Aquarea Air Smart fan coil ducted

Aquarea Air Smart fan coil ducted

High efficiency ducted fan coil for high comfort and quiet operation thanks to self modulating air flow control. Designed to provide both heating and cooling in one compact unit, they maximise energy savings when combined with an Aquarea Heat Pumps.

Specifications

See all
Aquarea Air Smart fan coil ducted SINGLE PHASE
1.40 kW 2.10 kW 2.60 kW 3.30 kW 4.45 kW 1.88 kW 2.14 kW 2.97 kW 3.48 kW 5.31 kW
Type Ducted thin Ducted thin Ducted thin Ducted thin Ducted thin Ducted Ducted Ducted Ducted Ducted
Model P-FTN15 P-FTN20 P-FTN25 P-FTN35 P-FTN45 P-FSN20 P-FSN25 P-FSN35 P-FSN45 P-FSN55
Fan speed (1) Min / Med / Max Min / Med / Max Min / Med / Max Min / Med / Max Min / Med / Max Min / Med / Max Min / Med / Max Min / Med / Max Min / Med / Max Min / Med / Max
Total cooling capacity (Min) (2) kW 0,66 1,01 1,23 1,47 1,72 0,82 1,27 1,53 1,81 1,82
Total cooling capacity (Med) (2) kW 1,14 1,84 2,17 2,4 2,8 1,37 1,86 2,38 3,22 3,97
Total cooling capacity (Max) (2) kW 1,4 2,1 2,6 3,3 4,45 1,88 2,14 2,97 3,48 5,31
Sensible capacity (Min) (2) kW 0,46 0,7 0,88 1,06 1,23 0,61 0,93 1,17 1,33 1,33
Sensible capacity (Med) (2) kW 0,84 1,27 1,56 1,77 2,33 0,96 1,43 1,98 2,58 2,75
Sensible capacity (Max) (2) kW 1,05 1,5 2,1 2,45 3,2 1,48 1,56 2,92 2,95 3,65
Water flow cooling (Min) (2) l/h 113 173 211 251 295 141 218 262 310 312
Water flow cooling (Med) (2) l/h 195 315 373 412 481 235 319 408 552 680
Water flow cooling (Max) (2) l/h 270 405 510 610 805 322 367 509 596 910
Water pressure drop cooling (Min) (2) kPa 1 2 4 2 2 9,2 9,9 2,4 9 4,1
Water pressure drop cooling (Med) (2) kPa 3 5 10 5 6 11,8 14,9 2,8 12,6 16,1
Water pressure drop cooling (Max) (2) kPa 5 8 17 11 14 15,7 19,4 2,9 14,6 27,2
Heating capacity (Min) (3) kW 0,68 1,01 1,32 1,63 1,89 0,9 1,36 1,81 1,96 1,95
Heating capacity (Med) (3) kW 1,32 1,8 2,32 2,76 3,98 1,48 2,04 2,63 3,77 4,23
Heating capacity (Max) (3) kW 1,65 2,1 2,86 3,71 5,2 1,98 2,54 3,45 4,46 5,73
Water flow heating (Min) (3) l/h 115 170 235 288 329 159 239 319 346 347
Water flow heating (Med) (3) l/h 222 303 410 486 692 261 360 464 665 754
Water flow heating (Max) (3) l/h 310 440 540 730 880 349 448 608 787 1.025
Water pressure drop heating (Min) (3) kPa 1 2 4 2 3 51 10,3 2,6 9,2 4
Water pressure drop heating (Med) (3) kPa 3 5 11 6 10 12 15,6 2,8 15,6 16,4
Water pressure drop heating (Max) (3) kPa 6 9 18 13 15 16,3 21,5 2,9 18,4 29,3
Sound levels . . . . . . . . . .
Sound power (Min) dB(A) 42 44 45 46 47 46 46 46 47 48
Sound power (Med) dB(A) 47 51 52 54 54 54 54 54 55 55
Sound power (Max) dB(A) 53 58 58 60 61 58 58 57 58 60
Ventilation . . . . . . . . . .
Number of fans 1 1 2 2 3 1 1 2 2 3
Air flow (Min) m³/h 90 140 190 230 250 120 180 240 260 280
Air flow (Med) m³/min 200 290 390 450 610 260 350 440 550 750
Air flow (Max) m³/h 290 390 550 680 870 390 560 730 905 1.150
Single zone air flow (Min) m³/h 100 90 120 110 140 90 130 110 140 140
Electrical data . . . . . . . . . .
Power supply (Voltage) V 230 230 230 230 230 230 230 230 230 230
Power supply (Phase) Single phase Single phase Single phase Single phase Single phase Single phase Single phase Single phase Single phase Single phase
Power supply (Frequency) Hz 50 50 50 50 50 50 50 50 50 50
Consumption (Min) W 14 22 26 33 38 6 7 8 13 14
Consumption (Med) W 32 55 65 80 115 11 14 16 30 42
Consumption (Max) W 80 140 160 160 230 24 31 34 38 85
Degree of protection IP X0 X0 X0 X0 X0 X0 X0 X0 X0 X0
Fan coils water connections . . . . . . . . . .
Hydraulic connections type Eurokonus Eurokonus Eurokonus Eurokonus Eurokonus Eurokonus Eurokonus Eurokonus Eurokonus Eurokonus
Hydraulic connections Inch ¾ ¾ ¾ ¾ ¾ ¾ ¾ ¾ ¾ ¾
Condensate drainage connection mm 20 20 20 20 20 20 20 20 20 20
Intake air connection (base x height) mm 460 x 100 660 x 100 860 x 100 1.060 x 100 1.320 x 100 460 x 150 660 x 150 860 x 150 1.060 x 150 1.320 x 150
Return air connection (base x height) mm 510 x 100 710 x 100 910 x 100 1.110 x 100 1.370 x 100 510 x 150 710 x 150 910 x 150 1.110 x 150 1.370 x 150
Dimensions and weight . . . . . . . . . .
Dimension (Height) mm 185 185 185 185 185 240 240 240 240 240
Dimension (Width) mm 590 790 990 1.190 1.440 590 790 990 1.190 1.440
Dimension (Depth) mm 575 575 575 575 575 695 695 695 695 695
Net weight kg 30 41 45 54 65 32 43 47 56 67

1) Fan standard factory set speeds.
2) According to Eurovent standard. Air: 27°C DB/19°C WB, chilled water: 7°C/12°C (for water pressure drop data: pressure loss by corresponding nominal flow).
3) According to Eurovent standard. Air: 20°C, hot water: 45°C/40°C. Pressure loss by corresponding nominal flow (for water pressure drop data: pressure loss by corresponding nominal flow)
.