T-CAP stand-alone outdoor M Series 1 phase - 3 phase · R290

Aquarea M Series, the latest generation of Aquarea air to water heat pumps with R290

Aquarea T‑CAP M Series delivers a revolution in the design, performance, connectivity, and sustainability

The solution is suitable for both new buildings and retrofits, as it offers a sustainable alternative to traditional fossil fuel heating systems and it can be easily integrated with existing water system such as fan coils, floor heating or domestic hot water tanks.

1) Down to 15ºC outdoor for 20, 25 and 30kW models
2) Sound pressure calculation for WH-WXG12ME5, free standing, A +7°C, W 35°C in Quite mode 3
3) Down to -25ºC outdoor for 20, 25 and 30kW models

Owning an Aquarea?

Specifications

See all
T-CAP stand-alone outdoor M Series 1 phase - 3 phase · R290
25 kW
Outdoor unit WH-WXG25ME8
Remote controller with Wi-Fi adapter CZ-RTW2TAW1C
Heating capacity (A +7°C, W 35°C) kW 25,00
COP (A +7°C, W 35°C) 4,50
Heating capacity (A +7°C, W 55°C) kW 25,00
COP (A +7°C, W 55°C) 3,00
Heating capacity (A +2°C, W 35°C) kW 25,00
COP (A +2°C, W 35°C) 2,80
Heating capacity (A +2°C, W 55°C) kW 25,00
COP (A +2°C, W 55°C) 1,97
Heating capacity (A -7°C, W 35°C) kW 25,00
COP (A -7°C, W 35°C) 2,36
Heating capacity (A -7°C, W 55°C) kW 25,00
COP (A -7°C, W 55°C) 1,80
Cooling capacity (A 35°C, W 7°C) at Comfort mode kW 25,00
EER (A 35°C, W 7°C) at Comfort mode EER 2,86
Cooling capacity (A 35°C, W 7°C) at Efficiency mode (default) kW 15,00
EER (A 35°C, W 7°C) at Efficiency mode (default) kW 3,61
Cooling capacity (A 35°C, W 18°C) at Comfort mode kW 25,00
EER (A 35°C, W 18°C) at Comfort mode EER 4,47
Heating average climate. Seasonal energy efficiency SCOP (W 35°C / W 55°C) SCOP 4,25 / 3,57
Heating average climate. Seasonal energy efficiency η (W 35°C / W 55°C) ηs % 167 / 140
Heating average climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A++/A++
Heating warm climate. Seasonal energy efficiency SCOP (W 35°C / W 55°C) SCOP 5,22 / 4,14
Heating warm climate. Seasonal energy efficiency η (W 35°C / W 55°C) ηs % 206 / 163
Heating warm climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+++ / A+++
Heating cold climate. Seasonal energy efficiency SCOP (W 35°C / W 55°C) SCOP 3,16 / 2,71
Heating cold climate. Seasonal energy efficiency η (W 35°C / W 55°C) ηs % 123 / 105
Heating cold climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+ / A+
Outdoor sound power (Heat) (2) dB(A) 59
Outdoor dimension (Height) mm 1.645
Outdoor dimension (Width) mm 1.500
Outdoor dimension (Depth) mm 460
Outdoor net weight kg 240
A class pump (Number of speeds) Variable speed
A class pump (Input power Min) W 230
Heating water flow (∆T=5 K. 35°C) L/min 71,6
Refrigerant (R290) / CO2 Eq. (3) kg / T 3,0 / 0,009
Operation range - Outdoor ambient (Heat) °C -25 ~ +35
Operation range - Outdoor ambient (Cool) °C +10 ~ +43
Water outlet (Heat) °C 20 ~ 75 (4)
Water outlet (Cool) °C 5 ~ 20
Outdoor recommended fuse, supply (5) A 50
Outdoor recommended minimum cable size, supply (5) mm² 5x10 - 5x16

(1) Scale from A+++ to D.
(2) Sound power level in accordance to EN12102 under conditions of the EN14825 (part load).
(3) WH-WXG models are hermetically sealed.
(4) Check local regulations.
* EER and COP calculation is based in accordance to EN 14511.