Fan coils - Floor Standing chassis (EC)

New range of fan coils. Designed to fit with your environment and enhance comfort

Panasonic introduces the new range of fan coils.

The key to this range is to provide performance and comfort and the ability to fit seamlessly within your environment.

Designed with user in mind, perfectly designed to adapt to any installation. Providing comfort to hotels, shops, restaurants, offices or residential applications.

Technical focus.
· Cooling capacity from 0,5 to 9,6kW
· Heating capacity from 0,6 to 13,6kW
· Low energy consumption EC fan(s)

Main features and accessories.
· 2 and 4-pipe configurations
· Left or right hand arrangements
· Ease of installation
· Very low acoustic levels
· 2 way or 3 way ON/OFF valves
· Auxiliary drain pan
· Air intake with removable grid
· G2 filter
· PAW-FC-SFS feet for floor-standing units

The reasons to choose Panasonic as your partner

Explore the new range of fan coils

Specifications

See all
Fan coils - Floor Standing chassis (EC)
8.8 kW
2-pipe - Left connection PAW-FC2E-P080L
2-pipe - Right connection PAW-FC2E-P080R
Total cooling capacity - 2-pipe (Lo) (1) kW 5,1
Total cooling capacity - 2-pipe (Med) (1) kW 6,5
Total cooling capacity - 2-pipe (Hi) (1) kW 8,8
Sensible cooling capacity - 2-pipe (Lo) (1) kW 3,7
Sensible cooling capacity - 2-pipe (Med) (1) kW 4,8
Sensible cooling capacity - 2-pipe (Hi) (1) kW 6,6
Water flow - 2-pipe (Cooling) (Lo) l/h 879
Water flow - 2-pipe (Cooling) (Med) l/h 1.111
Water flow - 2-pipe (Cooling) (Hi) l/h 1.254
Water pressure drop - 2-pipe (Cooling) (Lo) kPa 14,1
Water pressure drop - 2-pipe (Cooling) (Med) kPa 21,4
Water pressure drop - 2-pipe (Cooling) (Hi) kPa 26,6
Heating capacity - 2-pipe (Lo) (2) kW 6,2
Heating capacity - 2-pipe (Med) (2) kW 8,0
Heating capacity - 2-pipe (Hi) (2) kW 9,3
4-pipe - Left connection PAW-FC4E-P080L
4-pipe - Right connection PAW-FC4E-P080R
Total cooling capacity - 4-pipe (Lo) (1) kW 5,0
Total cooling capacity - 4-pipe (Med) (1) kW 6,2
Total cooling capacity - 4-pipe (Hi) (1) kW 9,6
Sensible cooling capacity - 4-pipe (Lo) (1) kW 3,6
Sensible cooling capacity - 4-pipe (Med) (1) kW 4,6
Sensible cooling capacity - 4-pipe (Hi) (1) kW 7,2
Water flow - 4-pipe (Cooling) (Lo) l/h 855
Water flow - 4-pipe (Cooling) (Med) l/h 1.070
Water flow - 4-pipe (Cooling) (Hi) l/h 1.242
Water pressure drop - 4-pipe (Cooling) (Lo) kPa 22,9
Water pressure drop - 4-pipe (Cooling) (Med) kPa 33,9
Water pressure drop - 4-pipe (Cooling) (Hi) kPa 44,3
Heating capacity - 4-pipe (Lo) (2) kW 4,5
Heating capacity - 4-pipe (Med) (2) kW 5,9
Heating capacity - 4-pipe (Hi) (2) kW 6,9
Water flow (Heating) (Lo) l/h 767
Water flow (Heating) (Med) l/h 1.011
Water flow (Heating) (Hi) l/h 1.194
Water pressure drop (Heating) (Lo) kPa 42,1
Water pressure drop (Heating) (Med) kPa 69,7
Water pressure drop (Heating) (Hi) kPa 95,1
Sound levels .
Sound power (Lo) dB(A) 51
Sound power (Med) dB(A) 56
Sound power (Hi) dB(A) 64
Sound pressure (Lo) (3) dB(A) 42
Sound pressure (Med) (3) dB(A) 47
Sound pressure (Hi) (3) dB(A) 55
Fan data .
Number of fans 3
Air flow - 2-pipe (Lo) m³/h 685
Air flow - 2-pipe (Med) m³/h 927
Air flow - 2-pipe (Hi) m³/h 1.398
Air flow - 4-pipe (Lo) m³/h 660
Air flow - 4-pipe (Med) m³/h 884
Air flow - 4-pipe (Hi) m³/h 1.079
Filter G2
Electrical data .
Power supply (Voltage) V 230
Power supply (Phase) Single phase
Power supply (Frequency) Hz 50 / 60
Power consumption - 2-pipe (Lo) W 23
Power consumption - 2-pipe (Med) W 42
Power consumption - 2-pipe (Hi) W 108
Power consumption - 4-pipe (Lo) W 22
Power consumption - 4-pipe (Med) W 41
Power consumption - 4-pipe (Hi) W 116
Fan coils water connections .
Type of water connections Female gas threaded
Water connections - 2-pipe Inch 3/4
Water connections - 4-pipe (Cooling) Inch 3/4
Water connections - 4-pipe (Heating) Inch 1/2
Dimensions and weight .
Dimension (Height) mm 575
Dimension (Width) mm 225
Dimension (Depth) mm 1.506
Weight - 2-pipe kg 47
Weight - 4-pipe kg 49

1) According to Eurovent standard. Air: 27°C DB / 19°C WB. Water in/out: 7°C / 12°C.
2) Air: 20°C. Water in/out: 50°C / 45°C.
3) The sound pressure levels are based on (NR) characteristics of a room having volume of 100m³ with reverberation of 0,5 seconds.
* Without support feet.