Fan coils - High Static Pressure Ducted (AC)

New range of fan coils. Designed to fit with your environment and enhance comfort

Panasonic introduces the new range of fan coils.

The key to this range is to provide performance and comfort and the ability to fit seamlessly within your environment.

Designed with user in mind, perfectly designed to adapt to any installation. Providing comfort to hotels, shops, restaurants, offices or residential applications.

Technical focus.
· 6 sizes
· Cooling capacity from 4,1 to 21,9kW
· Heating capacity from 4,7 to 21,5kW
· 5-speed AC fan motor

Main features and accessories.
· 2 and 4-pipe, left & right hand configurations
· Static pressure up to 220Pa
· Double skin insulation
· 2 way or 3 way ON/OFF valves
· Auxiliary drain pan
· Air intake with removable grid
· G3 filter

The reasons to choose Panasonic as your partner

Explore the new range of fan coils

Specifications

See all
Fan coils - High Static Pressure Ducted (AC)
15.0 kW
2-pipe - Left connection PAW-FC2A-E180L
2-pipe - Right connection PAW-FC2A-E180R
Total cooling capacity - 2-pipe (Lo) (1) kW 4,9
Total cooling capacity - 2-pipe (Med) (1) kW 11,5
Total cooling capacity - 2-pipe (Hi) (1) kW 15,0
Sensible cooling capacity - 2-pipe (Lo) (1) kW 3,7
Sensible cooling capacity - 2-pipe (Med) (1) kW 9,5
Sensible cooling capacity - 2-pipe (Hi) (1) kW 13,1
Water flow - 2-pipe (Cooling) (Lo) l/h 837
Water flow - 2-pipe (Cooling) (Med) l/h 1.979
Water flow - 2-pipe (Cooling) (Hi) l/h 2.589
Water pressure drop - 2-pipe (Cooling) (Lo) kPa 4,4
Water pressure drop - 2-pipe (Cooling) (Med) kPa 19,6
Water pressure drop - 2-pipe (Cooling) (Hi) kPa 32,0
Heating capacity - 2-pipe (Lo) (2) kW 6,3
Heating capacity - 2-pipe (Med) (2) kW 16,3
Heating capacity - 2-pipe (Hi) (2) kW 23,2
4-pipe - Left connection PAW-FC4A-E180L
4-pipe - Right connection PAW-FC4A-E180R
Total cooling capacity - 4-pipe (Lo) (1) kW 5,5
Total cooling capacity - 4-pipe (Med) (1) kW 11,2
Total cooling capacity - 4-pipe (Hi) (1) kW 13,6
Sensible cooling capacity - 4-pipe (Lo) (1) kW 3,9
Sensible cooling capacity - 4-pipe (Med) (1) kW 9,1
Sensible cooling capacity - 4-pipe (Hi) (1) kW 12,0
Water flow - 4-pipe (Cooling) (Lo) l/h 951
Water flow - 4-pipe (Cooling) (Med) l/h 1.928
Water flow - 4-pipe (Cooling) (Hi) l/h 2.335
Water pressure drop - 4-pipe (Cooling) (Lo) kPa 4,7
Water pressure drop - 4-pipe (Cooling) (Med) kPa 17,4
Water pressure drop - 4-pipe (Cooling) (Hi) kPa 25,0
Heating capacity - 4-pipe (Lo) (2) kW 5,3
Heating capacity - 4-pipe (Med) (2) kW 11,9
Heating capacity - 4-pipe (Hi) (2) kW 15,9
Water flow (Heating) (Lo) l/h 911
Water flow (Heating) (Med) l/h 2.045
Water flow (Heating) (Hi) l/h 2.745
Water pressure drop (Heating) (Lo) kPa 23,9
Water pressure drop (Heating) (Med) kPa 100,8
Water pressure drop (Heating) (Hi) kPa 174,3
Sound levels .
Sound power return + radiated (Lo) dB(A) 54
Sound power return + radiated (Med) dB(A) 66
Sound power return + radiated (Hi) dB(A) 74
Sound power discharge (Lo) dB(A) 52
Sound power discharge (Med) dB(A) 64
Sound power discharge (Hi) dB(A) 71
Sound pressure (Lo) (3) dB(A) 31
Sound pressure (Med) (3) dB(A) 45
Sound pressure (Hi) (3) dB(A) 51
Fan data .
Number of fans 1
Air flow - 2-pipe (Lo) m³/h 676
Air flow - 2-pipe (Med) m³/h 2.110
Air flow - 2-pipe (Hi) m³/h 3.197
Air flow - 4-pipe (Lo) m³/h 676
Air flow - 4-pipe (Med) m³/h 2.110
Air flow - 4-pipe (Hi) m³/h 3.197
Maximum external pressure Pa 200
Filter G3
Electrical data .
Power supply (Voltage) V 230
Power supply (Phase) Single phase
Power supply (Frequency) Hz 50 / 60
Power consumption (Lo) W 180
Power consumption (Med) W 421
Power consumption (Hi) W 675
Fan coils water connections .
Type of water connections Gas Male threaded
Water connections - 2-pipe Inch 1 ¼
Water connections - 4-pipe (Cooling) Inch 1
Water connections - 4-pipe (Heating) Inch 3/4
Dimensions and weight .
Dimension (Height) mm 375
Dimension (Width) mm 798
Dimension (Depth) mm 1.380
Net weight kg 65

1) According to Eurovent standard. Air: 27°C DB / 19°C WB. Water in/out: 7°C / 12°C.
2) Air: 20°C. Water in/out: 50°C / 45°C.
3) Informative data: Considering an hypothetical sound attenuation of the room and installation of 21dB.
Values indicated are for 50Pa external static pressure, for additional pressure characteristics, please refer the technical data manual.
* High fan speed used for capacity, water flow, sound and air flow values.