E2 Type high static pressure hide-away - R410A
High pressure duct and 100% Fresh air duct function
The E2 range of ducted units offers improved design flexibility for extended duct layouts as a result of their increased external static pressures and reduces energy consumption.
- No need of rap valve
- 100% fresh air duct function
- DC fan motor for more savings
- Complete flexibility for ductwork design
- Can be located into a weatherproof housing for external sitting
- Air OFF sensor avoids cold air dumping
- Configurable air temperature control
Specifications
E2 Type high static pressure hide-away - R410A | |||
---|---|---|---|
28.0 kW | |||
Model | High pressure duct | ||
Indoor unit | S-280ME2E5 | ||
Cooling capacity (Nominal) | kW | 28,0 | |
Input power cooling | kW | 715,00 | |
Current cooling | A | 3,95 | |
Heating capacity (Nominal) | kW | 31,5 | |
Input power heating | kW | 715,00 | |
Current heating | A | 3,95 | |
Air flow (Hi) | m³/min | 72,0 | |
Air flow (Med) | m³/min | 63,0 | |
Air flow (Lo) | m³/min | 53,0 | |
External static pressure | Pa | 140 (1) | |
External static pressure (Min) | Pa | 72 (1) | |
External static pressure (Max) | Pa | 270 (1) | |
Sound pressure (Hi) (2) | dB(A) | 49 | |
Sound pressure (Med) (2) | dB(A) | 47 | |
Sound pressure (Lo) (2) | dB(A) | 43 | |
Sound power (Hi) | dB(A) | 81 | |
Sound power (Med) | dB(A) | 79 | |
Sound power (Lo) | dB(A) | 75 | |
Dimension (Height) | mm | 479 | |
Dimension (Width) | mm | 1.453 | |
Dimension (Depth) | mm | 1.205 | |
Net weight | kg | 106 | |
Piping diameter (Liquid) | Inch (mm) | 3/8 (9,52) | |
Piping diameter (Gas) | Inch (mm) | 7/8 (22,22) |
Rating Conditions for 100% Fresh air duct function: Cooling Outdoor 33°C DB / 28°C WB. Heating Outdoor 0°C DB / -2,9°C WB.
1) Available to select the setting by initial setup.
2) Values with 140Pa setting.
* No filter included.
** No compatible with 3-Pipe ECO G GF3.