NX Series Jet Air Stream

PACi NX Jet Air Stream

Energy-saving solution for year-round heating and cooling in large and high

High air distribution for large spaces
· High air volume up to 5000m³/h
· Long maximum air throw distance of 30m

Optimal comfort with Smart Jet - self-directing nozzles
· Precise temperature control
· Preventing stratification and maintaining an ideal temperature exclusively in the occupied area

The next generation of commercial air conditioners is here

Specifications

See all
NX Series Jet Air Stream
24.2 kW
Kit KIT-250MC5ZH8
Remote controller PCZ-AHRX0012
Cooling capacity (Nominal) kW 24,2
Cooling capacity (Min) kW 6,1
Cooling capacity (Max) kW 25,6
EER (Nominal) (1) W/W 3,8
EER (Min) (1) W/W 2,49
EER (Max) (1) W/W 4,88
ηs,c (2) % 250%
Heating capacity (Nominal) kW 26,7
Heating capacity (Min) kW 5,5
Heating capacity (Max) kW 27,6
COP (Nominal) (1) W/W 3,74
COP (Min) (1) W/W 3,07
COP (Max) (1) W/W 4,78
Model Jet Air Stream Smart
ηs,h (2) 155%
Indoor unit P-VTVF250MC5-PE
Pdesign at -10°C kW 18,5
Nozzles type Smart Jet - self-directing nozzles
Number of nozzles 4
External static pressure Pa 170
Air flow m³/min 5.010
Indoor dimension (Height) mm 1.026
Indoor dimension (Width) mm 1.458
Indoor sound pressure (Cool) (3) dB(A) 46
Indoor dimension (Depth) mm 953
Indoor sound pressure (Heat) (3) dB(A) 46
Indoor net weight kg 130
Outdoor unit U-250PZH4E8
Power supply (Voltage) V 380 - 400 - 415
Power supply (Phase) Three phase
Power supply (Frequency) Hz 50
Recommended fuse A 30
Outdoor sound pressure (Cool - Hi) dB(A) 59
Outdoor sound pressure (Heat - Hi) dB(A) 63
Outdoor dimension (Height) mm 996
Outdoor dimension (Width) mm 1.140
Outdoor dimension (Depth) mm 460
Outdoor net weight kg 109
Piping diameter (Liquid) Inch (mm) 1/2 (12,70)
Piping diameter (Gas) Inch (mm) 7/8 (22,22)
Pipe length range m 5 ~ 100
Elevation difference (in/out) m 30
Pre-charged pipe length m 30
Additional gas amount g/m 80
Refrigerant (R32) / CO2 Eq. kg / T 4,80 / 3,24
Operating range (Cool - Min) °C -15
Operating range (Cool - Max) °C 52
Operating range (Heat - Min) °C -20
Operating range (Heat - Max) °C 35

1) EER and COP calculation is based in accordance to EN 14511.
2) For models above 12kW, the ηs,c / ηs,h values is calculated based on EN 14825.
3) Average sound pressure at 5m Lp.
4) Radiated sound power at 5 mLp.
5) Outdoor unit located lower / outdoor unit located higher.
6) Pipe length up to 30m
.