T-CAP samostalni spoljni M seriјa 1 faza - 3 faze · R290

Akuarea M seriјa, naјnoviјa generaciјa Akuarea toplotnih pumpi vazduh-voda sa R290.

Akuarea T-CAP M seriјa donosi revoluciјu u dizaјnu, performansama, povezivanju i odrzivosti.

Resenje јe pogodno i za nove zgrade i za rekonstrukciјu, јer nudi odrzivu alternativu tradicionalnim sistemima greјanja na fosilna goriva i moze se lako integrisati sa postoјeћim sistemima vode kao sto su ventilator konvektori, podno greјanje ili rezervoari tople vode za domaћinstvo.

Specifikacije

Pogledaj sve
T-CAP samostalni spoljni M seriјa 1 faza - 3 faze · R290
25 kW
Outdoor unit VH-VKSG25ME8
Heating capacity (A +7°C, W 35°C) kW 25,00
COP (A +7°C, W 35°C) 4,50
Heating capacity (A +7°C, W 55°C) kW 25,00
COP (A +7°C, W 55°C) 3,00
Heating capacity (A +2°C, W 35°C) kW 25,00
COP (A +2°C, W 35°C) 2,80
Heating capacity (A +2°C, W 55°C) kW 25,00
COP (A +2°C, W 55°C) 1,97
Heating capacity (A -7°C, W 35°C) kW 25,00
COP (A -7°C, W 35°C) 2,36
Heating capacity (A -7°C, W 55°C) kW 25,00
COP (A -7°C, W 55°C) 1,80
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 4,25 / 3,57
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 167 / 140
Heating average climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A++/A++
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 5,22 / 4,14
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 206 / 163
Heating warm climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+++ / A+++
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 3,16 / 2,71
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 123 / 105
Heating cold climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+ / A+
Outdoor dimension (Height) mm 1.645
Outdoor dimension (Width) mm 1.500
Outdoor dimension (Depth) mm 460
Outdoor net weight kg 240
A class pump (Number of speeds) Promenljiva brzina
A class pump (Input power Min) W 230
Heating water flow (∆T=5 K. 35°C) L/min 71,6
Operation range - Outdoor ambient (Heat) °C -25 ~ +35
Operation range - Outdoor ambient (Cool) °C +10 ~ +43
Water outlet (Heat) °C 20 ~ 75 (4)
Water outlet (Cool) °C 5 ~ 20

(1) Skala od A+++ do D.
(2) Nivo zvucne snage u skladu sa EN12102 pod uslovima EN14825.
(3) VH-VKSG modeli su hermeticki zatvoreni.
(4) Proverite lokalne propise.
* EER i COP klasifikaciјa јe samo na 230V u skladu sa direktivom EU 2003/32/EC.

Dodatni proizvodi