Veggmontert PACi Elite • R32
9.5 kW
Kit KIT-100PK2ZH8
Remote controller CZ-RTC5B
Cooling capacity (Nominal) kW 9,5
Cooling capacity (Min) kW 3,1
Cooling capacity (Max) kW 10,5
EER (Nominal) (1) W/W 3,26
SEER (2) 6,3 A++
Pdesign (cooling) kW 9,5
Input power cooling (Nominal) kW 2,91
Annual energy consumption cooling (3) kWh/a 526
Annual energy consumption cooling (3) kWh/a 526
Heating capacity (Nominal) kW 9,5
Heating capacity (Min) kW 3,1
Heating capacity (Max) kW 11,5
COP (Nominal) (1) W/W 3,97
SCOP (2) 4,1 A+
Pdesign at -10°C kW 8,0
Input power heating (Nominal) kW 2,39
Annual energy consumption heating (3) kWh/a 2732
Indoor unit S-100PK2E5B
Indoor air flow (Hi) m³/min 22,0
Indoor air flow (Med) m³/min 18,5
Indoor air flow (Lo) m³/min 15,0
Indoor sound pressure (Med) (4) dB(A) 45
Indoor sound pressure (Lo) (4) dB(A) 41
Indoor dimension (Height) mm 302
Indoor dimension (Width) mm 1120
Indoor dimension (Depth) mm 236
Indoor net weight kg 14
Outdoor unit U-100PZH2E8
Outdoor power source V 380 - 400 - 415
Current in cooling (1p 220V / 3p 380) A 4,60
Current in cooling (1p 230V / 3p 400) A 4,35
Current in cooling (1p 240V / 3p 415) A 4,20
Current in heating (1p 220V / 3p 380) A 3,75
Current in heating (1p 230V / 3p 400) A 3,55
Current in heating (1p 240V / 3p 415) A 3,45
Outdoor air flow (Cool) m³/min 118
Outdoor air flow (Heat) m³/min 108
Outdoor sound pressure (Cool -Hi) dB(A) 52
Outdoor sound pressure (Heat -Hi) dB(A) 52
Outdoor sound power (Cool -Hi) dB(A) 69
Outdoor sound power (Heat -Hi) dB(A) 69
Outdoor dimension (Height) mm 1416
Outdoor dimension (Width) mm 940
Outdoor dimension (Depth) mm 340
Outdoor net weight kg 99
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88)
Pipe length range m 5 ~ 85
Elevation difference (in/out) (5) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 45
Refrigerant (R32) / CO2 Eq. kg / T 3,05 / 2,059
Operating range (Cool - Min) °C -20 (6)
Operating range (Cool - Max) °C 46
Operating range (Heat - Min) °C -20
Operating range (Heat - Max) °C 24

(1) EER- og COP-beregning er basert på EN 14511.
(2) Energimerking fra A+++ til D. For modeller under 12 kW er SEER og SCOP beregnet ut fra verdiene i EU/626/2011. For modeller over 12 kW er SEER og SCOP beregnet ut fra verdiene i EU/2281/2016.
(3) Det årlige energiforbruket beregnes i henhold til EU/626/2011.
(4) Lydtrykket til enhetene viser verdien målt 1 m foran hoveddelen og 1 m under enheten. Lydtrykket er målt i samsvar med Eurovent 6/C/006-97-spesifikasjonene.
(5) Når utedelen installeres i en høyere posisjon enn innedelen.
(6) For modellene 100 ~ 140PZH2E5(8) er drift i datarom mulig ned til -20 °C med en rørlengde på 30 m eller mindre.
* Anbefalt sikring for innedel 3 A.

Kompletterende produkter