PACi NX Series Standard 4-cestný kazetový menič 60x60 - R32
4-cestná kazeta 60x60 - PY3
Od 2,5 do 6,0 kW (4 veľkosti výkonu)
Rozmery podvozku (v x š x h): 243 x 575 x 575 mm
Zabudované vypúšťacie čerpadlo
Kompaktný a štýlový dizajn.
Hĺbka stropu je len 250 mm
Odkrytá plocha je len 30 mm
Individuálne ovládanie klapky.
Lepšie ovládanie prúdenia vzduchu pomocou 4 motorov.
Špecifikácie
PACi NX Series Standard 4-cestný kazetový menič 60x60 - R32 | |||
---|---|---|---|
3.6 kW | |||
Kit | KIT-35PY3Z5 | ||
Remote controller | CZ-RTC5B | ||
Cooling capacity (Nominal) | kW | 3,6 | |
Cooling capacity (Min) | kW | 1,5 | |
Cooling capacity (Max) | kW | 4,0 | |
EER (Nominal) (1) | W/W | 3,96 | |
EER (Min) (1) | W/W | 3,57 | |
EER (Max) (1) | W/W | 5,88 | |
SEER (2) | 6,7 A++ | ||
Pdesign (cooling) | kW | 3,6 | |
Input power cooling (Nominal) | kW | 0,91 | |
Input power cooling (Min) | kW | 0,26 | |
Input power cooling (Max) | kW | 1,12 | |
Annual energy consumption cooling (3) | kWh/a | 188 | |
Heating capacity (Nominal) | kW | 3,6 | |
Heating capacity (Min) | kW | 1,5 | |
Heating capacity (Max) | kW | 4,6 | |
COP (Nominal) (1) | W/W | 4,29 | |
COP (Min) (1) | W/W | 3,38 | |
COP (Max) (1) | W/W | 6,52 | |
SCOP (2) | 4,3 A+ | ||
Pdesign at -10°C | kW | 2,8 | |
Input power heating (Nominal) | kW | 0,84 | |
Input power heating (Min) | kW | 0,23 | |
Input power heating (Max) | kW | 1,36 | |
Annual energy consumption heating (3) | kWh/a | 912 | |
Indoor unit | S-36PY3E | ||
Indoor air flow (Hi) | m³/min | 9,5 | |
Indoor air flow (Med) | m³/min | 7,0 | |
Indoor air flow (Lo) | m³/min | 6,0 | |
Moisture removal volume | L/h | 1,5 | |
Indoor sound pressure (Med) (4) | dB(A) | 30 | |
Indoor sound pressure (Lo) (4) | dB(A) | 25 | |
Indoor sound power (Hi) | dB(A) | 49 | |
Indoor sound power (Med) | dB(A) | 45 | |
Indoor sound power (Lo) | dB(A) | 40 | |
Indoor dimension (Height) | mm | 243 | |
Indoor dimension (Width) | mm | 575 | |
Indoor dimension (Depth) | mm | 575 | |
Panel dimension (Height) | mm | 30 | |
Panel dimension (Depth) | mm | 625 | |
Indoor net weight | kg | 15 | |
Panel net weight | kg | 2,8 | |
nanoe X Generator | Mark 2 | ||
Outdoor unit | U-36PZ3E5 | ||
Outdoor power source | V | 220 - 230 - 240 | |
Current in cooling (1p 220V / 3p 380) | A | 4,20 | |
Current in cooling (1p 230V / 3p 400) | A | 4,05 | |
Current in cooling (1p 240V / 3p 415) | A | 3,85 | |
Current in heating (1p 220V / 3p 380) | A | 3,95 | |
Current in heating (1p 230V / 3p 400) | A | 3,75 | |
Current in heating (1p 240V / 3p 415) | A | 3,60 | |
Outdoor air flow (Cool) | m³/min | 32,6 | |
Outdoor air flow (Heat) | m³/min | 34,0 | |
Outdoor sound pressure (Cool - Hi) | dB(A) | 46 | |
Outdoor sound pressure (Heat - Hi) | dB(A) | 47 | |
Outdoor sound power (Cool -Hi) | dB(A) | 64 | |
Outdoor sound power (Heat -Hi) | dB(A) | 66 | |
Outdoor dimension (Height) | mm | 619 | |
Outdoor dimension (Width) | mm | 824 | |
Outdoor dimension (Depth) | mm | 299 | |
Outdoor net weight | kg | 32 | |
Piping diameter (Liquid) | Inch (mm) | 1/4 (6,35) | |
Piping diameter (Gas) | Inch (mm) | 1/2 (12,70) | |
Pipe length range | m | 3 ~ 15 | |
Elevation difference (in/out) (5) | m | 15 / 15 | |
Pre-charged pipe length | m | 7,5 | |
Additional gas amount | g/m | 10 | |
Refrigerant (R32) / CO2 Eq. | kg / T | 0,87 / 0,59 | |
Operating range (Cool - Min) | °C | -10 | |
Operating range (Cool - Max) | °C | +43 | |
Operating range (Heat - Min) | °C | -15 | |
Operating range (Heat - Max) | °C | +24 |
1) Výpočet EER a COP vychádza z normy EN14511.
2) Pri modeloch s výkonom nižším ako 12 kW sa SEER a SCOP vypočítavajú na základe hodnôt EÚ/626/2011. Pre modely nad 12 kW sa hodnoty ηsc / ηsh vypočítavajú na základe normy EN 14825.
3) Nastavenie z výroby.
4) Akustický tlak jednotiek zobrazuje hodnotu nameranú z polohy 1,5 m pod jednotkou. Akustický tlak sa meria v súlade so špecifikáciou Eurovent 6/C/006-97.
5) Pripojte rúrku kvapalinovej zásuvky (Ø6,35-Ø9,52) k vnútornej jednotke na strane kvapalinovej hadice.
6) Pripojte rúrku plynovej zásuvky (Ø12,70-Ø15,88) k vnútornej jednotke na strane plynovej hadice.
7) Pri inštalácii vonkajšej jednotky vo vyššej polohe ako vnútorná jednotka.
8) Vonkajšia jednotka umiestnená nižšie / vonkajšia jednotka umiestnená vyššie.
* Odporúčaná poistka pre vnútornú jednotku 3A.
** Uvedené hodnoty sú v prípade nanoe™ X OFF.
*** K dispozícii na jeseň 2021.
**** Predbežné údaje.