Fan coils - Wall-mounted (AC)

New range of fan coils. Designed to fit with your environment and enhance comfort

Panasonic introduces the new range of fan coils.

The key to this range is to provide performance and comfort and the ability to fit seamlessly within your environment.

Designed with user in mind, perfectly designed to adapt to any installation. Providing comfort to hotels, shops, restaurants, offices or residential applications.

Technical focus.
· 4 sizes
· Cooling capacity from 1,0 to 3,9kW
· Heating capacity from 1,4 to 4,1kW
· Version: 2-pipes, AC fan

Main features and accessories.
· 2 way or 3 way valve ON/OFF
· 3-speed AC fan motor
· Silent unit for optimum customer comfort
· Aesthetic design suitable for residential and hotel applications
· Compatible with IR controller (supplied with IR versions)
· Coil with hydrophilic fins to improve the condensate flow

The reasons to choose Panasonic as your partner

Explore the new range of fan coils

Specifications

See all
Fan coils - Wall-mounted (AC) SINGLE PHASE
1.7 kW 2.4 kW 3.5 kW 3.9 kW
2-pipe PAW-FC2A-K007 PAW-FC2A-K009 PAW-FC2A-K018 PAW-FC2A-K022
2-pipe - With IR controller PAW-FC2A-K007IR PAW-FC2A-K009IR PAW-FC2A-K018IR PAW-FC2A-K022IR
Total cooling capacity - 2-pipe (Lo) (1) kW 1,0 1,6 2,8 2,9
Total cooling capacity - 2-pipe (Med) (1) kW 1,3 1,7 3,0 3,1
Total cooling capacity - 2-pipe (Hi) (1) kW 1,7 2,4 3,5 3,9
Sensible cooling capacity - 2-pipe (Lo) (1) kW 0,7 1,2 2,1 2,3
Sensible cooling capacity - 2-pipe (Med) (1) kW 1,0 1,3 2,3 2,5
Sensible cooling capacity - 2-pipe (Hi) (1) kW 1,2 1,9 2,7 3,1
Water flow - 2-pipe (Cooling) (Lo) l/h 172 270 483 502
Water flow - 2-pipe (Cooling) (Med) l/h 231 291 508 535
Water flow - 2-pipe (Cooling) (Hi) l/h 287 418 609 669
Water pressure drop - 2-pipe (Cooling) (Lo) kPa 18,6 18,5 34,6 37,2
Water pressure drop - 2-pipe (Cooling) (Med) kPa 24,9 27,0 41,3 33,7
Water pressure drop - 2-pipe (Cooling) (Hi) kPa 30,9 40,0 55,6 45,2
Heating capacity - 2-pipe (Lo) (2) kW 1,4 1,7 2,9 3,1
Heating capacity - 2-pipe (Med) (2) kW 1,7 2,0 3,2 3,7
Heating capacity - 2-pipe (Hi) (2) kW 2,0 2,7 4,0 4,4
Sound levels . . . .
Sound power (Lo) dB(A) 45 47 49 53
Sound power (Med) dB(A) 49 52 53 57
Sound power (Hi) dB(A) 51 57 56 63
Sound pressure (Lo) (3) dB(A) 30 32 39 39
Sound pressure (Med) (3) dB(A) 33 36 41 43
Sound pressure (Hi) (3) dB(A) 35 40 43 48
Fan data . . . .
Number of fans 1 1 1 1
Air flow (Low) m³/h 282 367 532 617
Air flow (Medium) m³/h 321 413 592 709
Air flow (High) m³/h 360 551 680 850
Filter G1 G1 G1 G1
Electrical data . . . .
Power supply (Voltage) V 230 230 230 230
Power supply (Phase) Single phase Single phase Single phase Single phase
Power supply (Frequency) Hz 50 50 50 50
Fuse rating A 3 3 3 3
Power consumption (Lo) W 39 30 44 50
Power consumption (Med) W 42 47 50 55
Power consumption (Hi) W 62 59 55 70
Fan coils water connections . . . .
Type of water connections Female gas threaded Female gas threaded Female gas threaded Female gas threaded
Water connections - 2-pipe Inch 1/2 1/2 1/2 1/2
Dimensions and weight . . . .
Dimension (Height) mm 275 275 298 298
Dimension (Width) mm 180 180 200 200
Dimension (Depth) mm 845 845 940 940
Net weight kg 11 11 13 13

1) According to Eurovent standard. Air: 27°C DB / 19°C WB. Water in/out: 7°C / 12°C.
2) According to Eurovent standard. Air: 20°C. Water in/out: 45°C / 40°C.
3) Sound pressure considering a local of 100m³ a reverberation time of 0,5 seconds and a distance of 1m.

Complementary products