Specifications
AHU connection kit for PACi NX and PACi | SINGLE PHASE | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
3.6 kW | 5.0 kW | 6.0 kW | 7.1 kW | 10.0 kW | 12.5 kW | 14.0 kW | 19.5 kW | 23.2 kW | |||
Reference | PAW-280PAH3M-1 | PAW-280PAH3M-1 | PAW-280PAH3M-1 | PAW-280PAH3M-1 | PAW-280PAH3M-1 | PAW-280PAH3M-1 | PAW-280PAH3M-1 | PAW-280PAH3M-1 (x2) | PAW-280PAH3M-1 (x2) | ||
Cooling capacity (Nominal) | kW | 3,6 | 5,0 | 6,0 | 7,1 | 10,0 | 12,5 | 14,0 | 19,5 | 23,2 | |
Heating capacity (Nominal) | kW | 4,0 | 5,6 | 7,0 | 8,0 | 11,2 | 14,0 | 16,0 | 22,4 | 28,0 | |
Air flow (Cool Hi) | m³/min | 540 | 630 | 780 | 780 | 900 | 1.140 | 1.200 | 2.160 | 2.280 | |
Air flow (Cool Lo) | m³/min | 870 | 990 | 1.320 | 1.320 | 2.160 | 2.280 | 2.400 | 4.320 | 5.040 | |
Dimension (Height) | mm | 500 | 500 | 500 | 500 | 500 | 500 | 500 | 278 | 278 | |
Dimension (Width) | mm | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 278 | 278 | |
Dimension (Depth) | mm | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 180 | 180 | |
Net weight | kg | 11,5 | 11,5 | 11,5 | 11,5 | 11,5 | 11,5 | 11,5 | 11,5 | 11,5 | |
Pipe length range (Standard) | m | 3 ~ 15 | 3 ~ 20 | 3 ~ 40 | 3 ~ 40 | 5 ~ 50 | 5 ~ 50 | 5 ~ 50 | |||
Pipe length range (Elite) | m | 3 ~ 40 | 3 ~ 40 | 3 ~ 40 | 5 ~ 50 | 5 ~ 85 | 5 ~ 85 | 5 ~ 85 | 5 ~ 90 | 5 ~ 60 | |
Elevation difference (in/out) | m | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | |
Piping diameter (Liquid) | Inch (mm) | 1/4 (6,35) | 1/4 (6,35) | 3/8 (9,52) | 3/8 (9,52) | 3/8 (9,52) | 3/8 (9,52) | 3/8 (9,52) | 3/8 (9,52) | 1/2 (12,70) | |
Piping diameter (Gas) | Inch (mm) | 1/2 (12,70) | 1/2 (12,70) | 5/8 (15,88) | 5/8 (15,88) | 5/8 (15,88) | 5/8 (15,88) | 5/8 (15,88) | 1 (25,40) | 1 (25,40) | |
Intake temperature of AHU connection kit (Cool - Min) | °C DB | 18 | 18 | 18 | 18 | 18 | 18 | 18 | 18 | 18 | |
Intake temperature of AHU connection kit (Cool - Max) | °C DB | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | |
Intake temperature of AHU connection kit (Cool - Min) | °C WB | 14 | 14 | 14 | 14 | 14 | 14 | 14 | |||
Intake temperature of AHU connection kit (Cool - Max) | °C WB | 25 | 25 | 25 | 25 | 25 | 25 | 25 | |||
Intake temperature of AHU connection kit (Heat - Min) | °C | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | |
Intake temperature of AHU connection kit (Heat - Max) | °C | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | |
Ambient temperature of outdoor unit (Standard) (Cool - Min) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | |
Ambient temperature of outdoor unit (Standard) (Cool - Max) | °C | +43 | +43 | +43 | +43 | +43 | +43 | +43 | +43 | +43 | |
Ambient temperature of outdoor unit (Standard) (Heat - Min) | °C | -15 | -15 | -15 | -15 | -15 | -15 | -15 | -15 | -15 | |
Ambient temperature of outdoor unit (Standard) (Heat - Max) | °C | +24 | +24 | +24 | +24 | +24 | +24 | +24 | +24 | +24 | |
Ambient temperature of outdoor unit (Elite) (Cool - Min) | °C | -15 | -15 | -15 | -15 | -20 | -20 | -20 | -20 | -20 | |
Ambient temperature of outdoor unit (Elite) (Cool - Max) | °C | +46 | +46 | +46 | +46 | +48 | +48 | +48 | +48 | +48 | |
Ambient temperature of outdoor unit (Elite) (Heat - Min) | °C | -20 | -20 | -20 | -20 | -20 | -20 | -20 | -20 | -20 | |