Models
4-cestná kazeta 60x60 - PY3
Od 3,6 do 6,0 kW (3 veľkosti výkonu).
Rozmery podvozku (v x š x h): 243 x 575 x 575 mm.
Trieda SEER/SCOP A++*.
Zabudované vypúšťacie čerpadlo.
* Trieda SCOP A+ v prípade 3,6 a 5,0 kW.
Kompaktný a štýlový dizajn.
Hĺbka stropu je len 250 mm
Odkrytá plocha je len 30 mm
Špičková energetická účinnosť v odvetví.
Dosiahnutá trieda SEER/SCOP A++*.
* Trieda SCOP A+ v prípade 3,6 a 5,0 kW.
Individuálne ovládanie klapiek.
Lepšie ovládanie prúdenia vzduchu pomocou 4 motorov.
Špecifikácie
PACi NX Series Elite 4-cestný kazetový menič 60x60 - R32 | SINGLE PHASE | ||||
---|---|---|---|---|---|
3.6 kW | 5.0 kW | 6.0 kW | |||
Kit | KIT-36PY3ZH5 | KIT-50PY3ZH5 | KIT-60PY3ZH5 | ||
Remote controller | CZ-RTC5B | CZ-RTC5B | CZ-RTC5B | ||
Cooling capacity (Nominal) | kW | 3,6 | 5,0 | 6,0 | |
Cooling capacity (Min) | kW | 1,2 | 1,2 | 1,2 | |
Cooling capacity (Max) | kW | 4,0 | 5,6 | 6,5 | |
EER (Nominal) (1) | W/W | 4,50 | 3,76 | 3,43 | |
EER (Min) (1) | W/W | 4,04 | 3,41 | 2,77 | |
EER (Max) (1) | W/W | 5,45 | 5,45 | 5,45 | |
SEER (2) | 7,3 A++ | 7,0 A++ | 6,7 A++ | ||
Pdesign (cooling) | kW | 3,6 | 5,0 | 6,0 | |
Input power cooling (Nominal) | kW | 0,80 | 1,33 | 1,75 | |
Input power cooling (Min) | kW | 0,22 | 0,22 | 0,20 | |
Input power cooling (Max) | kW | 0,99 | 1,64 | 2,35 | |
Annual energy consumption cooling (3) | kWh/a | 400 | 685 | 875 | |
Heating capacity (Nominal) | kW | 4,0 | 5,6 | 7,0 | |
Heating capacity (Min) | kW | 1,2 | 1,2 | 1,2 | |
Heating capacity (Max) | kW | 5,0 | 6,5 | 7,5 | |
COP (Nominal) (1) | W/W | 4,12 | 3,37 | 3,35 | |
COP (Min) (1) | W/W | 3,45 | 2,95 | 3,38 | |
COP (Max) (1) | W/W | 5,45 | 5,45 | 5,45 | |
SCOP (2) | 4,7 A++ | 4,6 A++ | 4,3 A+ | ||
Pdesign at -10°C | kW | 3,6 | 4,5 | 4,6 | |
Input power heating (Nominal) | kW | 0,97 | 1,66 | 2,09 | |
Input power heating (Min) | kW | 0,22 | 0,22 | 0,22 | |
Input power heating (Max) | kW | 1,45 | 2,20 | 2,22 | |
Annual energy consumption heating (3) | kWh/a | 1.073 | 1.370 | 1.495 | |
Indoor unit | S-36PY3E | S-50PY3E | S-60PY3E | ||
Indoor air flow (Hi) | m³/min | 9,5 | 12,0 | 14,0 | |
Indoor air flow (Med) | m³/min | 7,5 | 9,5 | 10,5 | |
Indoor air flow (Lo) | m³/min | 6,0 | 6,5 | 8,0 | |
Moisture removal volume | L/h | 1,5 | 2,5 | 2,8 | |
Indoor sound pressure (Med) (4) | dB(A) | 30 | 34 | 37 | |
Indoor sound pressure (Lo) (4) | dB(A) | 25 | 27 | 31 | |
Indoor sound power (Hi) | dB(A) | 49 | 54 | 58 | |
Indoor sound power (Med) | dB(A) | 45 | 49 | 52 | |
Indoor sound power (Lo) | dB(A) | 40 | 42 | 46 | |
Indoor dimension (Height) | mm | 243 | 243 | 243 | |
Indoor dimension (Width) | mm | 575 | 575 | 575 | |
Indoor dimension (Depth) | mm | 575 | 575 | 575 | |
Panel dimension (Height) | mm | 30 | 30 | 30 | |
Panel dimension (Depth) | mm | 625 | 625 | 625 | |
Indoor net weight | kg | 15 | 15 | 15 | |
Panel net weight | kg | 2,8 | 2,8 | 2,8 | |
nanoe X Generator | Mark 2 | Mark 2 | Mark 2 | ||
Outdoor unit | U-36PZH3E5 | U-50PZH3E5 | U-60PZH3E5 | ||
Outdoor power source | V | 220 - 230 - 240 | 220 - 230 - 240 | 220 - 230 - 240 | |
Current in cooling (1p 220V / 3p 380) | A | 3,95 | 5,30 | 8,20 | |
Current in cooling (1p 230V / 3p 400) | A | 3,60 | 5,00 | 7,85 | |
Current in cooling (1p 240V / 3p 415) | A | 3,60 | 5,75 | 7,60 | |
Current in heating (1p 220V / 3p 380) | A | 4,75 | 7,85 | 9,70 | |
Current in heating (1p 230V / 3p 400) | A | 4,55 | 7,50 | 9,25 | |
Current in heating (1p 240V / 3p 415) | A | 4,35 | 7,20 | 8,90 | |
Outdoor air flow (Cool) | m³/min | 34,1 | 42,0 | 42,0 | |
Outdoor air flow (Heat) | m³/min | 36,4 | 42,0 | 42,0 | |
Outdoor sound pressure (Cool - Hi) | dB(A) | 43 | 46 | 47 | |
Outdoor sound pressure (Heat - Hi) | dB(A) | 44 | 48 | 50 | |
Outdoor sound power (Cool -Hi) | dB(A) | 62 | 64 | 65 | |
Outdoor sound power (Heat -Hi) | dB(A) | 64 | 67 | 69 | |
Outdoor dimension (Height) | mm | 695 | 695 | 695 | |
Outdoor dimension (Width) | mm | 875 | 875 | 875 | |
Outdoor dimension (Depth) | mm | 320 | 320 | 320 | |
Outdoor net weight | kg | 42 | 42 | 43 | |
Piping diameter (Liquid) | Inch (mm) | 1/4 (6,35) | 1/4 (6,35) | 1/4 (6,35) (5) | |
Piping diameter (Gas) | Inch (mm) | 1/2 (12,70) | 1/2 (12,70) | 1/2 (12,70) (6) | |
Pipe length range | m | 3 ~ 40 | 3 ~ 40 | 3 ~ 40 | |
Elevation difference (in/out) (5) | m | 15 / 30 | 15 / 30 | 15 / 30 | |
Pre-charged pipe length | m | 30 | 30 | 30 | |
Additional gas amount | g/m | 15 | 15 | 15 | |
Refrigerant (R32) / CO2 Eq. | kg / T | 1,13 / 0,76 | 1,13 / 0,76 | 1,15 / 0,78 | |
Operating range (Cool - Min) | °C | -15 | -15 | -15 | |
Operating range (Cool - Max) | °C | +46 | +46 | +46 | |
Operating range (Heat - Min) | °C | -20 | -20 | -20 | |
Operating range (Heat - Max) | °C | +24 | +24 | +24 |
1) Výpočet EER a COP vychádza z normy EN14511.
2) Pri modeloch s výkonom nižším ako 12 kW sa SEER a SCOP vypočítavajú na základe hodnôt EÚ/626/2011. Pre modely nad 12 kW sa hodnoty ηsc / ηsh vypočítavajú na základe normy EN 14825.
3) Nastavenie z výroby.
4) Akustický tlak jednotiek zobrazuje hodnotu nameranú z polohy 1,5 m pod jednotkou. Akustický tlak sa meria v súlade so špecifikáciou Eurovent 6/C/006-97.
5) Pripojte rúrku kvapalinovej zásuvky (Ø6,35-Ø9,52) k vnútornej jednotke na strane kvapalinovej hadice.
6) Pripojte rúrku plynovej zásuvky (Ø12,70-Ø15,88) k vnútornej jednotke na strane plynovej hadice.
7) Pri inštalácii vonkajšej jednotky vo vyššej polohe ako vnútorná jednotka.
8) Vonkajšia jednotka umiestnená nižšie / vonkajšia jednotka umiestnená vyššie.
* Odporúčaná poistka pre vnútornú jednotku 3A.
** Uvedené hodnoty sú v prípade nanoe™ X OFF.
*** K dispozícii na jeseň 2021.
**** Predbežné údaje.