2-Pipe ECO G GE3 series

The GE3 Series has a top level of seasonal efficiency in this category

In addition, this product fits with special needs for commercial application thanks to DHW priority setting and auto pump down functions.


* 50 ~ 200% only when one outdoor unit is installed. In other cases 50 ~ 130%.

ECO G, the advanced Gas Driven VRF

Specifications

See all
2-Pipe ECO G GE3 series SINGLE PHASE
16 kW 20 kW 25 kW 30 kW
Refrigeration load Pdesign (Cooling) kW 45,0 56,0 71,0 85,0
Cooling ηsc (LOT21) (1) % 220,60 219,30 240,10 229,30
Hot water in cooling mode (at 65°C outlet) kW 23,60 29,10 36,40 46,00
Max COP in hot water W/W 1,55 1,55 1,49 1,47
Gas consumption cooling kW 41,10 52,10 67,20 84,10
Heating capacity (Standard) kW 50,0 63,0 80,0 95,0
Heating capacity (Low temperature) kW 53,0 67,0 78,0 90,0
Refrigeration load Pdesign (Heating) kW 37,0 53,0 60,0 65,0
Heating ηsh (LOT21) (1) % 150,60 143,70 146,90 151,30
Gas consumption heating (Standard) kW 38,00 51,10 68,60 75,30
Gas consumption heating (Low temperature) kW 45,40 62,70 60,70 73,90
Starter amperes A 30 30 30 30
Sound power (Normal mode) dB(A) 80 80 84 84
Sound power (Silent mode) dB(A) 77 77 81 81
Piping diameter (Fuel gas) Inch (mm) 19,05 (R3/4) 19,05 (R3/4) 19,05 (R3/4) 19,05 (R3/4)
Piping diameter (Exhaust drain port) mm 25 25 25 25
Piping diameter (Hot water supply in/out) Rp3/4 (Nut, thread) Rp3/4 (Nut, thread) Rp3/4 (Nut, thread) Rp3/4 (Nut, thread)
Elevation difference (in/out) m 50 50 50 50
Refrigerant (R410A) / CO2 Eq. kg / T 11,50 / 24,00 11,50 / 24,00 11,50 / 24,00 11,50 / 24,00
Maximum number of connectable indoor units 26 33 41 50

1) SEER/SCOP is calculated based on the seasonal space cooling/heating efficiency “η” values of the COMMISSION REGULATION (EU) 2016/2281.

Hot water take out function added, EU safety regulation standard cleared. 25HP chassis enlarged due to specification improvement. Pre-coat corrosion fin. Auto pump down function.