New range of fan coils. Designed to fit with your environment and enhance comfort

Panasonic introduces the new range of fan coils.

The key to this range is to provide performance and comfort and the ability to fit seamlessly within your environment.

Designed with user in mind, perfectly designed to adapt to any installation. Providing comfort to hotels, shops, restaurants, offices or residential applications.

Technical focus.
· Cooling capacity from 0,5 to 9,6kW
· Heating capacity from 0,6 to 13,6kW
· Low energy consumption EC fan(s)

Main features and accessories.
· 2 and 4-pipe configurations
· Left or right hand arrangements
· Can be installed both horizontally and vertically*
· Ease of installation
· Very low acoustic levels
· 2 way or 3 way ON/OFF valves
· Auxiliary drain pan
· Air intake with removable grid
· G2 filter

*PAW-FC2E-F040 and PAW-FC4E-F040 may only be installed horizontally.

The reasons to choose Panasonic as your partner

Explore the new range of fan coils

Specifications

See all
Fan coils - Ducted (EC)
5.0 kW
2-pipe - Left connection PAW-FC2E-D050L
2-pipe - Right connection PAW-FC2E-D050R
Total cooling capacity - 2-pipe (Lo) (1) kW 1,3
Total cooling capacity - 2-pipe (Med) (1) kW 4,0
Total cooling capacity - 2-pipe (Hi) (1) kW 5,0
Sensible cooling capacity - 2-pipe (Lo) (1) kW 1,1
Sensible cooling capacity - 2-pipe (Med) (1) kW 3,0
Sensible cooling capacity - 2-pipe (Hi) (1) kW 3,7
Water flow - 2-pipe (Cooling) (Lo) l/h 231
Water flow - 2-pipe (Cooling) (Med) l/h 685
Water flow - 2-pipe (Cooling) (Hi) l/h 743
Water pressure drop - 2-pipe (Cooling) (Lo) kPa 4,9
Water pressure drop - 2-pipe (Cooling) (Med) kPa 35,1
Water pressure drop - 2-pipe (Cooling) (Hi) kPa 41,0
Heating capacity - 2-pipe (Lo) (2) kW 1,7
Heating capacity - 2-pipe (Med) (2) kW 5,2
Heating capacity - 2-pipe (Hi) (2) kW 5,5
4-pipe - Left connection PAW-FC4E-D050L
4-pipe - Right connection PAW-FC4E-D050R
Total cooling capacity - 4-pipe (Lo) (1) kW 1,2
Total cooling capacity - 4-pipe (Med) (1) kW 3,6
Total cooling capacity - 4-pipe (Hi) (1) kW 4,6
Sensible cooling capacity - 4-pipe (Lo) (1) kW 1,0
Sensible cooling capacity - 4-pipe (Med) (1) kW 2,8
Sensible cooling capacity - 4-pipe (Hi) (1) kW 3,5
Water flow - 4-pipe (Cooling) (Lo) l/h 212
Water flow - 4-pipe (Cooling) (Med) l/h 625
Water flow - 4-pipe (Cooling) (Hi) l/h 686
Water pressure drop - 4-pipe (Cooling) (Lo) kPa 2,5
Water pressure drop - 4-pipe (Cooling) (Med) kPa 17,9
Water pressure drop - 4-pipe (Cooling) (Hi) kPa 21,3
Heating capacity - 4-pipe (Lo) (2) kW 1,6
Heating capacity - 4-pipe (Med) (2) kW 2,4
Heating capacity - 4-pipe (Hi) (2) kW 2,5
Water flow (Heating) (Lo) l/h 267
Water flow (Heating) (Med) l/h 416
Water flow (Heating) (Hi) l/h 438
Water pressure drop (Heating) (Lo) kPa 11,9
Water pressure drop (Heating) (Med) kPa 26,3
Water pressure drop (Heating) (Hi) kPa 28,9
Sound levels .
Sound power (Lo) dB(A) 30
Sound power (Med) dB(A) 51
Sound power (Hi) dB(A) 57
Sound pressure (Lo) (3) dB(A) 21
Sound pressure (Med) (3) dB(A) 42
Sound pressure (Hi) (3) dB(A) 48
Fan data .
Number of fans 2
Air flow - 2-pipe (Lo) m³/h 203
Air flow - 2-pipe (Med) m³/h 645
Air flow - 2-pipe (Hi) m³/h 816
Air flow - 4-pipe (Lo) m³/h 185
Air flow - 4-pipe (Med) m³/h 587
Air flow - 4-pipe (Hi) m³/h 646
Maximum external pressure Pa 70
Filter G2
Electrical data .
Power supply (Voltage) V 230
Power supply (Phase) Single phase
Power supply (Frequency) Hz 50 / 60
Power consumption - 2-pipe (Lo) W 4
Power consumption - 2-pipe (Med) W 24
Power consumption - 2-pipe (Hi) W 46
Power consumption - 4-pipe (Lo) W 2
Power consumption - 4-pipe (Med) W 23
Power consumption - 4-pipe (Hi) W 44
Fan coils water connections .
Type of water connections Female gas threaded
Water connections - 2-pipe Inch 1/2
Water connections - 4-pipe (Cooling) Inch 1/2
Water connections - 4-pipe (Heating) Inch 1/2
Dimensions and weight .
Dimension (Height) mm 220
Dimension (Width) mm 1.122
Dimension (Depth) mm 430
Weight - 2-pipe kg 22
Weight - 4-pipe kg 24

1) According to Eurovent standard. Air: 27°C DB / 19°C WB. Water in/out: 7°C / 12°C.
2) Air: 20°C. Water in/out: 50°C / 45°C.
3) The sound pressure levels are based on (NR) characteristics of a room having volume of 100m³ with reverberation of 0,5 seconds.
* The sound power levels indicated are from return and radiated measurements.
Values indicated are for 0Pa external static pressure, for additional pressure characteristics, please refer the technical data manual.

Complementary products