Aquarea Air Smart fan coil ducted

Aquarea Air Smart fan coil ducted

High efficiency ducted fan coil for high comfort and quiet operation thanks to self modulating air flow control. Designed to provide both heating and cooling in one compact unit, they maximise energy savings when combined with an Aquarea Heat Pumps.

Specifications

See all
Aquarea Air Smart fan coil ducted
2.60 kW
Type Ducted thin
Model P-FTN25
Fan speed (1) Min / Med / Max
Total cooling capacity (Min) (2) kW 1,23
Total cooling capacity (Med) (2) kW 2,17
Total cooling capacity (Max) (2) kW 2,6
Sensible capacity (Min) (2) kW 0,88
Sensible capacity (Med) (2) kW 1,56
Sensible capacity (Max) (2) kW 2,1
Water flow cooling (Min) (2) l/h 211
Water flow cooling (Med) (2) l/h 373
Water flow cooling (Max) (2) l/h 510
Water pressure drop cooling (Min) (2) kPa 4
Water pressure drop cooling (Med) (2) kPa 10
Water pressure drop cooling (Max) (2) kPa 17
Heating capacity (Min) (3) kW 1,32
Heating capacity (Med) (3) kW 2,32
Heating capacity (Max) (3) kW 2,86
Water flow heating (Min) (3) l/h 235
Water flow heating (Med) (3) l/h 410
Water flow heating (Max) (3) l/h 540
Water pressure drop heating (Min) (3) kPa 4
Water pressure drop heating (Med) (3) kPa 11
Water pressure drop heating (Max) (3) kPa 18
Sound levels .
Sound power (Min) dB(A) 45
Sound power (Med) dB(A) 52
Sound power (Max) dB(A) 58
Ventilation .
Number of fans 2
Air flow (Min) m³/h 190
Air flow (Med) m³/min 390
Air flow (Max) m³/h 550
Single zone air flow (Min) m³/h 120
Electrical data .
Power supply (Voltage) V 230
Power supply (Phase) Single phase
Power supply (Frequency) Hz 50
Consumption (Min) W 26
Consumption (Med) W 65
Consumption (Max) W 160
Degree of protection IP X0
Fan coils water connections .
Hydraulic connections type Eurokonus
Hydraulic connections Inch ¾
Condensate drainage connection mm 20
Intake air connection (base x height) mm 860 x 100
Return air connection (base x height) mm 910 x 100
Dimensions and weight .
Dimension (Height) mm 185
Dimension (Width) mm 990
Dimension (Depth) mm 575
Net weight kg 45

1) Fan standard factory set speeds.
2) According to Eurovent standard. Air: 27°C DB/19°C WB, chilled water: 7°C/12°C (for water pressure drop data: pressure loss by corresponding nominal flow).
3) According to Eurovent standard. Air: 20°C, hot water: 45°C/40°C. Pressure loss by corresponding nominal flow (for water pressure drop data: pressure loss by corresponding nominal flow)
.