigerant (R410A) kg 2 x 24,7 2 x 24,7 24,7/33,3 2 x 33,3 2 x 33,3
Number of refrigerant circuit 2 2 2 2 2
Compressors . . . . .
Number of compressors 4 4 4 4 4
Type of compressors Scroll Scroll Scroll Scroll Scroll
Part load step % 0 / 24 / 26 / 48 / 50 / 52 / 74 / 76 / 100 0 / 23 / 27 / 46 / 50 / 54 / 73 / 77 / 100 0 / 20 / 24 / 44 / 45 / 55 / 69 / 80 / 100 0 / 22 / 28 / 44 / 50 / 56 / 72 / 78 / 100 0 / 19 / 31 / 38 / 50 / 62 / 69 / 81 / 100
Crankcase heater W 4 x 66 4 x 66 3 x 66 / 82 2 x 82 / 2 x 66 2 x 95 / 2 x 66
Evaporator . . . . .
Number of evaporators 1 1 1 1 1
Type of evaporators Plate Plate Plate Plate Plate
Nominal water flow (cooling) m³/h 21,56 23,65 25,95 30,24 33,62
Water pressure drop (cooling) kPa 33 39 24 32 40
Water volume L 8,49 8,49 12,21 12,21 12,21
Antifreeze heater W 60 60 120 120 120
Coils . . . . .
Number of coils 4 4 4 4 4
Frontal surface 11,88 11,88 11,88 11,88 11,88
Number of rows 2 + 2 2 + 2 2 + 3 3 + 3 3 + 3
Fans standard . . . . .
Number of fans standard 4 4 4 4 4
Air flow of fans standard m³/h 56.000 56.000 71.000 86.000 83.000
Rotation speed r.p.m. 900 900 900 900 900
Power input (each fan) W 940 940 940 - 1.650 1.650 1.650
Chiller water connections . . . . .
Type of water connections Victaulic Victaulic Victaulic Victaulic Victaulic
Inlet - diameter Inch 2 ½ 2 ½ 2 ½ 2 ½ 2 ½
Outlet - diameter Inch 2 ½ 2 ½ 2 ½ 2 ½ 2 ½

1) Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.
2) Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers.
3) Those are the data with variable flow. For the data with fixed flow, please contact an authorised Panasonic dealer.
4) Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87 % R.H., according EN14511 standard.
5) Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps.
6) Sound pressure levels calculated at 10 meters. Sound pressure levels refer to ISO standard 3744 with parallel piped shape.