Aquarea T-CAP Bi-bloc H Generation 1 Phase / 3 Phase • R410A

Aquarea, an innovative new low-energy system based on Air to Water heat pump technology


Aquarea warms your home effectively and efficiently, even with extreme outdoor temperatures. Aquarea can also cool space in summer and bring hot water all year round.
Aquarea T-CAP is the range for retrofit and new builds, keeping Total Capacity even at extremely cold ambient.
The Bi‑Bloc system: The system, separate indoor and outdoor units, connects to the heating and/or hot water system.

A heat pump turns heat energy outside into warmth inside

Specifications

See all
Aquarea T-CAP Bi-bloc H Generation 1 Phase / 3 Phase • R410A SINGLE PHASE (Power to indoor) THREE PHASE (Power to indoor)
9 kW 12 kW 9 kW 12 kW 16 kW
Kit KIT-WXC09H3E5 KIT-WXC12H6E5 KIT-WXC09H3E8 KIT-WXC12H9E8 KIT-WXC16H9E8
Heating capacity (A +7°C, W 35°C) kW 9,00 12,00 9,00 12,00 16,00
COP (A +7°C, W 35°C) 4,84 4,74 4,84 4,74 4,28
Heating capacity (A +7°C, W 55°C) kW 9,00 12,00 9,00 12,00 16,00
COP (A +7°C, W 55°C) 2,94 2,88 2,94 2,88 2,71
Heating capacity (A +2°C, W 35°C) kW 9,00 12,00 9,00 12,00 16,00
COP (A +2°C, W 35°C) 3,59 3,44 3,59 3,44 3,10
Heating capacity (A +2°C, W 55°C) kW 9,00 12,00 9,00 12,00 16,00
COP (A +2°C, W 55°C) 2,21 2,19 2,21 2,19 2,13
Heating capacity (A -7°C, W 35°C) kW 9,00 12,00 9,00 12,00 16,00
COP (A -7°C, W 35°C) 2,85 2,72 2,85 2,72 2,49
Heating capacity (A -7°C, W 55°C) kW 9,00 12,00 9,00 12,00 16,00
COP (A -7°C, W 55°C) 2,02 1,92 2,02 1,92 1,86
Cooling capacity (A 35°C, W 7°C) kW 7,00 10,00 7,00 10,00 12,20
EER (A 35°C, W 7°C) 3,17 2,81 3,17 2,81 2,57
Cooling capacity (A 35°C, W 18°C) kW 7,00 10,00 7,00 10,00 12,20
EER (A 35°C, W 18°C) 5,19 5,13 5,19 5,13 3,49
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 181 / 130 170 / 130 181 / 130 170 / 130 160 / 125
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 4,60 / 3,33 4,33 / 3,33 4,60 / 3,33 4,33 / 3,33 4,08 / 3,20
Heating average climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+++ / A++ A++ / A++ A+++ / A++ A++ / A++ A++ / A++
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 235 / 158 231 / 158 235 / 158 231 / 158 231 / 159
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 5,95 / 4,03 5,85 / 4,03 5,95 / 4,03 5,85 / 4,03 5,85 / 4,05
Heating warm climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 160 / 125 160 / 125 160 / 125 160 / 125 150 / 125
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 4,08 / 3,20 4,08 / 3,20 4,08 / 3,20 4,08 / 3,20 3,83 / 3,20
Heating cold climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++
Indoor unit WH-SXC09H3E5 WH-SXC12H6E5 WH-SXC09H3E8 WH-SXC12H9E8 WH-SXC16H9E8
Indoor sound pressure (Heat) dB(A) 33 33 33 33 33
Indoor sound pressure (Cool) dB(A) 33 33 33 33 33
Indoor dimension (Height) mm 892 892 892 892 892
Indoor dimension (Width) mm 500 500 500 500 500
Indoor dimension (Depth) mm 340 340 340 340 340
Indoor net weight kg 43 43 43 44 45
Water pipe connector Inch R 1¼ R 1¼ R 1¼ R 1¼ R 1¼
A class pump (Number of speeds) Variable Speed Variable Speed Variable Speed Variable Speed Variable Speed
A class pump (Input power Min) W 32 34 32 34 30
A class pump (Input power Max) W 102 110 102 110 105
Heating water flow (∆T=5 K. 35°C) L/min 25,80 34,40 25,80 34,40 45,90
Capacity of integrated electric heater kW 3,00 6,00 3,00 9,00 9,00
Indoor recommended fuse A 30 / 30 30 / 30  16 / 16 16 / 16 16 / 16
Recommended cable size, supply 1 mm² 3 x 4,0 or 6,0 3 x 4,0 or 6,0 5 x 1,5 5 x 1,5 5 x 1,5
Recommended cable size, supply 2 mm² 3 x 4,0 3 x 4,0 3 x 1,5 5 x 1,5 5 x 1,5
Outdoor unit WH-UX09HE5 WH-UX12HE5 WH-UX09HE8 WH-UX12HE8 WH-UX16HE8
Outdoor sound power part load (Heat) (3) dB(A) 66 66 65 65 67
Outdoor sound power full load (Heat) dB(A) 68 69 68 69 72
Outdoor sound power full load (Cool) dB(A) 67 68 67 68 71
Outdoor dimension (Height) mm 1340 1340 1340 1340 1340
Outdoor dimension (Width) mm 900 900 900 900 900
Outdoor dimension (Depth) mm 320 320 320 320 320
Outdoor net weight kg 101 101 108 108 118
Refrigerant (R410A) / CO2 Eq. kg / T 2,85 / 5,951 2,85 / 5,951 2,85 / 5,951 2,85 / 5,951 2,90 / 6,055
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88)
Pipe length range m 3 ~ 30 3 ~ 30 3 ~ 30 3 ~ 30 3 ~ 30
Elevation difference (in/out) m 30 30 30 30 30
Pipe length for additional gas m 10 10 10 10 10
Additional gas amount g/m 50 50 50 50 50
Operation range (Outdoor ambient) °C -28 ~ +35 -28 ~ +35 -28 ~ +35 -28 ~ +35 -28 ~ +35
Water outlet (Heat) °C 20 ~ 60 20 ~ 60 20 ~ 60 20 ~ 60 20 ~ 60
Water outlet (Cool) °C 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20

(1) Sound power in accordance to 8112013,81312013 and EN12102-1:2017 at +7°C.
EER and COP calculation is based in accordance to EN14511.

Complementary products