Models
Mini ECOi LZ2 Series 8 and 10HP - R32
Introducing widest range of R32 Mini VRF.
Perfect fit for small to medium size projects.
8 and 10HP LZ2 Mini VRF units bring in the total benefits of a VRF system in a smaller application. You can enjoy advanced individual and central VRF control options including the revolutionary Panasonic AC Smart Cloud and AC Service Cloud.
For the most difficult conditions.
New ECOi LZ2 series are able to operate at the hardest conditions from -20°C up to +52°C providing continuous and efficient, heating and cooling for your space all year long.
Technical focus.
- SEER levels up to 7,56 and SCOP levels up to 4,59 (for 8HP model)
- Continuous operation at extreme ambient temperatures: -20°C (heating) to 52°C (cooling)
- Widest range of connectable units in R32 VRF
- New and unique indoors with nanoe™ X, hydroxyl radicals contained in water
- Allowing wide range of installations with and without refrigerant mitigation
- Flexible mitigation measures, with R32 refrigerant leak detector/alarm to be installed only when required
Bringing nature’s balance indoors
Specifications
Mini ECOi LZ2 Series 8 and 10HP - R32 | THREE PHASE | |||
---|---|---|---|---|
8 HP | 10 HP | |||
Outdoor unit | U-8LZ2E8 | U-10LZ2E8 | ||
Power supply (Voltage) | V | 380 - 400-415 | 380 - 400 - 415 | |
Power supply (Phase) | Three phase | Three phase | ||
Power supply (Frequency) | Hz | 50 | 50 | |
Cooling capacity (Nominal) | kW | 22,4 | 28,0 | |
EER (1) | W/W | 3,84 | 3,47 | |
Current cooling (1p 220V / 3p 380) | A | 9,73 | 13,2 | |
Current cooling (1p 230V / 3p 400) | A | 9,25 | 12,5 | |
Current cooling (1p 240V / 3p 415) | A | 8,91 | 12,1 | |
Input power cooling | kW | 5,83 | 8,07 | |
Heating capacity (Nominal) | kW | 25,0 | 28,0 | |
COP (1) | W/W | 4,30 | 4,47 | |
Current heating (1p 220V / 3p 380) | A | 9,81 | 10,5 | |
Current heating (1p 230V / 3p 400) | A | 9,32 | 9,93 | |
Current heating (1p 240V / 3p 415) | A | 8,98 | 9,57 | |
Input power heating | kW | 5,81 | 6,26 | |
Starting current | A | 1,0 | 1,0 | |
Maximum current | A | 13,7 | 19,5 | |
Maximum input power (1p 220V / 3p 380) | kW | 8,21 | 11,9 | |
Maximum input power (1p 230V / 3p 400) | kW | 8,64 | 12,6 | |
Maximum input power (1p 240V / 3p 415) | kW | 8,96 | 13,0 | |
Maximum number of connectable indoor units (2) | 16 | 16 | ||
External static pressure | Pa | 0 ~ 35 | 0 ~ 35 | |
Air flow | m³/min | 158 | 167 | |
Sound pressure (Cool) | dB(A) | 59,0 | 60,0 | |
Sound pressure (Cool silent 1) | dB(A) | 56 | 57 | |
Sound pressure (Cool silent 2) | dB(A) | 54 | 55 | |
Sound pressure (Cool silent 3) | dB(A) | 52 | 53 | |
Sound pressure (Cool silent 4) | dB(A) | 50 | 50 | |
Sound power (Cool) | dB(A) | 72 | 74 | |
Dimension (Height) | mm | 1.500 | 1.500 | |
Dimension (Width) | mm | 980 | 980 | |
Dimension (Depth) | mm | 370 | 370 | |
Net weight | kg | 125 | 126 | |
Piping diameter (Liquid) | Inch (mm) | 3/8 (9,52) | 3/8 (9,52) | |
Piping diameter (Gas) | Inch (mm) | 3/4 (19,05) | 7/8 (22,22) | |
Maximum piping length total | m | 300 | 300 | |
Elevation difference (in/out) (outdoor unit upper) | m | 50 | 50 | |
Elevation difference (in/out) (outdoor unit lower) | m | 40 | 40 | |
Refrigerant (R32) / CO2 Eq. | kg / T | 4,9 | 5,1 | |
Maximum allowable indoor / outdoor capacity ratio (3) | % | 50 ~ 150 (130) | 50 ~ 150 (130) | |
Operating range (Cool - Min) | °C | -10 | -10 | |
Operating range (Cool - Max) | °C | 52 | 52 | |
Operating range (Heat - Min) | °C | -20 | -20 | |
Operating range (Heat - Max) | °C | 18 | 18 | |
ErP data (4) | U-8LZ2E8 | U-10LZ2E8 | ||
SEER (5) | 7,56 | 7,08 | ||
ηs,c | 299,4% | 280,2% | ||
SCOP (5) | 4,59 | 4,60 | ||
ηs,h | 180,6% | 181,0% |
(2) The number in parenthesis indicates maximum number of connectable indoor unit in case of 1,5kW indoor units connection.
(3) The number in parenthesis indicates maximum allowed indoor / outdoor capacity ratio in case of 1,5kW indoor units connection.
(4) SEER / SCOP and ηs,c / ηs,h are in accordance with ErP test data for U2 type 4 way 90x90 cassette indoor units. Eurovent certified.
(5) SEER / SCOP is calculated based on the seasonal space cooling / heating efficiency “η” values of the COMMISSION REGULATION (EU) 2016/2281. SEER, SCOP = (η + Correction) × PEF.