2-Pipe ECOi EX ME2 series space saving combination from 22 to 80HP

A VRF system delivering energy-saving performance, powerful operation, reliability and comfort surpassing anything previously possible

It represents a true paradigm shift in air conditioning solutions.

Particularly suitable for retail, hotels and office applications

Specifications

See all
2-Pipe ECOi EX ME2 series space saving combination from 22 to 80HP
50 kW
HP 50HP
Outdoor unit U-14ME2E8 + U-16ME2E8 + U-20ME2E8
Power supply (Voltage) V 380 - 400 - 415
Power supply (Phase) Three phase
Power supply (Frequency) Hz 50
Cooling capacity (Nominal) kW 140,0
EER (1) W/W 3,55
SEER (2) 6,96
Current cooling (1p 220V / 3p 380) A 64,40
Current cooling (1p 230V / 3p 400) A 61,10
Current cooling (1p 240V / 3p 415) A 58,90
Input power cooling kW 39,40
Heating capacity (Nominal) kW 155,0
COP (1) W/W 4,29
SCOP (2) 4,08
Current heating (1p 220V / 3p 380) A 59,60
Current heating (1p 230V / 3p 400) A 56,60
Current heating (1p 240V / 3p 415) A 54,60
Input power heating kW 36,10
Starting current A 6,00
External static pressure (Max) Pa 80
Air flow m³/min 869
Sound pressure (Normal mode) dB(A) 65,5
Sound pressure (Silent mode 1) dB(A) 62,5
Sound power (Normal mode) dB(A) 86,5
Dimension (Height) mm 1.842
Dimension (Width) mm 4.020
Dimension (Depth) mm 1.000
Net weight kg 1.005
Piping diameter (Liquid) (3) Inch (mm) 3/4 (19,05) / 7/8 (22,22)
Piping diameter (Gas) (3) Inch (mm) 1-1/2 (38,10) / 1-5/8 (41,28)
Piping diameter (Balance) (3) Inch (mm) 1/4 (6,35)
Refrigerant (R410A) / CO2 Eq. kg / T 26,10 / 54,4968
Maximum allowable indoor / outdoor capacity ratio (4) % 50 ~ 130 (200)
Operating range (Cool - Min) °C -10
Operating range (Cool - Max) °C +52
Operating range (Heat - Min) °C -25
Operating range (Heat - Max) °C +18

1) EER and COP calculation is based in accordance to EN14511.
2) SEER/SCOP is calculated based on the seasonal space cooling/heating efficiency “η” values of the COMMISSION REGULATION (EU) 2016/2281. SEER, SCOP = (η + Correction) × PEF.
3) Piping diameter under 90m for ultimate indoor unit / over 90m for ultimate indoor unit (if the longest piping equivalent length exceeds 90m, increase the sizes of the main tubes by 1 rank for gas tubes and liquid tubes).
4) If the following conditions are satisfied, the effective range is above 130% and below 200%: A. Obey the limited number of connectable indoor units. B. The lower limit of operating range for heating outdoor temperature is limited to -10°C WB (standard -25°C WB). C. Simultaneous operation is limited to less than 130% of connectable indoor units.