Fan coils - Floor Standing chassis (EC)

New range of fan coils. Designed to fit with your environment and enhance comfort

Panasonic introduces the new range of fan coils.

The key to this range is to provide performance and comfort and the ability to fit seamlessly within your environment.

Designed with user in mind, perfectly designed to adapt to any installation. Providing comfort to hotels, shops, restaurants, offices or residential applications.

Technical focus.
· Cooling capacity from 0,5 to 9,6kW
· Heating capacity from 0,6 to 13,6kW
· Low energy consumption EC fan(s)

Main features and accessories.
· 2 and 4-pipe configurations
· Left or right hand arrangements
· Ease of installation
· Very low acoustic levels
· 2 way or 3 way ON/OFF valves
· Auxiliary drain pan
· Air intake with removable grid
· G2 filter
· PAW-FC-SFS feet for floor-standing units

The reasons to choose Panasonic as your partner

Explore the new range of fan coils

Specifications

See all
Fan coils - Floor Standing chassis (EC)
6.9 kW
2-pipe - Left connection PAW-FC2E-P070L
2-pipe - Right connection PAW-FC2E-P070R
Total cooling capacity - 2-pipe (Lo) (1) kW 2,7
Total cooling capacity - 2-pipe (Med) (1) kW 5,9
Total cooling capacity - 2-pipe (Hi) (1) kW 6,9
Sensible cooling capacity - 2-pipe (Lo) (1) kW 2,0
Sensible cooling capacity - 2-pipe (Med) (1) kW 4,3
Sensible cooling capacity - 2-pipe (Hi) (1) kW 5,2
Water flow - 2-pipe (Cooling) (Lo) l/h 463
Water flow - 2-pipe (Cooling) (Med) l/h 1.008
Water flow - 2-pipe (Cooling) (Hi) l/h 1.098
Water pressure drop - 2-pipe (Cooling) (Lo) kPa 3,0
Water pressure drop - 2-pipe (Cooling) (Med) kPa 14,0
Water pressure drop - 2-pipe (Cooling) (Hi) kPa 16,6
Heating capacity - 2-pipe (Lo) (2) kW 3,8
Heating capacity - 2-pipe (Med) (2) kW 7,3
Heating capacity - 2-pipe (Hi) (2) kW 8,2
4-pipe - Left connection PAW-FC4E-P070L
4-pipe - Right connection PAW-FC4E-P070R
Total cooling capacity - 4-pipe (Lo) (1) kW 2,6
Total cooling capacity - 4-pipe (Med) (1) kW 5,1
Total cooling capacity - 4-pipe (Hi) (1) kW 6,4
Sensible cooling capacity - 4-pipe (Lo) (1) kW 1,9
Sensible cooling capacity - 4-pipe (Med) (1) kW 3,8
Sensible cooling capacity - 4-pipe (Hi) (1) kW 4,8
Water flow - 4-pipe (Cooling) (Lo) l/h 443
Water flow - 4-pipe (Cooling) (Med) l/h 886
Water flow - 4-pipe (Cooling) (Hi) l/h 977
Water pressure drop - 4-pipe (Cooling) (Lo) kPa 3,5
Water pressure drop - 4-pipe (Cooling) (Med) kPa 13,6
Water pressure drop - 4-pipe (Cooling) (Hi) kPa 16,5
Heating capacity - 4-pipe (Lo) (2) kW 2,5
Heating capacity - 4-pipe (Med) (2) kW 3,4
Heating capacity - 4-pipe (Hi) (2) kW 3,6
Water flow (Heating) (Lo) l/h 434
Water flow (Heating) (Med) l/h 583
Water flow (Heating) (Hi) l/h 614
Water pressure drop (Heating) (Lo) kPa 61,5
Water pressure drop (Heating) (Med) kPa 103,8
Water pressure drop (Heating) (Hi) kPa 113,9
Sound levels .
Sound power (Lo) dB(A) 40
Sound power (Med) dB(A) 54
Sound power (Hi) dB(A) 59
Sound pressure (Lo) (3) dB(A) 31
Sound pressure (Med) (3) dB(A) 45
Sound pressure (Hi) (3) dB(A) 50
Fan data .
Number of fans 2
Air flow - 2-pipe (Lo) m³/h 350
Air flow - 2-pipe (Med) m³/h 850
Air flow - 2-pipe (Hi) m³/h 1.050
Air flow - 4-pipe (Lo) m³/h 329
Air flow - 4-pipe (Med) m³/h 798
Air flow - 4-pipe (Hi) m³/h 894
Filter G2
Electrical data .
Power supply (Voltage) V 230
Power supply (Phase) Single phase
Power supply (Frequency) Hz 50 / 60
Power consumption - 2-pipe (Lo) W 11
Power consumption - 2-pipe (Med) W 44
Power consumption - 2-pipe (Hi) W 77
Power consumption - 4-pipe (Lo) W 11
Power consumption - 4-pipe (Med) W 43
Power consumption - 4-pipe (Hi) W 75
Fan coils water connections .
Type of water connections Female gas threaded
Water connections - 2-pipe Inch 3/4
Water connections - 4-pipe (Cooling) Inch 3/4
Water connections - 4-pipe (Heating) Inch 1/2
Dimensions and weight .
Dimension (Height) mm 575
Dimension (Width) mm 225
Dimension (Depth) mm 1.319
Weight - 2-pipe kg 35
Weight - 4-pipe kg 37

1) According to Eurovent standard. Air: 27°C DB / 19°C WB. Water in/out: 7°C / 12°C.
2) Air: 20°C. Water in/out: 50°C / 45°C.
3) The sound pressure levels are based on (NR) characteristics of a room having volume of 100m³ with reverberation of 0,5 seconds.
* Without support feet.