2-Pipe ECO G GE3 series combination from 32 to 60HP
The GE3 Series has a top level of seasonal efficiency in this category.
In addition, this product fits with special needs for commercial application thanks to DHW priority setting and auto pump down functions.
- Maximum 60HP combination
- Superior seasonal energy efficiency, maximum 240,1%
- DHW priority setting
- Operating range in heating down to -21°C and up to +24°C for air to water system
- No defrost cycle
- Option of DX or chilled water for indoor heat exchange
- Maximum total piping length: 780m
ECO G, the advanced Gas Driven VRF
Specifications
2-Pipe ECO G GE3 series combination from 32 to 60HP | |||
---|---|---|---|
50 kW | |||
HP | 50HP | ||
Outdoor unit | U-25GE3E5 + U-25GE3E5 | ||
Power supply (Voltage) | V | 220 - 230 - 240 | |
Power supply (Phase) | Single phase | ||
Power supply (Frequency) | Hz | 50 | |
Cooling capacity (Nominal) | kW | 142,0 | |
Input power cooling | kW | 3,60 | |
Hot water in cooling mode (at 65°C outlet) | kW | 72,80 | |
Max COP in hot water | W/W | 1,49 | |
Gas consumption cooling | kW | 134,40 | |
Heating capacity (Standard) | kW | 160,0 | |
Heating capacity (Low temperature) | kW | 156,0 | |
Input power heating | kW | 1,82 | |
Gas consumption heating (Standard) | kW | 137,20 | |
Gas consumption heating (Low temperature) | kW | 121,40 | |
Starter amperes | A | 30 | |
External static pressure | Pa | 10 | |
Air flow | m³/min | 460 / 460 | |
Sound power (Normal mode) | dB(A) | 87 | |
Sound power (Silent mode) | dB(A) | 84 | |
Dimension (Height) | mm | 2.255 | |
Dimension (Width) | mm | 2.026 + 100 + 2.026 | |
Dimension (Depth) | mm | 1.000 | |
Net weight | kg | 1.740 (870 + 870) | |
Piping diameter (Liquid) | Inch (mm) | 3/4 (19,05) | |
Piping diameter (Gas) | Inch (mm) | 1-1/2 (38,10) | |
Piping diameter (Fuel gas) | Inch (mm) | 19,05 (R3/4) | |
Piping diameter (Exhaust drain port) | mm | 25 | |
Piping diameter (Hot water supply in/out) | Rp3/4 (Nut, thread) | ||
Elevation difference (in/out) | m | 50 | |
Refrigerant (R410A) / CO2 Eq. | kg / T | 2x 11,50 / 24,00 | |
Maximum number of connectable indoor units | 64 | ||
Operating range (Cool - Min) | °C | -10 | |
Operating range (Cool - Max) | °C | +43 | |
Operating range (Heat - Min) | °C | -21 | |
Operating range (Heat - Max) | °C | +18 |
Data is for reference. Hot water take out function added, EU safety regulation standard cleared. 25HP chassis enlarged due to specification improvement. Pre-coat corrosion fin. Auto pump down function.