Fan coils - High Static Pressure Ducted (AC)

New range of fan coils. Designed to fit with your environment and enhance comfort

Panasonic introduces the new range of fan coils.

The key to this range is to provide performance and comfort and the ability to fit seamlessly within your environment.

Designed with user in mind, perfectly designed to adapt to any installation. Providing comfort to hotels, shops, restaurants, offices or residential applications.

Technical focus.
· 6 sizes
· Cooling capacity from 4,1 to 21,9kW
· Heating capacity from 4,7 to 21,5kW
· 5-speed AC fan motor

Main features and accessories.
· 2 and 4-pipe, left & right hand configurations
· Static pressure up to 220Pa
· Double skin insulation
· 2 way or 3 way ON/OFF valves
· Auxiliary drain pan
· Air intake with removable grid
· G3 filter

The reasons to choose Panasonic as your partner

Explore the new range of fan coils

Specifications

See all
Fan coils - High Static Pressure Ducted (AC) SINGLE PHASE
6.4 kW 14.2 kW 15.0 kW 18.6 kW 23.3 kW 27.5 kW
2-pipe - Left connection PAW-FC2A-E070L PAW-FC2A-E150L PAW-FC2A-E180L PAW-FC2A-E210L PAW-FC2A-E240L* PAW-FC2A-E270L*
2-pipe - Right connection PAW-FC2A-E070R PAW-FC2A-E150R PAW-FC2A-E180R PAW-FC2A-E210R PAW-FC2A-E240R* PAW-FC2A-E270R*
Total cooling capacity - 2-pipe (Lo) (1) kW 4,4 5,6 4,9 5,2 14,3 15,8
Total cooling capacity - 2-pipe (Med) (1) kW 5,5 11,5 11,5 13,7 19,8 23,0
Total cooling capacity - 2-pipe (Hi) (1) kW 6,4 14,2 15,0 18,6 23,3 27,5
Sensible cooling capacity - 2-pipe (Lo) (1) kW 3,1 3,9 3,7 3,5 10,3 11,0
Sensible cooling capacity - 2-pipe (Med) (1) kW 4,2 9,2 9,5 9,9 14,9 16,3
Sensible cooling capacity - 2-pipe (Hi) (1) kW 5,1 12,2 13,1 13,7 17,8 19,7
Water flow - 2-pipe (Cooling) (Lo) l/h 749 966 837 899 2.468 2.718
Water flow - 2-pipe (Cooling) (Med) l/h 951 1.979 1.979 2.357 3.410 3.951
Water flow - 2-pipe (Cooling) (Hi) l/h 1.095 2.437 2.589 3.201 4.015 4.740
Water pressure drop - 2-pipe (Cooling) (Lo) kPa 26,5 5,5 4,4 4,9 13,8 12,8
Water pressure drop - 2-pipe (Cooling) (Med) kPa 42,5 19,9 19,6 28,8 25,2 25,2
Water pressure drop - 2-pipe (Cooling) (Hi) kPa 56,2 29,3 32,0 51,5 34,2 35,3
Heating capacity - 2-pipe (Lo) (2) kW 5,4 6,2 6,3 6,1 17,2 17,9
Heating capacity - 2-pipe (Med) (2) kW 8,6 14,2 16,3 16,5 26,3 27,5
Heating capacity - 2-pipe (Hi) (2) kW 12,7 20,0 23,2 23,4 32,6 33,7
4-pipe - Left connection PAW-FC4A-E070L PAW-FC4A-E150L PAW-FC4A-E180L PAW-FC4A-E210L PAW-FC4A-E240L* PAW-FC4A-E270L*
4-pipe - Right connection PAW-FC4A-E070R PAW-FC4A-E150R PAW-FC4A-E180R PAW-FC4A-E210R PAW-FC4A-E240R* PAW-FC4A-E270R*
Total cooling capacity - 4-pipe (Lo) (1) kW 4,0 5,3 5,5 5,9 13,3 14,3
Total cooling capacity - 4-pipe (Med) (1) kW 5,4 10,1 11,2 14,4 17,7 19,9
Total cooling capacity - 4-pipe (Hi) (1) kW 6,0 11,9 13,6 18,8 20,5 23,4
Sensible cooling capacity - 4-pipe (Lo) (1) kW 2,8 3,7 3,9 4,0 9,9 10,3
Sensible cooling capacity - 4-pipe (Med) (1) kW 4,1 8,4 9,1 10,6 13,9 14,9
Sensible cooling capacity - 4-pipe (Hi) (1) kW 4,7 10,9 12,0 14,5 16,3 17,8
Water flow - 4-pipe (Cooling) (Lo) l/h 680 919 951 1.013 2.291 2.464
Water flow - 4-pipe (Cooling) (Med) l/h 924 1.739 1.928 2.478 3.053 3.427
Water flow - 4-pipe (Cooling) (Hi) l/h 1.035 2.044 2.335 3.241 3.526 4.032
Water pressure drop - 4-pipe (Cooling) (Lo) kPa 29,7 4,1 4,7 6,6 14,5 12,8
Water pressure drop - 4-pipe (Cooling) (Med) kPa 52,1 13,5 17,4 35,2 25,0 23,3
Water pressure drop - 4-pipe (Cooling) (Hi) kPa 64,4 18,4 25,0 59,1 33,0 31,5
Heating capacity - 4-pipe (Lo) (2) kW 3,7 5,3 5,3 5,3 7,2 7,2
Heating capacity - 4-pipe (Med) (2) kW 6,0 11,8 11,9 11,9 11,1 11,1
Heating capacity - 4-pipe (Hi) (2) kW 7,4 15,9 15,9 16,0 13,5 13,5
Water flow (Heating) (Lo) l/h 636 906 911 916 1.242 1.242
Water flow (Heating) (Med) l/h 1.029 2.038 2.045 2.051 1.910 1.910
Water flow (Heating) (Hi) l/h 1.266 2.746 2.745 2.747 2.329 2.329
Water pressure drop (Heating) (Lo) kPa 14,2 39,0 23,9 24,2 45,8 28,3
Water pressure drop (Heating) (Med) kPa 30,7 167,6 100,8 101,4 87,8 53,3
Water pressure drop (Heating) (Hi) kPa 43,6 293,0 174,3 174,6 120,3 72,5
Sound levels . . . . . .
Sound power return + radiated (Lo) dB(A) 54 52 54 52 65 65
Sound power return + radiated (Med) dB(A) 60 66 66 66 73 73
Sound power return + radiated (Hi) dB(A) 63 72 74 72 75 75
Sound power discharge (Lo) dB(A) 53 52 52 52 64 64
Sound power discharge (Med) dB(A) 59 64 64 64 72 72
Sound power discharge (Hi) dB(A) 62 71 71 71 75 75
Sound pressure (Lo) (3) dB(A) 33 31 31 31 44 44
Sound pressure (Med) (3) dB(A) 39 45 45 45 52 52
Sound pressure (Hi) (3) dB(A) 42 51 51 51 54 54
Fan data . . . . . .
Number of fans 1 1 1 1 1 1
Air flow - 2-pipe (Lo) m³/h 680 676 676 676 1.927 1.927
Air flow - 2-pipe (Med) m³/h 1.091 2.110 2.110 2.110 3.130 3.130
Air flow - 2-pipe (Hi) m³/h 1.562 3.197 3.197 3.197 3.923 3.923
Air flow - 4-pipe (Lo) m³/h 552 676 676 676 1.927 1.927
Air flow - 4-pipe (Med) m³/h 1.132 2.110 2.110 2.110 3.130 3.130
Air flow - 4-pipe (Hi) m³/h 1.496 3.197 3.197 3.197 3.923 3.923
Maximum external pressure Pa 110 200 200 200 220 220
Filter G3 G3 G3 G3 G3 G3
Electrical data . . . . . .
Power supply (Voltage) V 230 230 230 230 230 230
Power supply (Phase) Single phase Single phase Single phase Single phase Single phase Single phase
Power supply (Frequency) Hz 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60
Power consumption (Lo) W 132 180 180 180 420 420
Power consumption (Med) W 182 421 421 421 530 530
Power consumption (Hi) W 222 675 675 675 673 673
Fan coils water connections . . . . . .
Type of water connections Female gas threaded Gas Male threaded Gas Male threaded Gas Male threaded Gas Male threaded Gas Male threaded
Water connections - 2-pipe Inch 1/2 1 1 ¼ 1 ¼ 1 ¼ 1 ¼
Water connections - 4-pipe (Cooling) Inch 1/2 1 1 1 1 ¼ 1 ¼
Water connections - 4-pipe (Heating) Inch 1/2 3/4 3/4 3/4 3/4 3/4
Dimensions and weight . . . . . .
Dimension (Height) mm 250 375 375 375 450 450
Dimension (Width) mm 698 798 798 798 798 798
Dimension (Depth) mm 1.200 1.380 1.380 1.380 1.500 1.500
Net weight kg 42 63 65 67 76 80

1) According to Eurovent standard. Air: 27°C DB / 19°C WB. Water in/out: 7°C / 12°C.
2) Air: 20°C. Water in/out: 50°C / 45°C.
3) Informative data: Considering an hypothetical sound attenuation of the room and installation of 21dB.
Values indicated are for 50Pa external static pressure, for additional pressure characteristics, please refer the technical data manual.
* High fan speed used for capacity, water flow, sound and air flow values.

Complementary products