Aquarea High Performance Bi-bloc H Generation 1 Phase • R410A

Aquarea, an innovative new low-energy system based on Air to Water heat pump technology


Aquarea warms your home effectively and efficiently, even with extreme outdoor temperatures. Aquarea can also cool space in summer and bring hot water all year round.
Aquarea High Performance is the range for new installations and low consumption homes. Outstanding efficiency and energy savings with minimised CO2 emissions and minimum space.
The Bi‑Bloc system: The system, separate indoor and outdoor units, connects to the heating and/or hot water system.

A heat pump turns heat energy outside into warmth inside

Specifikacije

See all
Aquarea High Performance Bi-bloc H Generation 1 Phase • R410A
16 kW
Kit KIT-WC16H6E5
Heating capacity (A +7°C, W 35°C) kW 16,00
COP (A +7°C, W 35°C) 4,28
Heating capacity (A +7°C, W 55°C) kW 14,50
COP (A +7°C, W 55°C) 2,68
Heating capacity (A +2°C, W 35°C) kW 13,00
COP (A +2°C, W 35°C) 3,28
Heating capacity (A +2°C, W 55°C) kW 9,80
COP (A +2°C, W 55°C) 2,17
Heating capacity (A -7°C, W 35°C) kW 11,40
COP (A -7°C, W 35°C) 2,57
Heating capacity (A -7°C, W 55°C) kW 9,00
COP (A -7°C, W 55°C) 1,82
Cooling capacity (A 35°C, W 7°C) kW 12,20
EER (A 35°C, W 7°C) 2,56
Cooling capacity (A 35°C, W 18°C) kW 12,20
EER (A 35°C, W 18°C) 4,12
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 190 / 130
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 4,83 / 3,33
Heating average climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+++ / A++
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 245 / 169
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 6,20 / 4,30
Heating warm climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+++ / A+++
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 168 / 121
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 4,28 / 3,10
Heating cold climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A++ / A+
Indoor unit WH-SDC16H6E5
Indoor sound pressure (Heat) dB(A) 33
Indoor sound pressure (Cool) dB(A) 33
Indoor dimension (Height) mm 892
Indoor dimension (Width) mm 500
Indoor dimension (Depth) mm 340
Indoor net weight kg 45
Water pipe connector Inch R 1¼
A class pump (Number of speeds) Variable Speed
A class pump (Input power Min) W 30
A class pump (Input power Max) W 105
Heating water flow (∆T=5 K. 35°C) L/min 45,90
Capacity of integrated electric heater kW 6,00
Indoor recommended fuse A 30 / 30 
Recommended cable size, supply 1 mm² 3 x 4,0 or 6,0
Recommended cable size, supply 2 mm² 3 x 4,0
Outdoor unit WH-UD16HE5
Outdoor sound power part load (Heat) (3) dB(A) 65
Outdoor sound power full load (Heat) dB(A) 72
Outdoor sound power full load (Cool) dB(A) 72
Outdoor dimension (Height) mm 1340
Outdoor dimension (Width) mm 900
Outdoor dimension (Depth) mm 320
Outdoor net weight kg 101
Refrigerant (R410A) / CO2 Eq. kg / T 2,55 / 5,324
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88)
Pipe length range m 3 ~ 50
Elevation difference (in/out) m 30
Pipe length for additional gas m 10
Additional gas amount g/m 50
Operation range (Outdoor ambient) °C -20 ~ +35
Water outlet (Heat) °C 20 ~ 55
Water outlet (Cool) °C 5 ~ 20

(1) Sound power in accordance to 8112013,81312013 and EN12102-1:2017 at +7°C.
EER and COP calculation is based in accordance to EN14511.