Fan coils - Ceiling chassis (EC)

New range of fan coils. Designed to fit with your environment and enhance comfort

Panasonic introduces the new range of fan coils.

The key to this range is to provide performance and comfort and the ability to fit seamlessly within your environment.

Designed with user in mind, perfectly designed to adapt to any installation. Providing comfort to hotels, shops, restaurants, offices or residential applications.

Technical focus.
· Cooling capacity from 0,5 to 9,6kW
· Heating capacity from 0,6 to 13,6kW
· Low energy consumption EC fan(s)

Main features and accessories.
· 2 and 4-pipe configurations
· Left or right hand arrangements
· Ease of installation
· Very low acoustic levels
· 2 way or 3 way ON/OFF valves
· Auxiliary drain pan
· Air intake with removable grid
· G2 filter

The reasons to choose Panasonic as your partner

Explore the new range of fan coils

Specifications

See all
Fan coils - Ceiling chassis (EC)
5.2 kW
2-pipe - Left connection PAW-FC2E-T060L
2-pipe - Right connection PAW-FC2E-T060R
Total cooling capacity - 2-pipe (Lo) (1) kW 2,0
Total cooling capacity - 2-pipe (Med) (1) kW 4,5
Total cooling capacity - 2-pipe (Hi) (1) kW 5,2
Sensible cooling capacity - 2-pipe (Lo) (1) kW 1,4
Sensible cooling capacity - 2-pipe (Med) (1) kW 3,5
Sensible cooling capacity - 2-pipe (Hi) (1) kW 4,0
Water flow - 2-pipe (Cooling) (Lo) l/h 341
Water flow - 2-pipe (Cooling) (Med) l/h 767
Water flow - 2-pipe (Cooling) (Hi) l/h 800
Water pressure drop - 2-pipe (Cooling) (Lo) kPa 7,8
Water pressure drop - 2-pipe (Cooling) (Med) kPa 35,8
Water pressure drop - 2-pipe (Cooling) (Hi) kPa 38,8
Heating capacity - 2-pipe (Lo) (2) kW 2,3
Heating capacity - 2-pipe (Med) (2) kW 5,9
Heating capacity - 2-pipe (Hi) (2) kW 6,1
4-pipe - Left connection PAW-FC4E-T060L
4-pipe - Right connection PAW-FC4E-T060R
Total cooling capacity - 4-pipe (Lo) (1) kW 1,8
Total cooling capacity - 4-pipe (Med) (1) kW 4,1
Total cooling capacity - 4-pipe (Hi) (1) kW 4,9
Sensible cooling capacity - 4-pipe (Lo) (1) kW 1,2
Sensible cooling capacity - 4-pipe (Med) (1) kW 3,2
Sensible cooling capacity - 4-pipe (Hi) (1) kW 3,8
Water flow - 4-pipe (Cooling) (Lo) l/h 306
Water flow - 4-pipe (Cooling) (Med) l/h 707
Water flow - 4-pipe (Cooling) (Hi) l/h 749
Water pressure drop - 4-pipe (Cooling) (Lo) kPa 5,1
Water pressure drop - 4-pipe (Cooling) (Med) kPa 24,3
Water pressure drop - 4-pipe (Cooling) (Hi) kPa 27,2
Heating capacity - 4-pipe (Lo) (2) kW 1,4
Heating capacity - 4-pipe (Med) (2) kW 2,9
Heating capacity - 4-pipe (Hi) (2) kW 3,1
Water flow (Heating) (Lo) l/h 233
Water flow (Heating) (Med) l/h 503
Water flow (Heating) (Hi) l/h 531
Water pressure drop (Heating) (Lo) kPa 11,5
Water pressure drop (Heating) (Med) kPa 43,6
Water pressure drop (Heating) (Hi) kPa 48,1
Sound levels .
Sound power (Lo) dB(A) 32
Sound power (Med) dB(A) 54
Sound power (Hi) dB(A) 58
Sound pressure (Lo) (3) dB(A) 23
Sound pressure (Med) (3) dB(A) 45
Sound pressure (Hi) (3) dB(A) 49
Fan data .
Number of fans 2
Air flow - 2-pipe (Lo) m³/h 245
Air flow - 2-pipe (Med) m³/h 737
Air flow - 2-pipe (Hi) m³/h 912
Air flow - 4-pipe (Lo) m³/h 205
Air flow - 4-pipe (Med) m³/h 668
Air flow - 4-pipe (Hi) m³/h 716
Filter G2
Electrical data .
Power supply (Voltage) V 230
Power supply (Phase) Single phase
Power supply (Frequency) Hz 50 / 60
Power consumption - 2-pipe (Lo) W 2
Power consumption - 2-pipe (Med) W 30
Power consumption - 2-pipe (Hi) W 54
Power consumption - 4-pipe (Lo) W 2
Power consumption - 4-pipe (Med) W 28
Power consumption - 4-pipe (Hi) W 52
Fan coils water connections .
Type of water connections Female gas threaded
Water connections - 2-pipe Inch 1/2
Water connections - 4-pipe (Cooling) Inch 1/2
Water connections - 4-pipe (Heating) Inch 1/2
Dimensions and weight .
Dimension (Height) mm 225
Dimension (Width) mm 1.506
Dimension (Depth) mm 477
Weight - 2-pipe kg 35
Weight - 4-pipe kg 37

1) According to Eurovent standard. Air: 27°C DB / 19°C WB. Water in/out: 7°C / 12°C.
2) Air: 20°C. Water in/out: 50°C / 45°C.
3) The sound pressure levels are based on (NR) characteristics of a room having volume of 100m³ with reverberation of 0,5 seconds.