PACi Elite Ceiling • R32

Capacitate anterioară Capacitate ulterioară

Ceiling mounted units provides large and wide air distribution which is good for big rooms. The height and depth of all capacities are the same for unified appearance in mixed installations.

Specificații

Vizualizare toate
PACi Elite Ceiling • R32
5.0 kW
Kit KIT-50PT2ZH5
Remote controller CZ-RTC5B
Cooling capacity (Nominal) kW 5,0
Cooling capacity (Min) kW 1,5
Cooling capacity (Max) kW 5,6
EER (Nominal) (1) W/W 4,17
SEER (2) 7,0 A++
Pdesign (cooling) kW 5,0
Input power cooling (Nominal) kW 1,20
Annual energy consumption cooling (3) kWh/a 250
Annual energy consumption cooling (3) kWh/a 250
Heating capacity (Nominal) kW 5,6
Heating capacity (Min) kW 1,5
Heating capacity (Max) kW 6,5
COP (Nominal) (1) W/W 4,34
SCOP (2) 4,6 A++
Pdesign at -10°C kW 4,5
Input power heating (Nominal) kW 1,29
Annual energy consumption heating (3) kWh/a 1370
Indoor unit S-50PT2E5B
Indoor air flow (Hi) m³/min 15,0
Indoor air flow (Med) m³/min 12,5
Indoor air flow (Lo) m³/min 10,5
Indoor sound pressure (Med) (4) dB(A) 33
Indoor sound pressure (Lo) (4) dB(A) 29
Indoor dimension (Height) mm 235
Indoor dimension (Width) mm 960
Indoor dimension (Depth) mm 690
Indoor net weight kg 27
Outdoor unit U-50PZH2E5
Outdoor power source V 220 - 230 - 240
Current in cooling (1p 220V / 3p 380) A 5,60
Current in cooling (1p 230V / 3p 400) A 5,35
Current in cooling (1p 240V / 3p 415) A 5,10
Current in heating (1p 220V / 3p 380) A 6,10
Current in heating (1p 230V / 3p 400) A 5,85
Current in heating (1p 240V / 3p 415) A 5,60
Outdoor air flow (Cool) m³/min 40
Outdoor air flow (Heat) m³/min 45
Outdoor sound pressure (Cool -Hi) dB(A) 45
Outdoor sound pressure (Heat -Hi) dB(A) 48
Outdoor sound power (Cool -Hi) dB(A) 64
Outdoor sound power (Heat -Hi) dB(A) 68
Outdoor dimension (Height) mm 695
Outdoor dimension (Width) mm 875
Outdoor dimension (Depth) mm 320
Outdoor net weight kg 43
Pipe diameter (Liquid) Inch (mm) 1/4 (6,35)
Pipe diameter (Gas) Inch (mm) 1/2 (12,70)
Pipe length range m 3 ~ 40
Elevation difference (in/out) (5) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 20
Refrigerant (R32) / CO2 Eq. kg / T 1,15 / 0,776
Operating range (Cool - Min) °C -15
Operating range (Cool - Max) °C 46
Operating range (Heat - Min) °C -20
Operating range (Heat - Max) °C 24

(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the SEER and SCOP is calculated based on values of EU/2281/2016.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) The sound pressure of the units shows the value measured of the position 1 m in front of the main body and 1 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(5) When installing the outdoor unit at a higher position than the indoor unit.
(6) For models 100 ~ 140PZH2E5(8), it is possible to operate the lowest -20 °C in the computer rooms with the piping length of 30 m or less.
* Recommended fuse for the indoor 3 A.

Produse complementare