PCB’s and cables for PACi, ECOi and ECO G indoor units

Cables
CZ-T10: All T10 functions. Requires field supplied accessory
PAW-FDC: Operate external fan. Requires field supplied accessory
PAW-OCT: All option monitoring signals. Requires field supplied accessory
CZ-CAPE2: 3-Pipe control PCB. Requires aditional wires from spare part supply
PAW-EXCT: Forced Thermo OFF/Leakage D. Requires field supplied accessory

PBC’s
PAW-T10: All T10 functions. Allows easy connection “Plug & Play”
PAW-T10V: All T10 functions powermonitoring. Same like PAW-T10 monitoring the power supply of indoor unit
PAW-T10H: ON/OFF; Prohibit 5VDC & 230VAC. Specials for single hotel card or window contact
PAW-T10HW: ON/OFF; Prohibit 5VDC. For hotel card window contact at same time
PAW-PACR2: Redundancy of 2 systems; T monitor. Redundancy of 2 PACi systems including temperature monitoring an equal operating time
PAW-PACR3: Redundancy of 3 systems; T monitor. Redundancy of 3 PACi systems including temperature monitoring an equal operating time
PAW-ECF: Fan speed control external EC fan. For external production Air Curtain units allow the EC fan control by standard VRF IU PCB
T10 connector (CN015)
CZ-T10: Panasonic has developed an optional accessory (consisting of plug + wires) called CZ-T10 to enable an easy connection to this T10 connector.
Connecting an ECOi indoor unit to an external device is easy. The T10 terminal featured in the electronic circuit board of all indoor units enables digital connection to external devices.
T10 terminal Specification (T10: CN015 at indoor unit PCB)
  • Control items:
  1. Start/stop input
  2. Remote controller prohibit input
  3. Start signal output
  4. Alarm signal output
  • Condition
  1. 1-2 (Pulse input): Unit ON/OFF condition switching with a pulse signal. (1 pulse signal: shortage status more than 300 msec. or more)
  2. 2-3 (Static input): Open / Operation with Remote is permitted.(Normal condition) Close / Remote controller is prohibited.
  3. 4-5 (Static output): 12 V output during the unit ON. / No output at OFF.
  4. 5-6 (Static output): 12 V output when some errors occur / No output at normal.

Example of wiring
A. 300 ms or more
B. 1-2 (pulse input)
C. 4-5 (output)
D. Unit condition
NOTE: The wire length from indoor unit to the Relay must be within 2.0 m. Pulse signal changeable to static with JP cutting. (Refer to JP001)
E. T10 (yellow)
Usage Example
Forced OFF control

  • Term 1 & 2: Free contact for ON/OFF signal (cut *JP1* for static signal) when the hotel card is it connected the contact must be close (the unit can be used).
  • Term 2 & 3: Free contact to prohibit all function in the remote controller install in the room when the hotel card is it removed the contact must be closed (the unit can not work).

Operation ON/OFF signal output
  • Condition:
4-5 (Static output): 12 V output during the unit ON / No output at OFF

Example of wiring
A. Terminal = T10
1. On / Off
2. Common
3. Proibit
4. Operation output 12 V DC
5. Common
6. Output alarm 12 V DC
B. Relay 12 V DC
C. T10 (yellow)
D. Indoor unit control PCB
E. Relay (Field supply)
F. Central control
NOTE: The wire length from indoor unit to the Relay must be within 2.0 m. Pulse signal changeable to static with JP cutting. (Refer to JP001).

* PACi-NX series is not compatible.

Fan Drive Connector (CN017)
PAW-FDC: Panasonic has developed an optional accessory (consisting of plug + wires) called PAW-FDC to enable an easy connection to this Fan Drive Connector (CN017).
Operating the ventilation fan from the remote controller
  • Start / stop of external ventilation and total heat exchanger fans
  • Works even if indoor unit is stopped
  • In case of group control: all fans will operate; no individual control
External fan On / Off
A. Ventilation button
B. Fan Drive (2 plug (white))
C. Indoor unit control PCB
D. Relay (field supply)
E. To external-control input terminal on ventilation fan
Option Connector (CN060) Output external signals
PAW-OCT: Panasonic has developed an optional accessory (consisting of plug + wires) called PAW-OCT to enable an easy connection to this Option Connector (CN060).
With the combination of the T10 and the option CN060 an external control of the I_U is possible!

6P (white): Outputs external signals as shown in the figure below.
A. Option (white)
B. Indoor unit control PCB (CR1)
C. Relay (DC 12V, field supply) (Note)
D. Fan signal
E. Heat start signal
F. Cool start signal
G. Thermostat signal
H. Defrost signal
Note: The relay must be installed at a distance of 2 m or less from the PCB.
EXCT Connector (CN009)
PAW-EXCT: Panasonic has developed an optional accessory (consisting of plug + wires) called PAW-EXCT to enable an easy connection to this EXCT Connector (CN009).
With static input
➔ static input ➔ thermo off ➔ energy saving
2P plug (red): Can be used for demand control. When input is present, forces the unit to operate with the thermostat OFF.

Note: The length of the wiring from the indoor unit control PCB to the relay must be 2m or less.
* Lead wire with 2P plug (special—order part: WIRE K/854 05280 75300)

A. EXCT (2P plug (red))
B. Indoor unit control PCB
C. Relay (field supply)
D. Relay coil signal

Example: In connection with a refrigerant sensor
· Signal from leakage detector: non voltage, static.
· Indoor unit setting: Code 0b ➔ 1
· Connector for leak detector: EXCT
· Outdoor unit setting:
Code C1: 1 power output if alarm from O2 connector 230 V
Code C1: 2 power output if alarm from O2 connector 0 V
· Displayed alarm message P14

A. Valves close
B. Signal
C. Leakage
D. Room 1
E. Room 2
F. Ref. detector