U - 140/150/170/190/210 CV

ECOi-W Cooling Only Chiller

Cooling capacity: 134,0 to 208,8kW.

Powerful and efficient operation with 4 scroll compressors and superior flexibility with plug and play hydraulic options.

· High seasonal efficiency
· Ambient temperature operating range: -10 to +50°C
· Water outlet temperature range: -10 to +18°C
· Super quiet operation
· Victaulic water connections
· Optimized design for service and maintenance
· Simple user friendly control as standard
· Modbus RTU as standard
· Modbus TCP/IP as standard

Technical focus.
· Chiller type: cooling only
· Compressor type (number of compressors): Scroll compressors (4)
· Refrigerant type: R410A
· Refrigerant circuit: 2
· Fan type (number of fans): axial fan (4)
· Heat exchanger: stainless steel plate heat exchanger
· Flow switch, water safety & air purge valves included
· Water filter included (mandatory to be installed on site)
· Night mode setting to save energy and reduce noise level
· Water compensation curve control
· Optional hydraulic kit
· Optional finned coil treatment
· Optional gauges hydraulic and refrigerant
· Optional BACnet
· Remote LAN connection as standard

The reasons to choose Panasonic as your partner

Explore the new range of fan coils

Specifications

See all
U - 140/150/170/190/210 CV THREE PHASE
132.0 kW 146.0 kW 164.0 kW 181.0 kW 208.0 kW
Model standard without buffer tank U-140CVNB U-150CVNB U-170CVNB U-190CVNB U-210CVNB
Model with buffer tank U-140CVBL U-150CVBL U-170CVBL U-190CVBL U-210CVBL
Power supply (Voltage) V 400 400 400 400 400
Power supply (Phase) Three phase Three phase Three phase Three phase Three phase
Power supply (Frequency) Hz 50 50 50 50 50
Cooling capacity (1) kW 132,0 146,0 164,0 181,0 208,0
Input power cooling (1) kW 43,1 47,6 54,8 61,1 69,8
Total EER 100% (1) 3,06 3,07 2,99 2,96 2,98
SEER (2) 4,40 4,45 4,38 4,40 4,25
ηs,c (2) % 173 175 172 173 167
Startup type Direct Direct Direct Direct Direct
Maximum operating current A 108,0 119,0 136,0 153,0 170,0
Startup current without softstarter A 251 262 324 341 396
Startup current with softstarter A 130 141 161 178 201
Sound power (with standard fans) dB(A) 85,4 85,4 87,0 88,1 88,1
Sound pressure (with standard fans) (3) dB(A) 53,4 53,4 55,0 56,1 56,1
Dimension (with standard fans) without buffer tank (Height) mm 2.295 2.295 2.295 2.295 2.295
Dimension (with standard fans) without buffer tank (Width) mm 2.856 2.856 2.856 2.856 2.856
Dimension (with standard fans) without buffer tank (Depth) mm 2.210 2.210 2.210 2.210 2.210
Dimension (with standard fans) with buffer tank (Height) mm 2.295 2.295 2.295 2.295 2.295
Dimension (with standard fans) with buffer tank (Width) mm 3.666 3.666 3.666 3.666 3.666
Dimension (with standard fans) with buffer tank (Depth) mm 2.210 2.210 2.210 2.210 2.210
Weight (with 1 pump) without buffer tank kg 1.510 1.520 1.610 1.680 1.940
Weight (with 1 pump) with buffer tank kg 1.640 1.650 1.740 1.810 2.070
Refrigerant (R410A) kg 2 x 24,7 2 x 24,7 24,7/33,3 2 x 33,3 2 x 33,3
Number of refrigerant circuit 2 2 2 2 2
Compressors . . . . .
Number of compressors 4 4 4 4 4
Type of compressors Scroll Scroll Scroll Scroll Scroll
Part load step % 0 / 24 / 26 / 48 / 50 / 52 / 74 / 76 / 100 0 / 23 / 27 / 46 / 50 / 54 / 73 / 77 / 100 0 / 20 / 24 / 44 / 45 / 55 / 69 / 80 / 100 0 / 22 / 28 / 44 / 50 / 56 / 72 / 78 / 100 0 / 19 / 31 / 38 / 50 / 62 / 69 / 81 / 100
Crankcase heater W 4 x 66 4 x 66 3 x 66 / 82 2 x 82 / 2 x 66 2 x 95 / 2 x 66
Evaporator . . . . .
Number of evaporators 1 1 1 1 1
Type of evaporators Plate Plate Plate Plate Plate
Nominal water flow (cooling) m³/h 21,56 23,65 25,95 30,24 33,62
Water pressure drop (cooling) kPa 33 39 24 32 40
Water volume L 8,49 8,49 12,21 12,21 12,21
Antifreeze heater W 60 60 120 120 120
Coils . . . . .
Number of coils 4 4 4 4 4
Frontal surface 11,88 11,88 11,88 11,88 11,88
Number of rows 2 + 2 2 + 2 2 + 3 3 + 3 3 + 3
Fans standard . . . . .
Number of fans standard 4 4 4 4 4
Air flow of fans standard m³/h 56.000 56.000 71.000 86.000 83.000
Rotation speed r.p.m. 900 900 900 900 900
Power input (each fan) W 940 940 940 - 1.650 1.650 1.650
Chiller water connections . . . . .
Type of water connections Victaulic Victaulic Victaulic Victaulic Victaulic
Inlet - diameter Inch 2 ½ 2 ½ 2 ½ 2 ½ 2 ½
Outlet - diameter Inch 2 ½ 2 ½ 2 ½ 2 ½ 2 ½

1) Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.
2) Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers.
3) Sound pressure levels calculated at 10 meters. Sound pressure levels refer to ISO standard 3744 with parallel piped shape.
** The data are calculated with variable flow.

Complementary products