2-rúrkový hybridný GHP/EHP

Hybridný systém Panasonic GHP/EHP. Prvá inteligentná technológia

Využitie výhod plynu a elektriny na dosiahnutie ešte lepšej úspory energie.

Špecifikácie

Pozri všetky
2-rúrkový hybridný GHP/EHP SINGLE PHASE THREE PHASE
20 kW 10 kW
System Hybrid GHP Hybrid EHP
HP 20HP 10HP
Outdoor unit U-20GES3E5 U-10MES2E8
Power supply (Voltage) V 220 - 230 - 240 380 - 400 - 415 
Power supply (Phase) Single phase Three phase
Power supply (Frequency) Hz 50 50
Cooling capacity (Nominal) kW 56,0 28,0
Cooling ηsc (LOT21) (1) % 211,80 275,40
Current cooling A 5,18 10,70 / 10,20 / 9,80
Input power cooling kW 1,12 6,41
Hot water in cooling mode (at 65°C outlet) kW 26,20
Gas consumption cooling kW 52,10
Heating capacity (Nominal) kW 63,0 31,5
Heating ηsh (LOT21) (1) % 143,20 167,60
Current heating A 4,79 11,10 / 10,50 / 10,10
Input power heating kW 1,05 6,62
Gas consumption heating (Standard) kW 51,10
Starting current A 30 1
Air flow m³/min 420 224
Sound pressure (Normal mode) dB(A) 58 56
Sound power (Normal mode) dB(A) 80 77
Dimension (Height) mm 2.255 1.842
Dimension (Width) mm 1.650 770
Dimension (Depth) mm 1.000 1.000
Net weight kg 765 210
Refrigerant (R410A) / CO2 Eq. kg / T 5/8 (15,88) 3/8 (9,52)
Piping diameter (Liquid) (2) Inch (mm) 1 1/8 (28,58) 7/8 (22,22)
Piping diameter (Gas) (2) Inch (mm) 1/4 (6,35) 1/4 (6,35)
Piping diameter (Balance) (2) Inch (mm) 40
Drain heater W 11,05 / 23,0724 5,60 / 11,6928
Maximum allowable indoor / outdoor capacity ratio % 50 ~ 130 50 ~ 130
Operating range (Cool - Min) °C -10 -10
Operating range (Cool - Max) °C +43 +43
Operating range (Heat - Min) °C -21 -21
Operating range (Heat - Max) °C +18 +18

1) SEER/SCOP sa vypočítava na základe hodnôt sezónnej účinnosti chladenia/vykurovania priestoru "η" podľa NARIADENIA KOMISIE (EÚ) 2016/2281.
2) Ak maximálna dĺžka potrubia presahuje 90 metrov (ekvivalentná dĺžka), pozrite si servisnú príručku.

Čo sa deje