Specifications

See all
T-CAP stand-alone outdoor M Series 1 phase - 3 phase · R290 SINGLE PHASE THREE PHASE
9 kW 12 kW 9 kW 12 kW 16 kW 20 kW 25 kW 30 kW
Outdoor unit WH-WXG09ME5 WH-WXG12ME5 WH-WXG09ME8 WH-WXG12ME8 WH-WXG16ME8 WH-WXG20ME8 WH-WXG25ME8 WH-WXG30ME8
Remote controller with Wi-Fi adapter CZ-RTW2TAW1C CZ-RTW2TAW1C CZ-RTW2TAW1C CZ-RTW2TAW1C CZ-RTW2TAW1C CZ-RTW2TAW1C CZ-RTW2TAW1C CZ-RTW2TAW1C
Heating capacity (A +7°C, W 35°C) kW 9,00 12,00 9,00 12,00 16,00 20,00 25,00 30,00
COP (A +7°C, W 35°C) 5,23 5,06 5,23 5,06 4,89 4,80 4,50 4,40
Heating capacity (A +7°C, W 55°C) kW 9,00 12,00 9,00 12,00 16,00 20,00 25,00 30,00
COP (A +7°C, W 55°C) 3,24 3,23 3,24 3,23 3,20 3,18 3,00 3,00
Heating capacity (A +2°C, W 35°C) kW 9,00 12,00 9,00 12,00 16,00 20,00 25,00 30,00
COP (A +2°C, W 35°C) 3,81 3,54 3,81 3,54 3,30 3,39 2,80 2,50
Heating capacity (A +2°C, W 55°C) kW 9,00 12,00 9,00 12,00 16,00 20,00 25,00 30,00
COP (A +2°C, W 55°C) 2,54 2,42 2,54 2,42 2,37 2,08 1,97 1,95
Heating capacity (A -7°C, W 35°C) kW 9,00 12,00 9,00 12,00 16,00 20,00 25,00 30,00
COP (A -7°C, W 35°C) 3,45 3,00 3,45 3,00 2,53 2,48 2,36 2,33
Heating capacity (A -7°C, W 55°C) kW 9,00 12,00 9,00 12,00 16,00 20,00 25,00 30,00
COP (A -7°C, W 55°C) 2,35 2,17 2,35 2,17 1,97 1,90 1,80 1,49
Cooling capacity (A 35°C, W 7°C) at Comfort mode kW 20,00 25,00 26,00
EER (A 35°C, W 7°C) at Comfort mode EER 3,02 2,86 2,68
Cooling capacity (A 35°C, W 7°C) at Efficiency mode (default) kW 9,00 9,00 9,00 9,00 9,00 15,00 15,00 15,00
EER (A 35°C, W 7°C) at Efficiency mode (default) kW 3,61 3,61 3,61 3,61 3,61 3,61 3,61 3,61
Cooling capacity (A 35°C, W 18°C) at Comfort mode kW 20,00 25,00 30,00
EER (A 35°C, W 18°C) at Comfort mode EER 4,79 4,47 4,10
Heating average climate. Seasonal energy efficiency SCOP (W 35°C / W 55°C) SCOP 5,00 / 3,50 4,73 / 3,65 5,00 / 3,50 4,73 / 3,65 4,75 / 3,70 4,36 / 3,59 4,25 / 3,57 3,95 / 3,46
Heating average climate. Seasonal energy efficiency η (W 35°C / W 55°C) ηs % 197 / 137 186 / 143 197 / 137 145 / 143 187 / 145 171 / 141 167 / 140 155 / 135
Heating average climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+++ / A++ A+++ / A++ A+++ / A++ A+++ / A++ A+++ / A++ A++/A++ A++/A++ A++/A++
Heating warm climate. Seasonal energy efficiency SCOP (W 35°C / W 55°C) SCOP 6,33 / 4,40 6,20 / 4,40 6,33 / 4,40 6,20 / 4,40 6,08 / 4,45 5,37 / 4,07 5,22 / 4,14 4,93 / 4,01
Heating warm climate. Seasonal energy efficiency η (W 35°C / W 55°C) ηs % 250 / 173 245 / 173 250 / 173 245 / 173 240 / 175 212 / 160 206 / 163 194 / 158
Heating warm climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++
Heating cold climate. Seasonal energy efficiency SCOP (W 35°C / W 55°C) SCOP 4,45 / 3,20 4,38 / 3,25 4,45 / 3,20 4,38 / 3,25 4,33 / 3,40 3,07 / 2,57 3,16 / 2,71 3,20 / 2,71
Heating cold climate. Seasonal energy efficiency η (W 35°C / W 55°C) ηs % 175 / 125 172 / 127 175 / 125 172 / 127 170 / 133 120 / 100 123 / 105 125 / 105
Heating cold climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+++ / A++ A++ / A++ A+++ / A++ A++ / A++ A++ / A++ A / A+ A+ / A+ A+ / A+
Outdoor sound power (Heat) (2) dB(A) 52 53 52 53 57 56 59 61
Outdoor dimension (Height) mm 1.520 1.520 1.520 1.520 1.520 1.645 1.645 1.645
Outdoor dimension (Width) mm 1.200 1.200 1.200 1.200 1.200 1.500 1.500 1.500
Outdoor dimension (Depth) mm 430 430 430 430 430 460 460 460
Outdoor net weight kg 163 163 163 163 165 240 240 240
A class pump (Number of speeds) Variable speed Variable speed Variable speed Variable speed Variable speed Variable speed Variable speed Variable speed
A class pump (Input power Min) W 30 30 30 30 30 230 230 230
A class pump (Input power Max) W 175 175 175 175 175
Heating water flow (∆T=5 K. 35°C) L/min 25,8 34,4 25,8 34,4 45,9 57,3 71,6 86,0
Refrigerant (R290) / CO2 Eq. (3) kg / T 1,78 / 0,006 1,78 / 0,006 1,78 / 0,006 1,78 / 0,006 1,77 / 0,006 3,0 / 0,009 3,0 / 0,009 3,0 / 0,009
Operation range - Outdoor ambient (Heat) °C -28 ~ +35 -28 ~ +35 -28 ~ +35 -28 ~ +35 -28 ~ +35 -25 ~ +35 -25 ~ +35 -25 ~ +35
Operation range - Outdoor ambient (Cool) °C +10 ~ +43 +10 ~ +43 +10 ~ +43 +10 ~ +43 +10 ~ +43 +10 ~ +43 +10 ~ +43 +10 ~ +43
Water outlet (Heat) °C 25 ~ 75 25 ~ 75 25 ~ 75 25 ~ 75 25 ~ 75 20 ~ 75 (4) 20 ~ 75 (4) 20 ~ 75 (4)
Water outlet (Cool) °C 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20
Outdoor recommended fuse, supply (5) A 30 30 20 20 25 50 50 50
Outdoor recommended minimum cable size, supply (5) mm² 3x4,0 3x4,0 5x1,5 5x1,5 5x2,5 5x10 - 5x16 5x10 - 5x16 5x10 - 5x16

(1) Scale from A+++ to D.
(2) Sound power level in accordance to EN12102 under conditions of the EN14825 (part load).
(3) WH-WXG models are hermetically sealed.
(4) Check local regulations.
* EER and COP calculation is based in accordance to EN 14511.