· 5 sizes
· Cooling capacity from 6,6 to 19,9kW
· Heating capacity from 5,9 to 21,4kW
· Low energy consumption EC fan

Main features and accessories.
· 2 and 4-pipe, left & right hand configurations
· Static pressure up to 300Pa
· Double skin insulation
· 2 way or 3 way ON/OFF valves
· Auxiliary drain pan
· Air intake with removable grid
· G3 filter

Specifications

See all
Fan coils - High Static Pressure Ducted (EC)
17.3 kW
2-pipe - Left connection PAW-FC2E-E180L
2-pipe - Right connection PAW-FC2E-E180R
Total cooling capacity - 2-pipe (Lo) (1) kW 7,8
Total cooling capacity - 2-pipe (Med) (1) kW 13,1
Total cooling capacity - 2-pipe (Hi) (1) kW 17,3
Sensible cooling capacity - 2-pipe (Lo) (1) kW 5,7
Sensible cooling capacity - 2-pipe (Med) (1) kW 10,3
Sensible cooling capacity - 2-pipe (Hi) (1) kW 14,1
Water flow - 2-pipe (Cooling) (Lo) l/h 1.351
Water flow - 2-pipe (Cooling) (Med) l/h 2.259
Water flow - 2-pipe (Cooling) (Hi) l/h 2.979
Water pressure drop - 2-pipe (Cooling) (Lo) kPa 6,1
Water pressure drop - 2-pipe (Cooling) (Med) kPa 24,9
Water pressure drop - 2-pipe (Cooling) (Hi) kPa 41,5
Heating capacity - 2-pipe (Lo) (2) kW 9,5
Heating capacity - 2-pipe (Med) (2) kW 17,9
Heating capacity - 2-pipe (Hi) (2) kW 24,3
4-pipe - Left connection PAW-FC4E-E180L
4-pipe - Right connection PAW-FC4E-E180R
Total cooling capacity - 4-pipe (Lo) (1) kW 6,6
Total cooling capacity - 4-pipe (Med) (1) kW 10,2
Total cooling capacity - 4-pipe (Hi) (1) kW 13,0
Sensible cooling capacity - 4-pipe (Lo) (1) kW 4,9
Sensible cooling capacity - 4-pipe (Med) (1) kW 8,4
Sensible cooling capacity - 4-pipe (Hi) (1) kW 11,2
Water flow - 4-pipe (Cooling) (Lo) l/h 1.141
Water flow - 4-pipe (Cooling) (Med) l/h 1.764
Water flow - 4-pipe (Cooling) (Hi) l/h 2.243
Water pressure drop - 4-pipe (Cooling) (Lo) kPa 6,5
Water pressure drop - 4-pipe (Cooling) (Med) kPa 14,7
Water pressure drop - 4-pipe (Cooling) (Hi) kPa 23,2
Heating capacity - 4-pipe (Lo) (2) kW 6,1
Heating capacity - 4-pipe (Med) (2) kW 10,0
Heating capacity - 4-pipe (Hi) (2) kW 12,8
Water flow (Heating) (Lo) l/h 1.052
Water flow (Heating) (Med) l/h 1.729
Water flow (Heating) (Hi) l/h 2.211
Water pressure drop (Heating) (Lo) kPa 30,7
Water pressure drop (Heating) (Med) kPa 74,1
Water pressure drop (Heating) (Hi) kPa 116,4
Sound levels .
Sound power return + radiated (Lo) dB(A) 56
Sound power return + radiated (Med) dB(A) 67
Sound power return + radiated (Hi) dB(A) 74
Sound power discharge (Lo) dB(A) 56
Sound power discharge (Med) dB(A) 65
Sound power discharge (Hi) dB(A) 74
Sound pressure (Lo) (3) dB(A) 35
Sound pressure (Med) (3) dB(A) 46
Sound pressure (Hi) (3) dB(A) 52
Fan data .
Number of fans 1
Air flow - 2-pipe (Lo) m³/h 1.071
Air flow - 2-pipe (Med) m³/h 2.418
Air flow - 2-pipe (Hi) m³/h 3.583
Air flow - 4-pipe (Lo) m³/h 1.071
Air flow - 4-pipe (Med) m³/h 2.418
Air flow - 4-pipe (Hi) m³/h 3.583
Maximum external pressure Pa 300
Electrical data .
Power supply (Voltage) V 230
Power supply (Phase) Single phase
Power supply (Frequency) Hz 50 / 60
Power consumption (Lo) W 67
Power consumption (Med) W 172
Power consumption (Hi) W 246
Fan coils water connections .
Type of water connections Gas Male threaded
Water connections - 2-pipe Inch 1  
Water connections - 4-pipe (Cooling) Inch 1
Water connections - 4-pipe (Heating) Inch 3/4
Dimensions and weight .
Dimension (Height) mm 375
Dimension (Width) mm 798
Dimension (Depth) mm 1.380
Net weight kg 65

1) According to Eurovent standard. Air: 27°C DB / 19°C WB. Water in/out: 7°C / 12°C.
2) Air: 20°C. Water in/out: 50°C / 45°C.
3) Informative data: Considering an hypothetical sound attenuation of the room and installation of 21dB.