Models
PRO-HT Tank Series for ECOi
PRO-HT Tank DHW. Big volume and high temperature tank for commercial application.
Panasonic commercial PRO-HT Tank solutions meet all needs of your hot water applications providing maximum water temperature 65°C.
High temperature hot water is efficiently produced without any boosters.
Can be combined with ECOi 3-Pipe to adapt various projects from high-end residentials to offices and hotels.
High performance and high saving.
- A7 COP maximum 5,29 and 6,70 for ECOi 3-Pipe in case of heat recovery
- Efficient hot water production by heat recovery
- High temperature hot water without booster
- Save installation time and cost by skipping additional accessories
Hot water production with simultaneous heating and cooling.
- Maximum water outlet temperature up to 65°C without an electric heater
- Big volume tank from 750L to 1.000L capacity
- Heat exchanger design inhibits limescale
Trusted quality.
- Double tube heat exchanger following drinking-water regulation
- Tank and heat exchanger made with stainless steel
- Internal and external pickling
Specifications
PRO-HT Tank DHW for ECOi | THREE PHASE | |||
---|---|---|---|---|
Reference | PAW-VP750LDHW-1 | PAW-VP1000LDHW-1 | ||
Outdoor unit | U-16MF3E8 | U-16MF3E8 | ||
Volume | L | 726 | 933 | |
Dimension (Height) | mm | 1.855 | 2.210 | |
Dimension (Diameter) | mm | 990 | 990 | |
Connections to the water supply network | 1 _" | 1 _" | ||
Net weight | kg | 179 | 191 | |
Weight (filled with water) | kg | 929 | 1.121 | |
Nominal electrical power | W | 5,12 | 6,14 | |
Reference tapping cycle | 2XL | 2XL | ||
Energy consumption by chosen cycle A7 / W10-55 | kWh | 4,14 | 5,1 | |
Energy consumption by chosen cycle A15 / W10-55 | kWh | 3,5 | 4,61 | |
COP DHW (A7 / W10-55) EN 16147 (1) | 5,29 | 4,81 | ||
COP DHW (A15 / W10-55) EN 16147 (2) | 7,01 | 5,32 | ||
Standby input power according to EN16147 | W | 77 | 80 | |
Sound pressure on 1m | dB(A) | 52 | 52 | |
Average insulation thickness | mm | 100 | 100 | |
Heat exchanger connection for inlet | Inch (mm) | 1/2 (12,70) | 1/2 (12,70) | |
Heat exchanger connection for outlet | Inch (mm) | 3/4 (19,05) | 3/4 (19,05) | |
Maximum power consumption without heater | W | 20,4 | 20,4 | |
Maximum power consumption with heater | W | 26,4 | 26,4 | |
Number of electrical heaters x power | W | 1 x 6.000 | 1 x 6.000 | |
Power supply (Voltage) | V | 400 | 400 | |
Power supply (Frequency) | Hz | 50 | 50 | |
Electric protection | A | 16 | 16 | |
Moisture protection | IP 24 | IP 24 | ||
Maximum pipe length | m | 50 | 50 | |
Elevation difference (in/out) | m | 30/30 | 30/30 | |
Operating range - outdoor temperature (Min) | °C | -20 | -20 | |
Operating range - outdoor temperature (Max) | °C | 35 | 35 | |
Water temperature with heat pump (Max) | °C | 65 | 65 | |
Water temperature with electrical heater (Max) | °C | 85 | 85 | |
Refrigerant (R410A) / CO2 Eq. | kg / T | 8,3 /17,1 | 8,3 /17,1 |
1) Heating of sanitary water up to 55°C with inlet air temperature at 7°C, humidity at 89% and inlet water temperature at 10°C. According to EN16147.
2) Heating of sanitary water up to 55°C with inlet air temperature at 15°C, humidity at 74% and inlet water temperature at 10°C. According to EN16147.
This product is designed to meet the European Drinking Directive 98/83/EC amended by 2015/1787/EU. The lifespan of the product is not guaranteed in the case of the use of groundwater, such as spring water or well water, the use of tap water when salt or other impurities are contained, nor in areas of acidic water quality. Maintenance and warranty costs related to these cases are the customer’s responsibility.
* When connected as pressurised, safety valve is mandatory.