Fan coils - Floor Standing chassis (EC)

Previous capacity Next capacity

New range of fan coils. Designed to fit with your environment and enhance comfort

Panasonic introduces the new range of fan coils.

The key to this range is to provide performance and comfort and the ability to fit seamlessly within your environment.

Designed with user in mind, perfectly designed to adapt to any installation. Providing comfort to hotels, shops, restaurants, offices or residential applications.

Technical focus.
· Cooling capacity from 0,5 to 9,6kW
· Heating capacity from 0,6 to 13,6kW
· Low energy consumption EC fan(s)

Main features and accessories.
· 2 and 4-pipe configurations
· Left or right hand arrangements
· Ease of installation
· Very low acoustic levels
· 2 way or 3 way ON/OFF valves
· Auxiliary drain pan
· Air intake with removable grid
· G2 filter
· PAW-FC-SFS feet for floor-standing units

The reasons to choose Panasonic as your partner

Explore the new range of fan coils

Specifications

See all
Fan coils - Floor Standing chassis (EC)
2.1 kW
2-pipe - Left connection PAW-FC2E-P010L
2-pipe - Right connection PAW-FC2E-P010R
Total cooling capacity - 2-pipe (Lo) (1) kW 0,6
Total cooling capacity - 2-pipe (Med) (1) kW 1,2
Total cooling capacity - 2-pipe (Hi) (1) kW 2,1
Sensible cooling capacity - 2-pipe (Lo) (1) kW 0,5
Sensible cooling capacity - 2-pipe (Med) (1) kW 1,1
Sensible cooling capacity - 2-pipe (Hi) (1) kW 1,9
Water flow - 2-pipe (Cooling) (Lo) l/h 107
Water flow - 2-pipe (Cooling) (Med) l/h 210
Water flow - 2-pipe (Cooling) (Hi) l/h 356
Water pressure drop - 2-pipe (Cooling) (Lo) kPa 8,2
Water pressure drop - 2-pipe (Cooling) (Med) kPa 28,2
Water pressure drop - 2-pipe (Cooling) (Hi) kPa 76,9
Heating capacity - 2-pipe (Lo) (2) kW 0,8
Heating capacity - 2-pipe (Med) (2) kW 1,6
Heating capacity - 2-pipe (Hi) (2) kW 2,9
4-pipe - Left connection PAW-FC4E-P010L
4-pipe - Right connection PAW-FC4E-P010R
Total cooling capacity - 4-pipe (Lo) (1) kW 0,5
Total cooling capacity - 4-pipe (Med) (1) kW 1,1
Total cooling capacity - 4-pipe (Hi) (1) kW 1,9
Sensible cooling capacity - 4-pipe (Lo) (1) kW 0,4
Sensible cooling capacity - 4-pipe (Med) (1) kW 0,9
Sensible cooling capacity - 4-pipe (Hi) (1) kW 1,7
Water flow - 4-pipe (Cooling) (Lo) l/h 92
Water flow - 4-pipe (Cooling) (Med) l/h 185
Water flow - 4-pipe (Cooling) (Hi) l/h 327
Water pressure drop - 4-pipe (Cooling) (Lo) kPa 5,8
Water pressure drop - 4-pipe (Cooling) (Med) kPa 20,1
Water pressure drop - 4-pipe (Cooling) (Hi) kPa 59,2
Heating capacity - 4-pipe (Lo) (2) kW 0,4
Heating capacity - 4-pipe (Med) (2) kW 0,8
Heating capacity - 4-pipe (Hi) (2) kW 1,4
Water flow (Heating) (Lo) l/h 76
Water flow (Heating) (Med) l/h 140
Water flow (Heating) (Hi) l/h 235
Water pressure drop (Heating) (Lo) kPa 1,8
Water pressure drop (Heating) (Med) kPa 4,0
Water pressure drop (Heating) (Hi) kPa 8,4
Sound levels .
Sound power (Lo) dB(A) 34
Sound power (Med) dB(A) 47
Sound power (Hi) dB(A) 60
Sound pressure (Lo) (3) dB(A) 25
Sound pressure (Med) (3) dB(A) 38
Sound pressure (Hi) (3) dB(A) 51
Fan data .
Number of fans 1
Air flow - 2-pipe (Lo) m³/h 108
Air flow - 2-pipe (Med) m³/h 228
Air flow - 2-pipe (Hi) m³/h 417
Air flow - 4-pipe (Lo) m³/h 91
Air flow - 4-pipe (Med) m³/h 199
Air flow - 4-pipe (Hi) m³/h 379
Filter G2
Electrical data .
Power supply (Voltage) V 230
Power supply (Phase) Single phase
Power supply (Frequency) Hz 50 / 60
Power consumption - 2-pipe (Lo) W 5
Power consumption - 2-pipe (Med) W 11
Power consumption - 2-pipe (Hi) W 41
Power consumption - 4-pipe (Lo) W 5
Power consumption - 4-pipe (Med) W 11
Power consumption - 4-pipe (Hi) W 39
Fan coils water connections .
Type of water connections Female gas threaded
Water connections - 2-pipe Inch 1/2
Water connections - 4-pipe (Cooling) Inch 1/2
Water connections - 4-pipe (Heating) Inch 1/2
Dimensions and weight .
Dimension (Height) mm 477
Dimension (Width) mm 225
Dimension (Depth) mm 766
Weight - 2-pipe kg 19
Weight - 4-pipe kg 20

1) According to Eurovent standard. Air: 27°C DB / 19°C WB. Water in/out: 7°C / 12°C.
2) Air: 20°C. Water in/out: 50°C / 45°C.
3) The sound pressure levels are based on (NR) characteristics of a room having volume of 100m³ with reverberation of 0,5 seconds.
* Without support feet.

Complementary products