Fan coils - Floor Standing chassis (EC)

New range of fan coils. Designed to fit with your environment and enhance comfort

Panasonic introduces the new range of fan coils.

The key to this range is to provide performance and comfort and the ability to fit seamlessly within your environment.

Designed with user in mind, perfectly designed to adapt to any installation. Providing comfort to hotels, shops, restaurants, offices or residential applications.

Technical focus.
· Cooling capacity from 0,5 to 9,6kW
· Heating capacity from 0,6 to 13,6kW
· Low energy consumption EC fan(s)

Main features and accessories.
· 2 and 4-pipe configurations
· Left or right hand arrangements
· Ease of installation
· Very low acoustic levels
· 2 way or 3 way ON/OFF valves
· Auxiliary drain pan
· Air intake with removable grid
· G2 filter
· PAW-FC-SFS feet for floor-standing units

The reasons to choose Panasonic as your partner

Explore the new range of fan coils

Specifications

See all
Fan coils - Floor Standing chassis (EC) SINGLE PHASE
2.1 kW 2.4 kW 3.1 kW 4.2 kW 5.0 kW 5.2 kW 6.9 kW 8.8 kW
2-pipe - Left connection PAW-FC2E-P010L PAW-FC2E-P020L PAW-FC2E-P030L PAW-FC2E-P040L PAW-FC2E-P050L PAW-FC2E-P060L PAW-FC2E-P070L PAW-FC2E-P080L
2-pipe - Right connection PAW-FC2E-P010R PAW-FC2E-P020R PAW-FC2E-P030R PAW-FC2E-P040R PAW-FC2E-P050R PAW-FC2E-P060R PAW-FC2E-P070R PAW-FC2E-P080R
Total cooling capacity - 2-pipe (Lo) (1) kW 0,6 0,6 0,9 1,3 1,3 2,0 2,7 5,1
Total cooling capacity - 2-pipe (Med) (1) kW 1,2 1,4 2,1 2,9 4,0 4,5 5,9 6,5
Total cooling capacity - 2-pipe (Hi) (1) kW 2,1 2,4 3,1 4,2 5,0 5,2 6,9 8,8
Sensible cooling capacity - 2-pipe (Lo) (1) kW 0,5 0,5 0,6 1,0 1,1 1,4 2,0 3,7
Sensible cooling capacity - 2-pipe (Med) (1) kW 1,1 1,1 1,6 2,1 3,0 3,5 4,3 4,8
Sensible cooling capacity - 2-pipe (Hi) (1) kW 1,9 1,9 2,4 3,0 3,7 4,0 5,2 6,6
Water flow - 2-pipe (Cooling) (Lo) l/h 107 110 148 230 231 341 463 879
Water flow - 2-pipe (Cooling) (Med) l/h 210 237 354 506 685 767 1.008 1.111
Water flow - 2-pipe (Cooling) (Hi) l/h 356 406 532 722 743 800 1.098 1.254
Water pressure drop - 2-pipe (Cooling) (Lo) kPa 8,2 1,5 5,0 6,4 4,9 7,8 3,0 14,1
Water pressure drop - 2-pipe (Cooling) (Med) kPa 28,2 4,6 20,5 24,4 35,1 35,8 14,0 21,4
Water pressure drop - 2-pipe (Cooling) (Hi) kPa 76,9 11,0 42,1 46,3 41,0 38,8 16,6 26,6
Heating capacity - 2-pipe (Lo) (2) kW 0,8 0,9 1,0 1,4 1,7 2,3 3,8 6,2
Heating capacity - 2-pipe (Med) (2) kW 1,6 1,9 2,2 3,0 5,2 5,9 7,3 8,0
Heating capacity - 2-pipe (Hi) (2) kW 2,9 3,3 3,4 5,3 5,5 6,1 8,2 9,3
4-pipe - Left connection PAW-FC4E-P010L PAW-FC4E-P020L PAW-FC4E-P030L PAW-FC4E-P040L PAW-FC4E-P050L PAW-FC4E-P060L PAW-FC4E-P070L PAW-FC4E-P080L
4-pipe - Right connection PAW-FC4E-P010R PAW-FC4E-P020R PAW-FC4E-P030R PAW-FC4E-P040R PAW-FC4E-P050R PAW-FC4E-P060R PAW-FC4E-P070R PAW-FC4E-P080R
Total cooling capacity - 4-pipe (Lo) (1) kW 0,5 0,6 0,8 1,2 1,2 1,8 2,6 5,0
Total cooling capacity - 4-pipe (Med) (1) kW 1,1 1,2 1,9 2,7 3,6 4,1 5,1 6,2
Total cooling capacity - 4-pipe (Hi) (1) kW 1,9 2,2 2,9 4,0 4,6 4,9 6,4 9,6
Sensible cooling capacity - 4-pipe (Lo) (1) kW 0,4 0,4 0,6 0,9 1,0 1,2 1,9 3,6
Sensible cooling capacity - 4-pipe (Med) (1) kW 0,9 1,0 1,5 1,9 2,8 3,2 3,8 4,6
Sensible cooling capacity - 4-pipe (Hi) (1) kW 1,7 1,8 2,2 2,8 3,5 3,8 4,8 7,2
Water flow - 4-pipe (Cooling) (Lo) l/h 92 97 129 205 212 306 443 855
Water flow - 4-pipe (Cooling) (Med) l/h 185 206 321 457 625 707 886 1.070
Water flow - 4-pipe (Cooling) (Hi) l/h 327 375 493 681 686 749 977 1.242
Water pressure drop - 4-pipe (Cooling) (Lo) kPa 5,8 1,3 4,0 6,3 2,5 5,1 3,5 22,9
Water pressure drop - 4-pipe (Cooling) (Med) kPa 20,1 3,7 9,2 29,6 17,9 24,3 13,6 33,9
Water pressure drop - 4-pipe (Cooling) (Hi) kPa 59,2 9,7 19,7 60,1 21,3 27,2 16,5 44,3
Heating capacity - 4-pipe (Lo) (2) kW 0,4 0,6 1,0 1,2 1,6 1,4 2,5 4,5
Heating capacity - 4-pipe (Med) (2) kW 0,8 0,9 1,4 2,0 2,4 2,9 3,4 5,9
Heating capacity - 4-pipe (Hi) (2) kW 1,4 1,5 1,8 2,8 2,5 3,1 3,6 6,9
Water flow (Heating) (Lo) l/h 76 95 166 204 267 233 434 767
Water flow (Heating) (Med) l/h 140 161 243 350 416 503 583 1.011
Water flow (Heating) (Hi) l/h 235 255 304 483 438 531 614 1.194
Water pressure drop (Heating) (Lo) kPa 1,8 1,4 5,3 15,6 11,9 11,5 61,5 42,1
Water pressure drop (Heating) (Med) kPa 4,0 3,8 9,7 41,8 26,3 43,6 103,8 69,7
Water pressure drop (Heating) (Hi) kPa 8,4 9,4 14,1 76,3 28,9 48,1 113,9 95,1
Sound levels . . . . . . . .
Sound power (Lo) dB(A) 34 34 31 29 30 32 40 51
Sound power (Med) dB(A) 47 47 50 44 51 54 54 56
Sound power (Hi) dB(A) 60 60 59 52 57 58 59 64
Sound pressure (Lo) (3) dB(A) 25 25 22 20 21 23 31 42
Sound pressure (Med) (3) dB(A) 38 38 41 35 42 45 45 47
Sound pressure (Hi) (3) dB(A) 51 51 50 43 48 49 50 55
Fan data . . . . . . . .
Number of fans 1 1 1 2 2 2 2 3
Air flow - 2-pipe (Lo) m³/h 108 98 145 170 203 245 350 685
Air flow - 2-pipe (Med) m³/h 228 234 380 412 645 737 850 927
Air flow - 2-pipe (Hi) m³/h 417 413 585 678 816 912 1.050 1.398
Air flow - 4-pipe (Lo) m³/h 91 84 123 148 185 205 329 660
Air flow - 4-pipe (Med) m³/h 199 200 342 369 587 668 798 884
Air flow - 4-pipe (Hi) m³/h 379 380 540 627 646 716 894 1.079
Filter G2 G2 G2 G2 G2 G2 G2 G2
Electrical data . . . . . . . .
Power supply (Voltage) V 230 230 230 230 230 230 230 230
Power supply (Phase) Single phase Single phase Single phase Single phase Single phase Single phase Single phase Single phase
Power supply (Frequency) Hz 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60
Power consumption - 2-pipe (Lo) W 5 5 4 2 4 2 11 23
Power consumption - 2-pipe (Med) W 11 13 16 13 24 30 44 42
Power consumption - 2-pipe (Hi) W 41 41 42 43 46 54 77 108
Power consumption - 4-pipe (Lo) W 5 5 6 2 2 2 11 22
Power consumption - 4-pipe (Med) W 11 13 15 12 23 28 43 41
Power consumption - 4-pipe (Hi) W 39 40 40 42 44 52 75 116
Fan coils water connections . . . . . . . .
Type of water connections Female gas threaded Female gas threaded Female gas threaded Female gas threaded Female gas threaded Female gas threaded Female gas threaded Female gas threaded
Water connections - 2-pipe Inch 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4
Water connections - 4-pipe (Cooling) Inch 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4
Water connections - 4-pipe (Heating) Inch 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Dimensions and weight . . . . . . . .
Dimension (Height) mm 477 766 477 477 477 477 575 575
Dimension (Width) mm 225 225 225 225 225 225 225 225
Dimension (Depth) mm 766 477 951 1.136 1.321 1.506 1.319 1.506
Weight - 2-pipe kg 19 19 22 27 30 35 35 47
Weight - 4-pipe kg 20 20 23 29 32 37 37 49

1) According to Eurovent standard. Air: 27°C DB / 19°C WB. Water in/out: 7°C / 12°C.
2) Air: 20°C. Water in/out: 50°C / 45°C.
3) The sound pressure levels are based on (NR) characteristics of a room having volume of 100m³ with reverberation of 0,5 seconds.
* Without support feet.