3-Pipe ECOi EX MF3 series combination from 18 to 48HP

Simultaneous heating and cooling operation with heat recovery type

The 3-Pipe ECOi EX MF3 Series is one of the most advanced VRF systems.

Not only high-efficient performance for simultaneous heating and cooling, but also sophisticated installation and maintenance available.

Particularly suitable for retail, hotels and office applications

Specifications

See all
3-Pipe ECOi EX MF3 series combination from 18 to 48HP THREE PHASE
18 kW 20 kW 22 kW 24 kW 26 kW 28 kW 30 kW 32 kW 34 kW 36 kW 38 kW 40 kW 42 kW 44 kW 46 kW 48 kW
HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP 42HP 44HP 46HP 48HP
Outdoor unit U-8MF3E8 + U-10MF3E8 U-8MF3E8 + U-12MF3E8 U-10MF3E8 + U-12MF3E8 U-12MF3E8 + U-12MF3E8 U-10MF3E8 + U-16MF3E8 U-12MF3E8 + U-16MF3E8 U-14MF3E8 + U-16MF3E8 U-16MF3E8 + U-16MF3E8 U-8MF3E8 + U-10MF3E8 + U-16MF3E8 U-8MF3E8 + U-12MF3E8 + U-16MF3E8 U-10MF3E8 + U-12MF3E8 + U-16MF3E8 U-8MF3E8 + U-16MF3E8 + U-16MF3E8 U-10MF3E8 + U-16MF3E8 + U-16MF3E8 U-12MF3E8 + U-16MF3E8 + U-16MF3E8 U-14MF3E8 + U-16MF3E8 + U-16MF3E8 U-16MF3E8 + U-16MF3E8 + U-16MF3E8
Power supply (Voltage) V 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415
Power supply (Phase) Three phase Three phase Three phase Three phase Three phase Three phase Three phase Three phase Three phase Three phase Three phase Three phase Three phase Three phase Three phase Three phase
Power supply (Frequency) Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
Cooling capacity (Nominal) kW 50,0 56,0 61,5 68,0 73,0 78,5 85,0 90,0 96,0 101,0 107,0 113,0 118,0 124,0 130,0 135,0
EER (1) W/W 4,90 4,31 4,24 3,89 3,88 3,65 3,59 3,49 4,10 3,90 3,88 3,72 3,72 3,58 3,55 3,49
Current cooling (1p 220V / 3p 380) A 16,8 21,0 23,7 28,3 31,0 35,1 39,6 42,6 38,6 42,3 45,6 50,2 52,4 56,5 61,1 63,9
Current cooling (1p 230V / 3p 400) A 16,0 20,0 22,5 26,9 29,5 33,4 37,6 40,5 36,7 40,2 43,3 47,7 49,7 53,7 58,1 60,7
Current cooling (1p 240V / 3p 415) A 15,4 19,2 21,7 25,9 28,4 32,2 36,2 39,0 35,4 38,7 41,7 46,0 47,9 51,8 56,0 58,5
Input power cooling kW 10,20 13,00 14,50 17,50 18,80 21,50 23,70 25,8 23,40 25,90 27,60 30,40 31,70 34,60 36,60 38,70
Heating capacity kW 56,0 63,0 69,0 76,5 81,5 87,5 95,0 100,0 108,0 113,0 119,0 127,0 132,0 138,0 145,0 150,0
COP (1) W/W 5,23 4,77 4,79 4,47 4,50 4,31 4,19 4,17 4,64 4,48 4,51 4,31 4,36 4,25 4,18 4,17
Current heating (1p 220V / 3p 380) A 17,7 21,3 23,5 27,6 30,2 33,5 37,9 40,1 38,9 41,6 43,6 49,3 50,6 53,7 57,9 60,1
Current heating (1p 230V / 3p 400) A 16,8 20,3 22,3 26,3 28,7 31,8 36,0 38,1 37,0 39,5 41,4 46,8 48,1 51,0 55,0 57,1
Current heating (1p 240V / 3p 415) A 16,2 19,5 21,5 25,3 27,7 30,7 34,7 36,7 35,6 38,1 39,9 45,1 46,3 49,1 53,0 55,0
Input power heating kW 10,70 13,20 14,40 17,10 18,10 20,30 22,70 24,00 23,30 25,20 26,40 29,50 30,30 32,50 34,70 36,00
Starting current A 2,00 2,00 2,00 2,00 3,00 3,00 4,00 4,00 4,00 4,00 4,00 5,00 5,00 5,00 6,00 6,00
External static pressure (Max) Pa 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80
Air flow m³/min 430 442 452 464 452 464 464 464 662 674 684 674 684 696 696 696
Sound pressure (Normal mode) dB(A) 59,0 61,0 62,0 63,0 63,5 64,5 64,5 65,0 64,0 64,5 65,0 65,5 66,0 66,5 66,5 67,0
Sound pressure (Silent mode 1) dB(A) 56,0 58,0 59,0 60,0 60,5 61,5 61,5 62,0 61,0 61,5 62,0 62,5 63,0 63,5 63,5 64,0
Sound pressure (Silent mode 2) dB(A) 54,0 56,0 57,0 58,0 58,5 59,5 59,5 60,0 59,0 59,5 60,0 60,5 61,0 61,5 61,5 62,0
Sound power (Normal mode) dB(A) 81,5 84,0 84,5 86,0 84,5 86,0 86,0 86,0 84,5 85,5 85,5 85,5 86,0 86,5 87,0 87,0
Dimension (Height) mm 1.842 1.842 1.842 1.842 1.842 1.842 1.842 1.842 1.842 1.842 1.842 1.842 1.842 1.842 1.842 1.842
Dimension (Width) mm 2.360 (+60) 2.360 (+60) 2.360 (+60) 2.360 (+60) 2.360 (+60) 2.360 (+60) 2.360 (+60) 2.360 (+60) 3.540 (+120) 3.540 (+120) 3.540 (+120) 3.540 (+120) 3.540 (+120) 3.540 (+120) 3.540 (+120) 3.540 (+120)
Dimension (Depth) mm 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000
Net weight kg 523 547 548 574 596 620 668 668 857 881 882 929 930 954 1.002 1.002
Piping diameter (Liquid) (2) Inch (mm) 5/8 (15,88) / 3/4 (19,05) 5/8 (15,88) / 3/4 (19,05) 5/8 (15,88) / 3/4 (19,05) 5/8 (15,88) / 3/4 (19,05) 3/4 (19,05) / 7/8 (22,22) 3/4 (19,05) / 7/8 (22,22) 3/4 (19,05) / 7/8 (22,22) 3/4 (19,05) / 7/8 (22,22) 3/4 (19,05) / 7/8 (22,22)  3/4 (19,05) / 7/8 (22,22)  3/4 (19,05) / 7/8 (22,22)  3/4 (19,05) / 7/8 (22,22)  3/4 (19,05) / 7/8 (22,22)  3/4 (19,05) / 7/8 (22,22)  3/4 (19,05) / 7/8 (22,22)  3/4 (19,05) / 7/8 (22,22) 
Piping diameter (Discharge) (2) Inch (mm) 7/8 (22,22) / 1 (25,40) 7/8 (22,22) / 1 (25,40) 1 (25,40) / 1-1/8 (28,58) 1 (25,40) / 1-1/8 (28,58) 1 (25,40) / 1-1/8 (28,58) 1-1/8 (28,58) / 1-1/4 (31,75) 1-1/8 (28,58) / 1-1/4 (31,75) 1-1/8 (28,58) / 1-1/4 (31,75) 1-1/8 (28,58) / 1-1/4 (31,75) 1-1/8 (28,58) / 1-1/4 (31,75) 1-1/4 (31,75) / 1-1/2 (38,10) 1-1/4 (31,75) / 1-1/2 (38,10) 1-1/4 (31,75) / 1-1/2 (38,10) 1-1/4 (31,75) / 1-1/2 (38,10) 1-1/4 (31,75) / 1-1/2 (38,10) 1-1/4 (31,75) / 1-1/2 (38,10)
Piping diameter (Suction) (2) Inch (mm) 1-1/8 (28,58) / 1-1/4 (31,75) 1-1/8 (28,58) / 1-1/4 (31,75) 1-1/8 (28,58) / 1-1/4 (31,75) 1-1/8 (28,58) / 1-1/4 (31,75) 1-1/4 (31,75) / 1-1/2 (38,10) 1-1/4 (31,75) / 1-1/2 (38,10) 1-1/4 (31,75) / 1-1/2 (38,10) 1-1/4 (31,75) / 1-1/2 (38,10) 1-1/4 (31,75) / 1-1/2 (38,10) 1-1/2 (38,10) / 1-5/8 (41,28)  1-1/2 (38,10) / 1-5/8 (41,28)  1-1/2 (38,10) / 1-5/8 (41,28)  1-1/2 (38,10) / 1-5/8 (41,28)  1-1/2 (38,10) / 1-5/8 (41,28)  1-1/2 (38,10) / 1-5/8 (41,28)  1-1/2 (38,10) / 1-5/8 (41,28) 
Piping diameter (Balance) (2) Inch (mm) 1/4 (6,35) 1/4 (6,35) 1/4 (6,35) 1/4 (6,35) 1/4 (6,35) 1/4 (6,35) 1/4 (6,35) 1/4 (6,35) 1/4 (6,35) 1/4 (6,35) 1/4 (6,35) 1/4 (6,35) 1/4 (6,35) 1/4 (6,35) 1/4 (6,35) 1/4 (6,35)
Refrigerant (R410A) / CO2 Eq. kg / T 13,60 / 28,3968 15,10 / 31,5288 15,10 / 31,5288 16,60 / 34,6608 15,10 / 31,5288 16,60 / 34,6608 16,60 / 34,6608 16,60 / 34,6608 21,90 / 45,72719 23,40 / 48,85919 23,40 / 48,85919 23,40 / 48,85919 23,40 / 48,85919 24,90 / 46,3536 24,90 / 51,9912 24,90 / 51,9912
Maximum allowable indoor / outdoor capacity ratio % 50 ~ 150 50 ~ 150 50 ~ 150 50 ~ 150 50 ~ 150 50 ~ 150 50 ~ 150 50 ~ 150 50 ~ 150 50 ~ 150 50 ~ 150 50 ~ 150 50 ~ 150 50 ~ 150 50 ~ 150 50 ~ 150
Operating range (Cool - Min) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
Operating range (Cool - Max) °C +52 +52 +52 +52 +52 +52 +52 +52 +52 +52 +52 +52 +52 +52 +52 +52
Operating range (Heat - Min) °C -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20
Operating range (Heat - Max) °C +18 +18 +18 +18 +18 +18 +18 +18 +18 +18 +18 +18 +18 +18 +18 +18
Operating range (Simultaneous operation - Min) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
Operating range (Simultaneous operation - Max) % +24 +24 +24 +24 +24 +24 +24 +24 +24 +24 +24 +24 +24 +24 +24 +24

1) EER and COP calculation is based in accordance to EN14511.
2) Piping diameter under 90m for ultimate indoor unit / over 90m for ultimate indoor unit (if the longest piping equivalent length exceeds 90m, increase the sizes of the main tubes by 1 rank for gas tubes and liquid tubes).