Aquarea Air Smart fan coil ducted

Aquarea Air Smart fan coil ducted

High efficiency ducted fan coil for high comfort and quiet operation thanks to self modulating air flow control. Designed to provide both heating and cooling in one compact unit, they maximise energy savings when combined with an Aquarea Heat Pumps.

Specifications

See all
Aquarea Air Smart fan coil ducted
1.88 kW
Type Ducted
Model P-FSN20
Fan speed (1) Min / Med / Max
Total cooling capacity (Min) (2) kW 0,82
Total cooling capacity (Med) (2) kW 1,37
Total cooling capacity (Max) (2) kW 1,88
Sensible capacity (Min) (2) kW 0,61
Sensible capacity (Med) (2) kW 0,96
Sensible capacity (Max) (2) kW 1,48
Water flow cooling (Min) (2) l/h 141
Water flow cooling (Med) (2) l/h 235
Water flow cooling (Max) (2) l/h 322
Water pressure drop cooling (Min) (2) kPa 9,2
Water pressure drop cooling (Med) (2) kPa 11,8
Water pressure drop cooling (Max) (2) kPa 15,7
Heating capacity (Min) (3) kW 0,9
Heating capacity (Med) (3) kW 1,48
Heating capacity (Max) (3) kW 1,98
Water flow heating (Min) (3) l/h 159
Water flow heating (Med) (3) l/h 261
Water flow heating (Max) (3) l/h 349
Water pressure drop heating (Min) (3) kPa 51
Water pressure drop heating (Med) (3) kPa 12
Water pressure drop heating (Max) (3) kPa 16,3
Sound levels .
Sound power (Min) dB(A) 46
Sound power (Med) dB(A) 54
Sound power (Max) dB(A) 58
Ventilation .
Number of fans 1
Air flow (Min) m³/h 120
Air flow (Med) m³/min 260
Air flow (Max) m³/h 390
Single zone air flow (Min) m³/h 90
Electrical data .
Power supply (Voltage) V 230
Power supply (Phase) Single phase
Power supply (Frequency) Hz 50
Consumption (Min) W 6
Consumption (Med) W 11
Consumption (Max) W 24
Degree of protection IP X0
Fan coils water connections .
Hydraulic connections type Eurokonus
Hydraulic connections Inch ¾
Condensate drainage connection mm 20
Intake air connection (base x height) mm 460 x 150
Return air connection (base x height) mm 510 x 150
Dimensions and weight .
Dimension (Height) mm 240
Dimension (Width) mm 590
Dimension (Depth) mm 695
Net weight kg 32

1) Fan standard factory set speeds.
2) According to Eurovent standard. Air: 27°C DB/19°C WB, chilled water: 7°C/12°C (for water pressure drop data: pressure loss by corresponding nominal flow).
3) According to Eurovent standard. Air: 20°C, hot water: 45°C/40°C. Pressure loss by corresponding nominal flow (for water pressure drop data: pressure loss by corresponding nominal flow)
.