Models
AHU connection kit. 16, 28 and 56 kW for ECOi and ECO G
AHU connection kits connect ECOi and ECO G systems to air handling unit systems, using the same refrigerant circuit as the VRF system. The essential solution for hotels, offices, server rooms, or all large buildings where air quality control such as humidity control and fresh air is required.
- 3 models: 5HP (PAW-160MAH3M), 10HP (PAW-280MAH3M) and 20HP (PAW-560MAH3M)
- Durable metal casing (IP66)
- Maximum capacity/system: 80HP (224kW)
- Maximum piping length: 100m (120m equivalent)
- Maximum number of AHU connection kits: 4 units*
- CONEX Bluetooth® control built-in (CZ-RTC6BL)
- Panasonic H&C Control App available
* To be simultaneous operation controlled by one remote controller sensor.
ECO G, the advanced Gas Driven VRF
Specifications
AHU connection kit MAH3M for ECOi and ECO G | SINGLE PHASE | ||||||||
---|---|---|---|---|---|---|---|---|---|
14 kW | 28 kW | 56 kW | 84 kW | 112 kW | 140 kW | 168 kW | |||
HP | 5 HP | 10 HP | 20 HP | 30 HP | 40 HP | 50 HP | 60 HP | ||
Reference | PAW-160MAH3M | PAW-280MAH3M | PAW-560MAH3M | PAW-280MAH3M + PAW-560MAH3M | PAW-560MAH3M + PAW-560MAH3M | PAW-560MAH3M + PAW-560MAH3M + PAW-280MAH3M | PAW-560MAH3M + PAW-560MAH3M + PAW-560MAH3M | ||
Cooling capacity (Nominal) | kW | 14,0 | 28,0 | 56,0 | 84,0 | 112,0 | 140,0 | 168,0 | |
Heating capacity (Nominal) | kW | 16,0 | 31,5 | 63,0 | 95,0 | 127,0 | 155,0 | 189,0 | |
Air flow (Cool Hi) | m³/min | 2.598 | 4.998 | 10.002 | 15.000 | 19.998 | 24.996 | 30.000 | |
Air flow (Cool Lo) | m³/min | 1.140 | 3.498 | 7.002 | 10.500 | 13.998 | 17.496 | 21.000 | |
Bypass factor recommended | 0,9 | 0,9 | 0,9 | 0,9 | 0,9 | 0,9 | 0,9 | ||
Dimension (Height) | mm | 278 | 278 | 278 | 278 | 278 | 278 | 278 | |
Dimension (Width) | mm | 278 | 278 | 278 | 278 | 278 | 278 | 278 | |
Dimension (Depth) | mm | 180 | 180 | 180 | 180 | 180 | 180 | 180 | |
Net weight | kg | 3,2 | 6,3 | 6,3 | 6,3 | 6,3 | 6,3 | 6,3 | |
Pipe length range | m | 10 ~ 100 | 10 ~ 100 | 10 ~ 100 | 10 ~ 100 | 10 ~ 100 | 10 ~ 100 | 10 ~ 100 | |
Elevation difference (in/out) | m | 10 | 10 | 10 | 10 | 10 | 10 | 10 | |
Piping diameter (Liquid) | Inch (mm) | 3/8 (9,52) | 3/8 (9,52) | 5/8 (15,88) | 3/4 (19,05) | 3/4 (19,05) | 3/4 (19,05) | 3/4 (19,05) | |
Piping diameter (Gas) | Inch (mm) | 5/8 (15,88) | 7/8 (22,22) | 1 1/8 (28,58) | 1 1/4 (31,75) | 1 1/2 (38,15) | 1 1/2 (38,15) | 1 1/2 (38,15) | |
Intake temperature of AHU connection kit (Cool - Min) | °C DB | +18 | +18 | +18 | +18 | +18 | +18 | +18 | |
Intake temperature of AHU connection kit (Cool - Max) | °C DB | +32 | +32 | +32 | +32 | +32 | +32 | +32 | |
Intake temperature of AHU connection kit (Cool - Min) | °C WB | +13 | +13 | +13 | +13 | +13 | +13 | +13 | |
Intake temperature of AHU connection kit (Cool - Max) | °C WB | +23 | +23 | +23 | +23 | +23 | +23 | +23 | |
Intake temperature of AHU connection kit (Heat - Min) | °C | +16 | +16 | +16 | +16 | +16 | +16 | +16 | |
Intake temperature of AHU connection kit (Heat - Max) | °C | +30 | +30 | +30 | +30 | +30 | +30 | +30 | |
Ambient temperature of outdoor unit (Cool - Min) | °C | -10 | -10 | -10 | -10 | -10 | -10 | -10 | |
Ambient temperature of outdoor unit (Cool - Max) | °C | +43 | +43 | +43 | +43 | +43 | +43 | +43 | |
Ambient temperature of outdoor unit (Heat - Min) | °C | -20 | -20 | -20 | -20 | -20 | -20 | -20 | |
Ambient temperature of outdoor unit (Heat - Max) | °C | +15 | +15 | +15 | +15 | +15 | +15 | +15 |