U - 140/150/170/190/210 CV
ECOi-W Cooling Only Chiller
Cooling capacity: 134,0 to 208,8kW.
Powerful and efficient operation with 4 scroll compressors and superior flexibility with plug and play hydraulic options.
· Ambient temperature operating range: -10 to +50°C
· Water outlet temperature range: -10 to +18°C
· Super quiet operation
· Victaulic water connections
· Optimized design for service and maintenance
· Simple user friendly control as standard
· Modbus RTU as standard
· Modbus TCP/IP as standard
Technical focus.
· Chiller type: cooling only
· Compressor type (number of compressors): Scroll compressors (4)
· Refrigerant type: R410A
· Refrigerant circuit: 2
· Fan type (number of fans): axial fan (4)
· Heat exchanger: stainless steel plate heat exchanger
· Flow switch, water safety & air purge valves included
· Water filter included (mandatory to be installed on site)
· Night mode setting to save energy and reduce noise level
· Water compensation curve control
· Optional hydraulic kit
· Optional finned coil treatment
· Optional gauges hydraulic and refrigerant
· Optional BACnet
· Remote LAN connection as standard
The reasons to choose Panasonic as your partner



Unrivaled reliability and quality
Panasonic does not compromise on product quality, always strives for 100% quality.
Panasonic solutions can be enjoyed for years to come, even in the most extreme climates.
· Quality certified by Panasonic
· Eurovent certified performance
· ECOi-W Series are compliant with ErP regulation
Panasonic solutions can be enjoyed for years to come, even in the most extreme climates
These new series provides a wide variety of HVAC system solutions, to meet all of your residential, commercial and industrial needs.
ECOi-W series offers smart technology
· High seasonal efficiency in cooling and heating mode
· Super quiet
· Ultimate customisation
· Automatic fan operation
· Down to -17 °C in heating mode
· Up to 50 °C in cooling mode
· Defrost limiting cycle (140 – 210)
· Bluefin coil comes as standard
· BMS connectivity
Unrivaled reliability and quality
Panasonic does not compromise on product quality, always strives for 100% quality.
Panasonic solutions can be enjoyed for years to come, even in the most extreme climates.
· Quality certified by Panasonic
· Eurovent certified performance
· ECOi-W Series are compliant with ErP regulation
Panasonic solutions can be enjoyed for years to come, even in the most extreme climates
These new series provides a wide variety of HVAC system solutions, to meet all of your residential, commercial and industrial needs.
ECOi-W series offers smart technology
· High seasonal efficiency in cooling and heating mode
· Super quiet
· Ultimate customisation
· Automatic fan operation
· Down to -17 °C in heating mode
· Up to 50 °C in cooling mode
· Defrost limiting cycle (140 – 210)
· Bluefin coil comes as standard
· BMS connectivity
Explore the new range of fan coils
Specifications
U - 140/150/170/190/210 CV | |||
---|---|---|---|
132.0 kW | |||
Model standard without buffer tank | U-140CVNB | ||
Model with buffer tank | U-140CVBL | ||
Power supply (Voltage) | V | 400 | |
Power supply (Phase) | Three phase | ||
Power supply (Frequency) | Hz | 50 | |
Cooling capacity (1) | kW | 132,0 | |
Input power cooling (1) | kW | 43,1 | |
Total EER 100% (1) | 3,06 | ||
SEER (2) | 4,40 | ||
ηs,c (2) | % | 173 | |
Startup type | Direct | ||
Maximum operating current | A | 108,0 | |
Startup current without softstarter | A | 251 | |
Startup current with softstarter | A | 130 | |
Sound power (with standard fans) | dB(A) | 85,4 | |
Sound pressure (with standard fans) (3) | dB(A) | 53,4 | |
Dimension (with standard fans) without buffer tank (Height) | mm | 2.295 | |
Dimension (with standard fans) without buffer tank (Width) | mm | 2.856 | |
Dimension (with standard fans) without buffer tank (Depth) | mm | 2.210 | |
Dimension (with standard fans) with buffer tank (Height) | mm | 2.295 | |
Dimension (with standard fans) with buffer tank (Width) | mm | 3.666 | |
Dimension (with standard fans) with buffer tank (Depth) | mm | 2.210 | |
Weight (with 1 pump) without buffer tank | kg | 1.510 | |
Weight (with 1 pump) with buffer tank | kg | 1.640 | |
Refrigerant (R410A) | kg | 2 x 24,7 | |
Number of refrigerant circuit | 2 | ||
Compressors | . | ||
Number of compressors | 4 | ||
Type of compressors | Scroll | ||
Part load step | % | 0 / 24 / 26 / 48 / 50 / 52 / 74 / 76 / 100 | |
Crankcase heater | W | 4 x 66 | |
Evaporator | . | ||
Number of evaporators | 1 | ||
Type of evaporators | Plate | ||
Nominal water flow (cooling) | m³/h | 21,56 | |
Water pressure drop (cooling) | kPa | 33 | |
Water volume | L | 8,49 | |
Antifreeze heater | W | 60 | |
Coils | . | ||
Number of coils | 4 | ||
Frontal surface | m² | 11,88 | |
Number of rows | 2 + 2 | ||
Fans standard | . | ||
Number of fans standard | 4 | ||
Air flow of fans standard | m³/h | 56.000 | |
Rotation speed | r.p.m. | 900 | |
Power input (each fan) | W | 940 | |
Chiller water connections | . | ||
Type of water connections | Victaulic | ||
Inlet - diameter | Inch | 2 ½ | |
Outlet - diameter | Inch | 2 ½ |
1) Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.
2) Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers.
3) Sound pressure levels calculated at 10 meters. Sound pressure levels refer to ISO standard 3744 with parallel piped shape.
** The data are calculated with variable flow.