Models
Connect the Hydrokit to your VRF system, together with other indoor units
Total system performs high energy efficiency by this heat recovering operation, and it gives an advantage for sustainability related assessment methods, such as BREEAM in UK.
- Only with 3-Pipe ECOi EX MF3 Series outdoor units
- Remote controller CZ-RTC5B common use with DX coil indoor units ECOi and PACi
Basic principle and advantage
Hydrokit module provides hot water by using waste heat that is recovered from standard air-conditioning indoor unit in cooling mode.
Hydrokit control function / CZ-RTC5B
- CZ-RTC5B is updated version from CZ-RTC3. It can be used for hydrokit and also normal indoor unit. CZ-RTC5B checks the type of connected unit and switch hydrokit or air conditioner style of display automatically
- Operating mode on hydrokit style to be set at initial setting of the system from following modes: tank mode or air conditioning mode
Specifications
Hydrokit for ECOi, water at 45°C - R410A | SINGLE PHASE | |||
---|---|---|---|---|
8.0 kW | 12.5 kW | |||
Cooling capacity (Nominal) | kW | 8,0 | 12,5 | |
Cooling capacity (Nominal) | kW | 8,0 | 12,5 | |
Heating capacity (Nominal) | kW | 9,0 | 14,0 | |
Heating capacity (Nominal) | kW | 9,0 | 14,0 | |
Power supply (Voltage) | V | 230 | 230 | |
Power supply (Phase) | Single phase | Single phase | ||
Power supply (Frequency) | Hz | 50 | 50 | |
Cooling capacity (Nominal) | kW | 8,0 | 12,5 | |
Heating capacity (Nominal) | kW | 9,0 | 14,0 | |
Maximum temperature | °C | ~45 / ~65 (1) | ~45 / ~65 (1) | |
Dimension (Height) | mm | 892 | 892 | |
Dimension (Width) | mm | 502 | 502 | |
Dimension (Depth) | mm | 353 | 353 | |
Water pipe connector | Inch | R 1 | R 1 | |
Water pump (built-in) | DC motor (A class) | DC motor (A class) | ||
Water flow rate (Cool) | L/min | 22,90 | 35,80 | |
Water flow rate (Heat) | L/min | 25,80 | 40,10 | |
Piping diameter (Drain) | mm | 15 ~ 17 (inner size) | 15 ~ 17 (inner size) | |
Operating range (Cool ambient -Min) | °C | +10 | +10 | |
Operating range (Cool ambient -Max) | °C | +43 | +43 | |
Operating range (Cool water -Min) | °C | +5 | +5 | |
Operating range (Cool water -Max) | °C | +20 | +20 | |
Operating range (Heat ambient -Min) | °C | -20 | -20 | |
Operating range (Heat ambient -Max) | °C | +43 | +43 | |
Operating range (Heat water -Min) | °C | +25 | +25 | |
Operating range (Heat water -Max) | °C | +45 | +45 |
Connectable system: 3-Pipe (heat recovery type) VRF System (system capable up to 48HP).
Maximum indoor ratio (connectable hydrokit module capacity ratio): Total indoor unit + Hydrokit capacity: up to 130% (** ~ **% vs total outdoor unit capacity).
1) Maximum 45°C by refrigerant circuit (heat pump cycle), over 45°C is provided by electric heater operation.