Technical focus.
· Cooling capacity from 0,7 to 8,1kW
· Heating capacity from 0,7 to 10,3kW
· 5-speed AC fan motor(s)

Main features and accessories.
· 2 and 4-pipe configurations
· Left or right hand arrangements
· Ease of installation
· Very low acoustic levels
· 2 way or 3 way ON/OFF valves
· Auxiliary drain pan
· Air intake with removable grid
· G2 filter
· PAW-FC-SFS feet for floor-standing units

The reasons to choose Panasonic as your partner

Explore the new range of fan coils

Specifications

See all
Fan coils - Floor Standing chassis (AC) SINGLE PHASE
1.5 kW 1.7 kW 2.5 kW 3.2 kW 4.6 kW 5.8 kW 7.3 kW 8.1 kW
2-pipe - Left connection PAW-FC2A-P010L PAW-FC2A-P020L PAW-FC2A-P030L PAW-FC2A-P040L PAW-FC2A-P050L PAW-FC2A-P060L PAW-FC2A-P070L PAW-FC2A-P080L
2-pipe - Right connection PAW-FC2A-P010R PAW-FC2A-P020R PAW-FC2A-P030R PAW-FC2A-P040R PAW-FC2A-P050R PAW-FC2A-P060R PAW-FC2A-P070R PAW-FC2A-P080R
Total cooling capacity - 2-pipe (Lo) (1) kW 0,7 0,7 1,0 1,2 1,7 2,7 3,4 4,6
Total cooling capacity - 2-pipe (Med) (1) kW 1,0 1,2 2,0 2,4 3,2 4,6 6,1 6,1
Total cooling capacity - 2-pipe (Hi) (1) kW 1,5 1,7 2,5 3,2 4,6 5,8 7,3 8,1
Sensible cooling capacity - 2-pipe (Lo) (1) kW 0,5 0,6 0,8 0,9 1,2 1,9 2,4 3,4
Sensible cooling capacity - 2-pipe (Med) (1) kW 0,8 0,9 1,5 1,8 2,2 3,3 4,3 4,6
Sensible cooling capacity - 2-pipe (Hi) (1) kW 1,1 1,3 1,9 2,3 3,3 4,5 5,1 6,3
Water flow - 2-pipe (Cooling) (Lo) l/h 124 127 172 206 296 466 587 798
Water flow - 2-pipe (Cooling) (Med) l/h 172 213 341 413 544 784 1.058 1.048
Water flow - 2-pipe (Cooling) (Hi) l/h 250 289 430 547 798 1.003 1.252 1.400
Water pressure drop - 2-pipe (Cooling) (Lo) kPa 10,7 1,9 6,3 5,4 7,5 13,9 4,8 11,9
Water pressure drop - 2-pipe (Cooling) (Med) kPa 19,5 3,9 19,3 17,1 22,8 37,4 15,4 19,3
Water pressure drop - 2-pipe (Cooling) (Hi) kPa 39,2 6,3 28,8 28,0 46,9 60,2 21,5 32,5
Heating capacity - 2-pipe (Lo) (2) kW 0,9 0,9 1,3 1,4 2,1 3,1 4,3 5,9
Heating capacity - 2-pipe (Med) (2) kW 1,4 1,5 2,4 2,9 4,1 5,3 7,9 8,1
Heating capacity - 2-pipe (Hi) (2) kW 2,0 2,2 3,1 4,0 5,7 7,1 9,3 11,6
4-pipe - Left connection PAW-FC4A-P010L PAW-FC4A-P020L PAW-FC4A-P030L PAW-FC4A-P040L PAW-FC4A-P050L PAW-FC4A-P060L PAW-FC4A-P070L PAW-FC4A-P080L
4-pipe - Right connection PAW-FC4A-P010R PAW-FC4A-P020R PAW-FC4A-P030R PAW-FC4A-P040R PAW-FC4A-P050R PAW-FC4A-P060R PAW-FC4A-P070R PAW-FC4A-P080R
Total cooling capacity - 4-pipe (Lo) (1) kW 0,7 0,6 1,0 1,1 1,7 2,6 3,3 4,5
Total cooling capacity - 4-pipe (Med) (1) kW 0,9 1,1 1,9 2,3 3,0 4,4 5,9 5,9
Total cooling capacity - 4-pipe (Hi) (1) kW 1,3 1,6 2,4 3,0 4,3 5,6 6,9 8,0
Sensible cooling capacity - 4-pipe (Lo) (1) kW 0,5 0,5 0,8 0,8 1,2 1,8 2,3 3,3
Sensible cooling capacity - 4-pipe (Med) (1) kW 0,7 0,8 1,5 1,7 2,2 3,2 4,2 4,4
Sensible cooling capacity - 4-pipe (Hi) (1) kW 1,0 1,2 1,8 2,2 3,1 4,3 4,9 6,2
Water flow - 4-pipe (Cooling) (Lo) l/h 114 109 165 194 284 449 575 775
Water flow - 4-pipe (Cooling) (Med) l/h 159 192 327 388 522 756 1.019 1.020
Water flow - 4-pipe (Cooling) (Hi) l/h 225 268 414 517 748 967 1.193 1.380
Water pressure drop - 4-pipe (Cooling) (Lo) kPa 8,3 1,5 3,0 6,4 4,2 10,2 5,9 19,3
Water pressure drop - 4-pipe (Cooling) (Med) kPa 15,2 3,4 9,5 22,3 12,8 27,7 17,9 31,1
Water pressure drop - 4-pipe (Cooling) (Hi) kPa 29,0 5,6 14,4 36,8 25,1 44,5 24,4 53,6
Heating capacity - 4-pipe (Lo) (2) kW 0,5 0,6 1,0 0,9 1,5 1,9 2,7 3,9
Heating capacity - 4-pipe (Med) (2) kW 0,7 0,9 1,4 1,6 2,3 2,9 3,6 5,6
Heating capacity - 4-pipe (Hi) (2) kW 1,0 1,1 1,6 2,1 3,0 3,7 4,3 7,1
Water flow (Heating) (Lo) l/h 79 100 164 160 251 325 456 673
Water flow (Heating) (Med) l/h 127 146 232 273 401 505 626 963
Water flow (Heating) (Hi) l/h 178 190 274 354 508 633 736 1.226
Water pressure drop (Heating) (Lo) kPa 1,9 1,5 5,1 9,2 10,7 20,3 67,2 33,1
Water pressure drop (Heating) (Med) kPa 3,5 3,2 9,0 26,5 24,6 43,9 117,9 63,7
Water pressure drop (Heating) (Hi) kPa 5,6 5,3 11,9 42,7 29,5 52,9 137,8 75
Sound levels . . . . . . . .
Sound power (Lo) dB(A) 33 31 30 30 34 38 43 50
Sound power (Med) dB(A) 40 43 45 44 46 51 56 55
Sound power (Hi) dB(A) 49 50 52 51 56 58 61 64
Sound pressure (Lo) (3) dB(A) 24 22 21 21 25 29 34 41
Sound pressure (Med) (3) dB(A) 31 34 36 35 37 42 47 46
Sound pressure (Hi) (3) dB(A) 40 41 43 42 47 49 52 55
Fan data . . . . . . . .
Number of fans 1 1 1 2 2 2 2 3
Air flow - 2-pipe (Lo) m³/h 111 105 138 173 253 350 480 660
Air flow - 2-pipe (Med) m³/h 190 179 274 357 486 640 893 936
Air flow - 2-pipe (Hi) m³/h 283 265 390 499 716 933 1.064 1.397
Air flow - 4-pipe (Lo) m³/h 95 89 132 162 242 334 470 634
Air flow - 4-pipe (Med) m³/h 168 161 263 335 466 614 859 905
Air flow - 4-pipe (Hi) m³/h 253 241 369 467 671 885 1.012 1.370
Filter G2 G2 G2 G2 G2 G2 G2 G2
Electrical data . . . . . . . .
Power supply (Voltage) V 230 230 230 230 230 230 230 230
Power supply (Phase) Single phase Single phase Single phase Single phase Single phase Single phase Single phase Single phase
Power supply (Frequency) Hz 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60
Power consumption - 2-pipe (Lo) W 13 10 16 15 28 37 53 90
Power consumption - 2-pipe (Med) W 24 18 37 37 55 75 100 112
Power consumption - 2-pipe (Hi) W 36 29 45 56 72 105 147 188
Power consumption - 4-pipe (Lo) W 13 10 16 15 28 37 53 90
Power consumption - 4-pipe (Med) W 24 18 37 37 54 74 99 112
Power consumption - 4-pipe (Hi) W 36 28 44 55 70 104 145 188
Fan coils water connections . . . . . . . .
Type of water connections Female gas threaded Female gas threaded Female gas threaded Female gas threaded Female gas threaded Female gas threaded Female gas threaded Female gas threaded
Water connections - 2-pipe Inch 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4
Water connections - 4-pipe (Cooling) Inch 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4
Water connections - 4-pipe (Heating) Inch 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Dimensions and weight . . . . . . . .
Dimension (Height) mm 477 766 477 477 477 477 575 575
Dimension (Width) mm 225 225 225 225 225 225 225 225
Dimension (Depth) mm 766 477 951 1.136 1.321 1.506 1.319 1.506
Weight - 2-pipe kg 19 19 22 27 30 35 35 47
Weight - 4-pipe kg 20 20 23 29 32 37 37 49

1) According to Eurovent standard. Air: 27°C DB / 19°C WB. Water in/out: 7°C / 12°C.
2) Air: 20°C. Water in/out: 50°C / 45°C.
3) The sound pressure levels are based on (NR) characteristics of a room having volume of 100m³ with reverberation of 0,5 seconds.
* Without support feet.