U - 140/150/170/190/210 CW

ECOi-W Heat Pump Chiller

Cooling capacity: 125,4 to 195,4kW.

Heating capacity: 143,7 to 217,6kW.

Heat pump chiller series with powerful operation by 4 scroll compressors. Maximum water outlet temperature in heating is up to 55°C 1). Defrost limiting design ensures to provide stable hot water even at low ambient conditions.


1) Special condition apply. Please contact an authorized Panasonic dealer in the case of condition >50°C.
· Smart defrost: Defrost limiting design to ensure a constant water outlet temperature even at very low temperatures
· High seasonal efficiency in cooling and heating
· Eurovent certified
· Ambient temperature operating range: -10 to +50°C in cooling, -17 to +20°C in heating
· Water outlet temperature range: -10 to +18°C in cooling, +20 to +50°C in heating
· Super quiet operation
· Victaulic water connections
· Optimized design for service and maintenance
· Simple user friendly control as standard
· Modbus RTU as standard
· Modbus TCP/IP as standard

Technical focus.
· Chiller type: heat pump
· Compressor type (number of compressors): Scroll compressors (4)
· Refrigerant type: R410A
· Refrigerant circuit: 2
· Fan type (number of fans): axial fan (4)
· Heat exchanger: stainless steel plate heat exchanger
· Flow switch, water safety & air purge valves included
· Water filter included (mandatory to be installed on site)
· Night mode setting to save energy and reduce noise level
· Water compensation curve control
· Bluefin anti-corrosion coating
· Optional hydraulic kit
· Optional finned coil treatment
· Optional gauges hydraulic and refrigerant
· Optional BACnet
· Remote LAN connection as standard

The reasons to choose Panasonic as your partner

Explore the new range of fan coils

Specifications

See all
U - 140/150/170/190/210 CW
163.9 kW

1) Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.
2) Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers.
3) Those are the data with variable flow. For the data with fixed flow, please contact an authorised Panasonic dealer.
4) Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87 % R.H., according EN14511 standard.
5) Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps.
6) Sound pressure levels calculated at 10 meters. Sound pressure levels refer to ISO standard 3744 with parallel piped shape.