Série PACi NX Elite Split Inverter+ · R32

Função anterior Função seguinte

As unidades mural com um elegante branco mate é ideal para diversos tipos de aplicações, tais como estúdios, ginásios, áreas com tetos elevados e até salas de servidores.

O design compacto e a superfície plana da unidade garantem uma instalação discreta, mesmo num espaço pequeno.

A próxima geração de ar condicionado comercial

Especificações

Ver tudo
Série PACi NX Elite Split Inverter+ · R32
3.6 kW
Kit KIT-36PK3ZH5
Remote controller CZ-RTC5B
Cooling capacity (Nominal) kW 3,6
Cooling capacity (Min) kW 1,2
Cooling capacity (Max) kW 4,0
EER (Nominal) (1) W/W 4,93
EER (Min) (1) W/W 5,45
EER (Max) (1) W/W 4,49
SEER (2) 8,4 A++
Pdesign (cooling) kW 3,6
Input power cooling (Nominal) kW 0,73
Input power cooling (Min) kW 0,22
Input power cooling (Max) kW 8,90
Annual energy consumption cooling (3) kWh/a 150
Heating capacity (Nominal) kW 4,0
Heating capacity (Min) kW 1,2
Heating capacity (Max) kW 5,0
COP (Nominal) (1) W/W 4,82
COP (Min) (1) W/W 5,45
COP (Max) (1) W/W 4,17
SCOP (2) 4,9 A++
Pdesign at -10°C kW 3,6
Input power heating (Nominal) kW 0,83
Input power heating (Min) kW 0,22
Input power heating (Max) kW 1,20
Annual energy consumption heating (3) kWh/a 1.029
Indoor unit S-3650PK3E
Indoor air flow (Hi) m³/min 13,0
Indoor air flow (Med) m³/min 11,0
Indoor air flow (Lo) m³/min 9,0
Moisture removal volume L/h 0,9
Indoor sound pressure (Med) (4) dB(A) 31
Indoor sound pressure (Lo) (4) dB(A) 27
Indoor sound power (Hi) dB(A) 51
Indoor sound power (Med) dB(A) 47
Indoor sound power (Lo) dB(A) 43
Indoor dimension (Height) mm 302
Indoor dimension (Width) mm 1.120
Indoor dimension (Depth) mm 236
Indoor net weight kg 13
nanoe X Generator Mark 2
Outdoor unit U-36PZH3E5
Outdoor power source V 220 - 230 - 240
Current in cooling (1p 220V / 3p 380) A 3,60
Current in cooling (1p 230V / 3p 400) A 3,45
Current in cooling (1p 240V / 3p 415) A 3,30
Current in heating (1p 220V / 3p 380) A 4,05
Current in heating (1p 230V / 3p 400) A 3,90
Current in heating (1p 240V / 3p 415) A ,3,70
Outdoor air flow (Cool) m³/min 34,1
Outdoor air flow (Heat) m³/min 36,4
Outdoor sound pressure (Cool -Hi) dB(A) 43
Outdoor sound pressure (Heat -Hi) dB(A) 44
Outdoor sound power (Cool -Hi) dB(A) 62
Outdoor sound power (Heat -Hi) dB(A) 64
Outdoor dimension (Height) mm 695
Outdoor dimension (Width) mm 875
Outdoor dimension (Depth) mm 320
Outdoor net weight kg 42
Pipe diameter (Liquid) Inch (mm) 1/4 (6,35)
Pipe diameter (Gas) Inch (mm) 1/2 (12,70)
Pipe length range m 3 ~ 40
Elevation difference (in/out) (7) m 15 / 30 (8)
Pipe length for additional gas m 30
Additional gas amount g/m 15
Refrigerant (R32) / CO2 Eq. kg / T 1,13 / 0,76
Operating range (Cool - Min) °C -15
Operating range (Cool - Max) °C +46
Operating range (Heat - Min) °C -20
Operating range (Heat - Max) °C +24
1) O EER e o COP são calculados com base na norma EN14511.
2) Para modelos abaixo dos 12 kW, o SEER e SCOP são calculados com base nos valores da diretiva UE/626/2011. Para modelos acima dos 12 kW, os valores do ηsc / ηsh são calculados com base na norma EN14825.
3) Configurações de fábrica.
4) O nível de pressão acústica das unidades mostra o valor medido num ponto situado a 1 metro à frente do corpo principal e 1 metro abaixo da unidade. A pressão acústica é medida de acordo com a especificação Eurovent 6/C/006-97.
5) Ligue o tubo do bocal do líquido (Ø6,35-Ø9,52) à lateral da tubagem de líquido na unidade interior.
6) Ligue o tubo do bocal do gás (Ø12,70-Ø15,88) à lateral da tubagem de gás na unidade interior.
7) Unidade exterior localizada mais abaixo / unidade exterior localizada mais acima.
8) Comprimento da tubagem até 30 m.
* Recomenda-se um fusível de 3 A para o interior.
** Os valores acima aplicam-se ao nanoe™ X OFF.

Produtos complementares