Models
Aquarea M Series, the latest generation of Aquarea air to water heat pumps with R290
Aquarea T‑CAP M Series delivers a revolution in the design, performance, connectivity, and sustainability
The solution is suitable for both new buildings and retrofits, as it offers a sustainable alternative to traditional fossil fuel heating systems and it can be easily integrated with existing water system such as fan coils, floor heating or domestic hot water tanks.
- Up to 75°C water outlet down to -15°C outdoor 1)
- Quiet operation: Only 29dB(A) sound pressure at 5m 2)
- Reliable outdoor units with Panasonic compressor, operating down to -28°C outdoor 3)
- T-CAP technology: Keeping heating capacity down to -20°C
- Panasonic Comfort Cloud App and Aquarea Service Cloud included
1) Down to 15ºC outdoor for 20, 25 and 30kW models
2) Sound pressure calculation for WH-WXG12ME5, free standing, A +7°C, W 35°C in Quite mode 3
3) Down to -25ºC outdoor for 20, 25 and 30kW models
Owning an Aquarea?
Specifications
T-CAP stand-alone outdoor M Series 1 phase - 3 phase · R290 | SINGLE PHASE | THREE PHASE | ||||||||
---|---|---|---|---|---|---|---|---|---|---|
9 kW | 12 kW | 9 kW | 12 kW | 16 kW | 20 kW | 25 kW | 30 kW | |||
Outdoor unit | WH-WXG09ME5 | WH-WXG12ME5 | WH-WXG09ME8 | WH-WXG12ME8 | WH-WXG16ME8 | WH-WXG20ME8 | WH-WXG25ME8 | WH-WXG30ME8 | ||
Remote controller with Wi-Fi adapter | CZ-RTW2TAW1C | CZ-RTW2TAW1C | CZ-RTW2TAW1C | CZ-RTW2TAW1C | CZ-RTW2TAW1C | CZ-RTW2TAW1C | CZ-RTW2TAW1C | CZ-RTW2TAW1C | ||
Heating capacity (A +7°C, W 35°C) | kW | 9,00 | 12,00 | 9,00 | 12,00 | 16,00 | 20,00 | 25,00 | 30,00 | |
COP (A +7°C, W 35°C) | 5,23 | 5,06 | 5,23 | 5,06 | 4,89 | 4,80 | 4,50 | 4,40 | ||
Heating capacity (A +7°C, W 55°C) | kW | 9,00 | 12,00 | 9,00 | 12,00 | 16,00 | 20,00 | 25,00 | 30,00 | |
COP (A +7°C, W 55°C) | 3,24 | 3,23 | 3,24 | 3,23 | 3,20 | 3,18 | 3,00 | 3,00 | ||
Heating capacity (A +2°C, W 35°C) | kW | 9,00 | 12,00 | 9,00 | 12,00 | 16,00 | 20,00 | 25,00 | 30,00 | |
COP (A +2°C, W 35°C) | 3,81 | 3,54 | 3,81 | 3,54 | 3,30 | 3,39 | 2,80 | 2,50 | ||
Heating capacity (A +2°C, W 55°C) | kW | 9,00 | 12,00 | 9,00 | 12,00 | 16,00 | 20,00 | 25,00 | 30,00 | |
COP (A +2°C, W 55°C) | 2,54 | 2,42 | 2,54 | 2,42 | 2,37 | 2,08 | 1,97 | 1,95 | ||
Heating capacity (A -7°C, W 35°C) | kW | 9,00 | 12,00 | 9,00 | 12,00 | 16,00 | 20,00 | 25,00 | 30,00 | |
COP (A -7°C, W 35°C) | 3,45 | 3,00 | 3,45 | 3,00 | 2,53 | 2,48 | 2,36 | 2,33 | ||
Heating capacity (A -7°C, W 55°C) | kW | 9,00 | 12,00 | 9,00 | 12,00 | 16,00 | 20,00 | 25,00 | 30,00 | |
COP (A -7°C, W 55°C) | 2,35 | 2,17 | 2,35 | 2,17 | 1,97 | 1,90 | 1,80 | 1,49 | ||
Cooling capacity (A 35°C, W 7°C) at Comfort mode | kW | 20,00 | 25,00 | 26,00 | ||||||
EER (A 35°C, W 7°C) at Comfort mode | EER | 3,02 | 2,86 | 2,68 | ||||||
Cooling capacity (A 35°C, W 7°C) at Efficiency mode (default) | kW | 9,00 | 9,00 | 9,00 | 9,00 | 9,00 | 15,00 | 15,00 | 15,00 | |
EER (A 35°C, W 7°C) at Efficiency mode (default) | kW | 3,61 | 3,61 | 3,61 | 3,61 | 3,61 | 3,61 | 3,61 | 3,61 | |
Cooling capacity (A 35°C, W 18°C) at Comfort mode | kW | 20,00 | 25,00 | 30,00 | ||||||
EER (A 35°C, W 18°C) at Comfort mode | EER | 4,79 | 4,47 | 4,10 | ||||||
Heating average climate. Seasonal energy efficiency SCOP (W 35°C / W 55°C) | SCOP | 5,00 / 3,50 | 4,73 / 3,65 | 5,00 / 3,50 | 4,73 / 3,65 | 4,75 / 3,70 | 4,36 / 3,59 | 4,25 / 3,57 | 3,95 / 3,46 | |
Heating average climate. Seasonal energy efficiency η (W 35°C / W 55°C) | ηs % | 197 / 137 | 186 / 143 | 197 / 137 | 145 / 143 | 187 / 145 | 171 / 141 | 167 / 140 | 155 / 135 | |
Heating average climate. Energy class (W 35°C / W 55°C) (1) | A+++ to D | A+++ / A++ | A+++ / A++ | A+++ / A++ | A+++ / A++ | A+++ / A++ | A++/A++ | A++/A++ | A++/A++ | |
Heating warm climate. Seasonal energy efficiency SCOP (W 35°C / W 55°C) | SCOP | 6,33 / 4,40 | 6,20 / 4,40 | 6,33 / 4,40 | 6,20 / 4,40 | 6,08 / 4,45 | 5,37 / 4,07 | 5,22 / 4,14 | 4,93 / 4,01 | |
Heating warm climate. Seasonal energy efficiency η (W 35°C / W 55°C) | ηs % | 250 / 173 | 245 / 173 | 250 / 173 | 245 / 173 | 240 / 175 | 212 / 160 | 206 / 163 | 194 / 158 | |
Heating warm climate. Energy class (W 35°C / W 55°C) (1) | A+++ to D | A+++ / A+++ | A+++ / A+++ | A+++ / A+++ | A+++ / A+++ | A+++ / A+++ | A+++ / A+++ | A+++ / A+++ | A+++ / A+++ | |
Heating cold climate. Seasonal energy efficiency SCOP (W 35°C / W 55°C) | SCOP | 4,45 / 3,20 | 4,38 / 3,25 | 4,45 / 3,20 | 4,38 / 3,25 | 4,33 / 3,40 | 3,07 / 2,57 | 3,16 / 2,71 | 3,20 / 2,71 | |
Heating cold climate. Seasonal energy efficiency η (W 35°C / W 55°C) | ηs % | 175 / 125 | 172 / 127 | 175 / 125 | 172 / 127 | 170 / 133 | 120 / 100 | 123 / 105 | 125 / 105 | |
Heating cold climate. Energy class (W 35°C / W 55°C) (1) | A+++ to D | A+++ / A++ | A++ / A++ | A+++ / A++ | A++ / A++ | A++ / A++ | A / A+ | A+ / A+ | A+ / A+ | |
Outdoor sound power (Heat) (2) | dB(A) | 52 | 53 | 52 | 53 | 57 | 56 | 59 | 61 | |
Outdoor dimension (Height) | mm | 1.520 | 1.520 | 1.520 | 1.520 | 1.520 | 1.645 | 1.645 | 1.645 | |
Outdoor dimension (Width) | mm | 1.200 | 1.200 | 1.200 | 1.200 | 1.200 | 1.500 | 1.500 | 1.500 | |
Outdoor dimension (Depth) | mm | 430 | 430 | 430 | 430 | 430 | 460 | 460 | 460 | |
Outdoor net weight | kg | 163 | 163 | 163 | 163 | 165 | 240 | 240 | 240 | |
A class pump (Number of speeds) | Variable speed | Variable speed | Variable speed | Variable speed | Variable speed | Variable speed | Variable speed | Variable speed | ||
A class pump (Input power Min) | W | 30 | 30 | 30 | 30 | 30 | 230 | 230 | 230 | |
A class pump (Input power Max) | W | 175 | 175 | 175 | 175 | 175 | ||||
Heating water flow (∆T=5 K. 35°C) | L/min | 25,8 | 34,4 | 25,8 | 34,4 | 45,9 | 57,3 | 71,6 | 86,0 | |
Refrigerant (R290) / CO2 Eq. (3) | kg / T | 1,78 / 0,006 | 1,78 / 0,006 | 1,78 / 0,006 | 1,78 / 0,006 | 1,77 / 0,006 | 3,0 / 0,009 | 3,0 / 0,009 | 3,0 / 0,009 | |
Operation range - Outdoor ambient (Heat) | °C | -28 ~ +35 | -28 ~ +35 | -28 ~ +35 | -28 ~ +35 | -28 ~ +35 | -25 ~ +35 | -25 ~ +35 | -25 ~ +35 | |
Operation range - Outdoor ambient (Cool) | °C | +10 ~ +43 | +10 ~ +43 | +10 ~ +43 | +10 ~ +43 | +10 ~ +43 | +10 ~ +43 | +10 ~ +43 | +10 ~ +43 | |
Water outlet (Heat) | °C | 25 ~ 75 | 25 ~ 75 | 25 ~ 75 | 25 ~ 75 | 25 ~ 75 | 20 ~ 75 (4) | 20 ~ 75 (4) | 20 ~ 75 (4) | |
Water outlet (Cool) | °C | 5 ~ 20 | 5 ~ 20 | 5 ~ 20 | 5 ~ 20 | 5 ~ 20 | 5 ~ 20 | 5 ~ 20 | 5 ~ 20 | |
Outdoor recommended fuse, supply (5) | A | 30 | 30 | 20 | 20 | 25 | 50 | 50 | 50 | |
Outdoor recommended minimum cable size, supply (5) | mm² | 3x4,0 | 3x4,0 | 5x1,5 | 5x1,5 | 5x2,5 | 5x10 - 5x16 | 5x10 - 5x16 | 5x10 - 5x16 |
(1) Scale from A+++ to D.
(2) Sound power level in accordance to EN12102 under conditions of the EN14825 (part load).
(3) WH-WXG models are hermetically sealed.
(4) Check local regulations.
* EER and COP calculation is based in accordance to EN 14511.