Fan coils - Ducted (EC)

New range of fan coils. Designed to fit with your environment and enhance comfort

Panasonic introduces the new range of fan coils.

The key to this range is to provide performance and comfort and the ability to fit seamlessly within your environment.

Designed with user in mind, perfectly designed to adapt to any installation. Providing comfort to hotels, shops, restaurants, offices or residential applications.

Technical focus.
· Cooling capacity from 0,5 to 9,6kW
· Heating capacity from 0,6 to 13,6kW
· Low energy consumption EC fan(s)

Main features and accessories.
· 2 and 4-pipe configurations
· Left or right hand arrangements
· Can be installed both horizontally and vertically*
· Ease of installation
· Very low acoustic levels
· 2 way or 3 way ON/OFF valves
· Auxiliary drain pan
· Air intake with removable grid
· G2 filter

*PAW-FC2E-F040 and PAW-FC4E-F040 may only be installed horizontally.

The reasons to choose Panasonic as your partner

Explore the new range of fan coils

Specifications

See all
Fan coils - Ducted (EC)
9.2 kW
2-pipe - Left connection PAW-FC2E-F040L
2-pipe - Right connection PAW-FC2E-F040R
Total cooling capacity - 2-pipe (Lo) (1) kW 3,6
Total cooling capacity - 2-pipe (Med) (1) kW 6,6
Total cooling capacity - 2-pipe (Hi) (1) kW 9,2
Sensible cooling capacity - 2-pipe (Lo) (1) kW 2,9
Sensible cooling capacity - 2-pipe (Med) (1) kW 6,1
Sensible cooling capacity - 2-pipe (Hi) (1) kW 9,1
Water flow - 2-pipe (Cooling) (Lo) l/h 627
Water flow - 2-pipe (Cooling) (Med) l/h 1.142
Water flow - 2-pipe (Cooling) (Hi) l/h 1.575
Water pressure drop - 2-pipe (Cooling) (Lo) kPa 10,6
Water pressure drop - 2-pipe (Cooling) (Med) kPa 51,2
Water pressure drop - 2-pipe (Cooling) (Hi) kPa 93,8
Heating capacity - 2-pipe (Lo) (2) kW 4,4
Heating capacity - 2-pipe (Med) (2) kW 8,3
Heating capacity - 2-pipe (Hi) (2) kW 11,8
4-pipe - Left connection PAW-FC4E-F040L
4-pipe - Right connection PAW-FC4E-F040R
Total cooling capacity - 4-pipe (Lo) (1) kW 3,3
Total cooling capacity - 4-pipe (Med) (1) kW 6,4
Total cooling capacity - 4-pipe (Hi) (1) kW 8,8
Sensible cooling capacity - 4-pipe (Lo) (1) kW 2,7
Sensible cooling capacity - 4-pipe (Med) (1) kW 5,6
Sensible cooling capacity - 4-pipe (Hi) (1) kW 8,0
Water flow - 4-pipe (Cooling) (Lo) l/h 567
Water flow - 4-pipe (Cooling) (Med) l/h 1.093
Water flow - 4-pipe (Cooling) (Hi) l/h 1.511
Water pressure drop - 4-pipe (Cooling) (Lo) kPa 10,0
Water pressure drop - 4-pipe (Cooling) (Med) kPa 47,2
Water pressure drop - 4-pipe (Cooling) (Hi) kPa 86,7
Heating capacity - 4-pipe (Lo) (2) kW 2,5
Heating capacity - 4-pipe (Med) (2) kW 4,5
Heating capacity - 4-pipe (Hi) (2) kW 6,2
Water flow (Heating) (Lo) l/h 432
Water flow (Heating) (Med) l/h 783
Water flow (Heating) (Hi) l/h 1.065
Water pressure drop (Heating) (Lo) kPa 30,6
Water pressure drop (Heating) (Med) kPa 107,6
Water pressure drop (Heating) (Hi) kPa 214,8
Sound levels .
Sound power (Lo) dB(A) 42
Sound power (Med) dB(A) 58
Sound power (Hi) dB(A) 68*
Sound pressure (Lo) (3) dB(A) 23
Sound pressure (Med) (3) dB(A) 39
Sound pressure (Hi) (3) dB(A) 52
Fan data .
Number of fans 1
Air flow - 2-pipe (Lo) m³/h 592
Air flow - 2-pipe (Med) m³/h 1.284
Air flow - 2-pipe (Hi) m³/h 1.935
Air flow - 4-pipe (Lo) m³/h 523
Air flow - 4-pipe (Med) m³/h 1.222
Air flow - 4-pipe (Hi) m³/h 1.864
Maximum external pressure Pa 190
Filter G2
Electrical data .
Power supply (Voltage) V 230
Power supply (Phase) Single phase
Power supply (Frequency) Hz 50 / 60
Power consumption - 2-pipe (Lo) W 11
Power consumption - 2-pipe (Med) W 62
Power consumption - 2-pipe (Hi) W 197
Power consumption - 4-pipe (Lo) W 11
Power consumption - 4-pipe (Med) W 60
Power consumption - 4-pipe (Hi) W 188
Fan coils water connections .
Type of water connections Female gas threaded
Water connections - 2-pipe Inch 3/4
Water connections - 4-pipe (Cooling) Inch 3/4
Water connections - 4-pipe (Heating) Inch 1/2
Dimensions and weight .
Dimension (Height) mm 223
Dimension (Width) mm 1.233
Dimension (Depth) mm 653
Weight - 2-pipe kg 19
Weight - 4-pipe kg 19

1) According to Eurovent standard. Air: 27°C DB / 19°C WB. Water in/out: 7°C / 12°C.
2) Air: 20°C. Water in/out: 50°C / 45°C.
3) The sound pressure levels are based on (NR) characteristics of a room having volume of 100m³ with reverberation of 0,5 seconds.
* The sound power levels indicated are from return and radiated measurements.
Values indicated are for 0Pa external static pressure, for additional pressure characteristics, please refer the technical data manual.