Models
Energy recovery ventilation with DX coil - HRPT Series for VRF
It’s an ideal solution to achieve the highest energy certification for buildings in the tertiary, industrial and collective residential sectors including centralized condominium systems.
- Dual flow ventilation with EC fan, featuring high efficiency heat recovery (>85% η)
- 5 model line-up is available with air flow rates of 480, 800, 1.100, 1.500 and 1.750m³/h
- 2 types of polypropylene heat exchanger (high efficiency and sensible) with counter-current flows and integrated bypass as standard
- Modbus connection available
Specifications
Energy recovery ventilation with DX coil - HRPT Series | SINGLE PHASE | THREE PHASE | |||||
---|---|---|---|---|---|---|---|
500 m³/h | 800 m³/h | 1.500 m³/h | 1.700 m³/h | 2.450 m³/h | |||
Indoor unit with high-efficiency heat exchanger | PAW-HRPT40HX | PAW-HRPT80HX | PAW-HRPT120HX | PAW-HRPT160HX | PAW-HRPT200HX | ||
Indoor unit with sensible heat exchanger | PAW-HRPT40 | PAW-HRPT80 | PAW-HRPT120 | PAW-HRPT160 | PAW-HRPT200 | ||
Heat recovery temperature efficiency cooling (1) | % | 63,4 (HX) / 84,6 | 60,0 (HX) / 84,3 | 61,4 (HX) / 84,8 | 62,2 (HX) / 84,7 | 59,4 (HX) / 83,8 | |
Heat recovery temperature efficiency heating (1) | % | 76,7 (HX) / 84,9 | 73,5 (HX) / 84,7 | 75,0 (HX) (HX) / 85,2 | 76,0 (HX) / 85,1 | 73,2 (HX) / 84,2 | |
Heat recovery enthalpy efficiency cooling (1) | % | 52,3 (HX) | 47,8 (HX) | 49,5 | 50,0 (HX) | 46,8 (HX) | |
Heat recovery enthalpy efficiency heating (1) | % | 53,2 (HX) | 49,2 (HX) | 50,7 (HX) | 51,2 (HX) | 48,3 (HX) | |
Common data | . | . | . | . | . | ||
Power supply (Voltage) | V | 230 | 230 | 230 | 230 | 380 | |
Power supply (Phase) | Single phase | Single phase | Single phase | Single phase | Three phase | ||
Power supply (Frequency) | Hz | 50 | 50 | 50 | 50 | 50 | |
DX coil total / sensible capacity cooling (2) | kW | 3,0 / 2,4 | 6,0 / 4,1 | 8,0 / 5,5 | 10,0 / 7,1 | 12,5 / 8,6 | |
DX coil total / sensible capacity heating (2) | kW | 3,2 | 6,2 | 8,3 | 11,0 | 12,8 | |
Maximum input current | A | 1,5 | 2,2 | 4,1 | 4,4 | 3,3 | |
Sound pressure | dB(A) | 41 (@1m) / 35 (@3m) | 51 (@1m) / 43 (@3m) | 42 (@1m) / 36 (@3m) | 49 (@1m) / 41 (@3m) | 57 (@1m) / 49 (@3m) | |
Air flow (Nominal) | m³/h | 400 | 800 | 1.200 | 1.600 | 2.000 | |
External static pressure (High) | Pa | 150 | 150 | 150 | 150 | 150 | |
Dimension (Height) | mm | 286 | 425 | 425 | 425 | 425 | |
Dimension (Width) | mm | 1.003 | 1.226 | 1.628 | 2.030 | 2.030 | |
Dimension (Depth) | mm | 1475 | 1.878 | 1.878 | 1.720 | 1.878 | |
Net weight | kg | 70 (HX) / 66 | 114 (HX) / 110 | 150 (HX) / 145 | 184 (HX) / 180 | 194 (HX) / 190 | |
Piping diameter (Liquid) | Inch (mm) | 1/4 (6,35) | 1/4 (6,35) | 3/8 (9,52) | 3/8 (9,52) | 3/8 (9,52) | |
Piping diameter (Gas) | Inch (mm) | 1/2 (12,70) | 1/2 (12,70) | 5/8 (15,88) | 5/8 (15,88) | 5/8 (15,88) |
1) Data refers to the following conditions (UNI EN 13141-7): nominal air flow, heating external air 5°C with 72% r. / expelled air 25°C with 28% r. - cooling 35°C with 40% / expelled air 27°C with 48%.
2) Data refers to the following conditions: nominal air flow, cooling inlet coil summer 27°C with 48% / heating inlet coil winter 20°C with 50% r.