4-veis PACi Elite 90x90 kassett – PU3 – R32

Ny 4-veis 90x90 kassett – PU3 for R32 PACi

Kraftig turbovifte og intelligent Econavi-sensor sikrer høy energieffektivitet, og nanoe™ X, som er installert som standard, bidrar til markant bedre inneluftkvalitet.

Naturens balanse innendørs

Spesifikasjoner

Se alle
4-veis PACi Elite 90x90 kassett – PU3 – R32 1-FASE 3-FASE
3.6 kW 5.0 kW 6.0 kW 7.1 kW 10.0 kW 12.5 kW 14.0 kW 7.1 kW 10.0 kW 12.5 kW 14.0 kW
Kit KIT-36PU3ZH25 KIT-50PU3ZH25 KIT-60PU3ZH25 KIT-71PU3ZH25 KIT-100PU3ZH25 KIT-125PU3ZH25 KIT-140PU3ZH25 KIT-71PU3ZH28 KIT-100PU3ZH28 KIT-125PU3ZH28 KIT-140PU3ZH28
Remote controller CZ-RTC6 CZ-RTC6 CZ-RTC6 CZ-RTC6 CZ-RTC6 CZ-RTC6 CZ-RTC6 CZ-RTC6 CZ-RTC6 CZ-RTC6 CZ-RTC6
EER (Min) (1) W/W 6,25 6,25 8,00 5,79 5,34 5,33 5,32 5,79 5,34 5,33 5,32
EER (Max) (1) W/W 4,60 3,61 3,36 2,69 3,42 3,08 2,74 2,69 3,42 3,08 2,74
SEER/ηsc (2) % 8,5 A+++ 8,2 A++ 8,0 A++ 7,7 A++ 7,8 A++ 304,3 286,6 7,6 A++ 7,7 A++ 303,0 285,6
Annual energy consumption cooling (3) kWh/a 148 213 262 323 449 327 455
COP (Min) (1) W/W 7,89 7,89 9,47 5,56 5,54 5,52 5,50 5,56 5,54 5,52 5,50
COP (Max) (1) W/W 4,90 4,19 4,10 3,16 3,64 3,37 3,27 3,16 3,64 3,37 3,27
SCOP/ηsc (2) % 5,1 A+++ 4,9 A++ 4,8 A++ 4,8 A++ 4,9 A++ 186,0 181,2 4,8 A++ 4,9 A++ 186,0 181,1
Annual energy consumption heating (3) kWh/a 988 1286 1750 1517 2286 1517 2286
Indoor air flow (Hi) m³/min 14,5 16,5 21,0 22,0 36,0 37,0 38,0 22,0 36,0 37,0 38,0
Indoor air flow (Med) m³/min 13,0 13,5 16,0 16,0 26,0 27,0 29,0 16,0 26,0 27,0 29,0
Indoor air flow (Lo) m³/min 11,5 11,5 13,0 13,0 18,0 19,0 20,0 13,0 18,0 19,0 20,0
Moisture removal volume L/h 0,7 1,6 1,7 2,5 2,7 4,8 6 2,5 2,7 4,8 6
Indoor sound pressure (Med) (4) dB(A) 28 29 31 31 38 39 40 31 38 39 40
Indoor sound pressure (Lo) (4) dB(A) 27 27 28 28 32 33 34 28 32 33 34
Indoor sound power (Hi) dB(A) 45 47 51 52 60 61 62 52 60 61 62
Indoor sound power (Med) dB(A) 43 44 46 46 53 54 55 46 53 54 55
Indoor sound power (Lo) dB(A) 42 42 43 43 47 48 49 43 47 48 49
nanoe X Generator Mark 1 Mark 1 Mark 1 Mark 1 Mark 1 Mark 1 Mark 1 Mark 1 Mark 1 Mark 1 Mark 1
Outdoor unit U-36PZH2E5 U-50PZH2E5 U-60PZH2E5 U-71PZH2E5 U-100PZH2E5 U-125PZH2E5 U-140PZH2E5 U-71PZH2E8 U-100PZH2E8 U-125PZH2E8 U-140PZH2E8
Outdoor power source V 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415
Current in cooling (1p 220V / 3p 380) A 3,35 5,45 7,30 8,25 10,40 15,20 19,10 2,75 3,50 5,15 6,45
Current in cooling (1p 230V / 3p 400) A 3,20 5,25 6,95 7,90 9,95 14,50 18,20 2,65 3,35 4,90 6,15
Current in cooling (1p 240V / 3p 415) A 3,05 5,00 6,70 7,55 9,50 13,90 17,50 2,55 3,20 4,70 5,90
Current in heating (1p 220V / 3p 380) A 3,55 5,70 8,05 8,60 10,20 14,00 17,20 2,90 3,45 4,75 5,85
Current in heating (1p 230V / 3p 400) A 3,40 5,45 7,70 8,25 9,80 13,40 16,50 2,80 3,30 4,50 5,55
Current in heating (1p 240V / 3p 415) A 3,25 5,20 7,40 8,00 9,40 12,80 15,80 2,70 3,15 4,35 5,35
Outdoor air flow (Cool) m³/min 40 40 40 61 118 125 129 61 118 125 129
Outdoor air flow (Heat) m³/min 40 45 45 60 108 112 116 60 108 112 116
Outdoor sound pressure (Cool -Hi) dB(A) 43 45 46 48 52 53 54 48 52 53 54
Outdoor sound pressure (Heat -Hi) dB(A) 44 48 49 50 52 53 54 50 52 53 54
Outdoor sound power (Cool -Hi) dB(A) 62 64 65 65 69 70 71 65 69 70 71
Outdoor sound power (Heat -Hi) dB(A) 64 68 69 67 69 70 71 67 69 70 71
Outdoor dimension (Height) mm 695 695 695 996 1416 1416 1416 996 1416 1416 1416
Outdoor dimension (Width) mm 875 875 875 940 940 940 940 940 940 940 940
Outdoor dimension (Depth) mm 320 320 320 340 340 340 340 340 340 340 340
Pipe length range m 3 ~ 40 3 ~ 40 3 ~ 40 5 ~ 50 5 ~ 85 5 ~ 85 5 ~ 85 5 ~ 50 5 ~ 85 5 ~ 85 5 ~ 85
Elevation difference (in/out) (5) m 30 30 30 30 30 30 30 30 30 30 30
(1) EER- og COP-beregning er basert på EN 14511.
(2) Energimerking fra A+++ til D. For modeller under 12 kW er SEER og SCOP beregnet ut fra verdiene i EU/626/2011. For modeller over 12 kW er beregningene av ηsc-/ηsh-verdiene basert på EN 14825.
(3) Det årlige energiforbruket beregnes i henhold til EU/626/2011.
(4) Lydtrykket til enhetene viser verdien målt 1,5 m under enheten. Lydtrykket er målt i samsvar med Eurovent 6/C/006-97-spesifikasjonene.
(5) Når utedelen installeres i en høyere posisjon enn innedelen.
(6) For modellene 100 ~ 140PZH2E5(8) er drift i datarom mulig ned til -20 °C med en rørlengde på 30 m eller mindre.
* Anbefalt sikring for innedel 3 A.
** Verdiene ovenfor gjelder når nanoe™ X er AV.

Kompletterende produkter