New range of fan coils. Designed to fit with your environment and enhance comfort

Panasonic introduces the new range of fan coils.

The key to this range is to provide performance and comfort and the ability to fit seamlessly within your environment.

Designed with user in mind, perfectly designed to adapt to any installation. Providing comfort to hotels, shops, restaurants, offices or residential applications.

Technical focus.
· Cooling capacity from 0,7 to 8,1kW
· Heating capacity from 0,7 to 10,3kW
· 5-speed AC fan motor(s)

Main features and accessories.
· 2 and 4-pipe configurations
· Left or right hand arrangements
· Ease of installation
· Very low acoustic levels
· 2 way or 3 way ON/OFF valves
· Auxiliary drain pan
· Air intake with removable grid
· G2 filter

The reasons to choose Panasonic as your partner

Explore the new range of fan coils

Specifications

See all
Fan coils - Ducted (AC)
4.6 kW
2-pipe - Left connection PAW-FC2A-D050L
2-pipe - Right connection PAW-FC2A-D050R
Total cooling capacity - 2-pipe (Lo) (1) kW 1,7
Total cooling capacity - 2-pipe (Med) (1) kW 3,2
Total cooling capacity - 2-pipe (Hi) (1) kW 4,6
Sensible cooling capacity - 2-pipe (Lo) (1) kW 1,2
Sensible cooling capacity - 2-pipe (Med) (1) kW 2,2
Sensible cooling capacity - 2-pipe (Hi) (1) kW 3,3
Water flow - 2-pipe (Cooling) (Lo) l/h 296
Water flow - 2-pipe (Cooling) (Med) l/h 544
Water flow - 2-pipe (Cooling) (Hi) l/h 798
Water pressure drop - 2-pipe (Cooling) (Lo) kPa 7,5
Water pressure drop - 2-pipe (Cooling) (Med) kPa 22,8
Water pressure drop - 2-pipe (Cooling) (Hi) kPa 46,9
Heating capacity - 2-pipe (Lo) (2) kW 2,1
Heating capacity - 2-pipe (Med) (2) kW 4,1
Heating capacity - 2-pipe (Hi) (2) kW 5,7
4-pipe - Left connection PAW-FC4A-D050L
4-pipe - Right connection PAW-FC4A-D050R
Total cooling capacity - 4-pipe (Lo) (1) kW 1,7
Total cooling capacity - 4-pipe (Med) (1) kW 3,0
Total cooling capacity - 4-pipe (Hi) (1) kW 4,3
Sensible cooling capacity - 4-pipe (Lo) (1) kW 1,2
Sensible cooling capacity - 4-pipe (Med) (1) kW 2,2
Sensible cooling capacity - 4-pipe (Hi) (1) kW 3,1
Water flow - 4-pipe (Cooling) (Lo) l/h 284
Water flow - 4-pipe (Cooling) (Med) l/h 522
Water flow - 4-pipe (Cooling) (Hi) l/h 748
Water pressure drop - 4-pipe (Cooling) (Lo) kPa 4,2
Water pressure drop - 4-pipe (Cooling) (Med) kPa 12,8
Water pressure drop - 4-pipe (Cooling) (Hi) kPa 25,1
Heating capacity - 4-pipe (Lo) (2) kW 1,5
Heating capacity - 4-pipe (Med) (2) kW 2,3
Heating capacity - 4-pipe (Hi) (2) kW 3,0
Water flow (Heating) (Lo) l/h 251
Water flow (Heating) (Med) l/h 401
Water flow (Heating) (Hi) l/h 508
Water pressure drop (Heating) (Lo) kPa 10,7
Water pressure drop (Heating) (Med) kPa 24,6
Water pressure drop (Heating) (Hi) kPa 29,5
Sound levels .
Sound power (Lo) dB(A) 34
Sound power (Med) dB(A) 46
Sound power (Hi) dB(A) 56
Sound pressure (Lo) (3) dB(A) 25
Sound pressure (Med) (3) dB(A) 37
Sound pressure (Hi) (3) dB(A) 47
Fan data .
Number of fans 2
Air flow - 2-pipe (Lo) m³/h 253
Air flow - 2-pipe (Med) m³/h 486
Air flow - 2-pipe (Hi) m³/h 716
Air flow - 4-pipe (Lo) m³/h 242
Air flow - 4-pipe (Med) m³/h 466
Air flow - 4-pipe (Hi) m³/h 671
Maximum external pressure Pa 85
Filter G2
Electrical data .
Power supply (Voltage) V 230
Power supply (Phase) Single phase
Power supply (Frequency) Hz 50 / 60
Power consumption - 2-pipe (Lo) W 28
Power consumption - 2-pipe (Med) W 55
Power consumption - 2-pipe (Hi) W 72
Power consumption - 4-pipe (Lo) W 28
Power consumption - 4-pipe (Med) W 54
Power consumption - 4-pipe (Hi) W 70
Fan coils water connections .
Type of water connections Female gas threaded
Water connections - 2-pipe Inch 1/2
Water connections - 4-pipe (Cooling) Inch 1/2
Water connections - 4-pipe (Heating) Inch 1/2
Dimensions and weight .
Dimension (Height) mm 220
Dimension (Width) mm 1.122
Dimension (Depth) mm 430
Weight - 2-pipe kg 22
Weight - 4-pipe kg 24

1) According to Eurovent standard. Air: 27°C DB / 19°C WB. Water in/out: 7°C / 12°C.
2) Air: 20°C. Water in/out: 50°C / 45°C.
3) The sound pressure levels are based on (NR) characteristics of a room having volume of 100m³ with reverberation of 0,5 seconds.
Values indicated are for 0Pa external static pressure, for additional pressure characteristics, please refer the technical data manual.

Complementary products