14.0 kW
Kit KIT-140PU3ZH28
Remote controller CZ-RTC6
EER (Min) (1) W/W 5,32
EER (Max) (1) W/W 2,74
SEER/ηsc (2) % 285,6
Annual energy consumption cooling (3) kWh/a
COP (Min) (1) W/W 5,50
COP (Max) (1) W/W 3,27
SCOP/ηsc (2) % 181,1
Annual energy consumption heating (3) kWh/a
Indoor air flow (Hi) m³/min 38,0
Indoor air flow (Med) m³/min 29,0
Indoor air flow (Lo) m³/min 20,0
Moisture removal volume L/h 6
Indoor sound pressure (Med) (4) dB(A) 40
Indoor sound pressure (Lo) (4) dB(A) 34
Indoor sound power (Hi) dB(A) 62
Indoor sound power (Med) dB(A) 55
Indoor sound power (Lo) dB(A) 49
nanoe X Generator Mark 1
Outdoor power source V 380 - 400 - 415
Current in cooling (1p 220V / 3p 380) A 6,45
Current in cooling (1p 230V / 3p 400) A 6,15
Current in cooling (1p 240V / 3p 415) A 5,90
Current in heating (1p 220V / 3p 380) A 5,85
Current in heating (1p 230V / 3p 400) A 5,55
Current in heating (1p 240V / 3p 415) A 5,35
Outdoor air flow (Cool) m³/min 129
Outdoor air flow (Heat) m³/min 116
Outdoor sound pressure (Cool -Hi) dB(A) 54
Outdoor sound pressure (Heat -Hi) dB(A) 54
Outdoor sound power (Cool -Hi) dB(A) 71
Outdoor sound power (Heat -Hi) dB(A) 71
Outdoor dimension (Height) mm 1416
Outdoor dimension (Width) mm 940
Outdoor dimension (Depth) mm 340
Pipe length range m 5 ~ 85
Elevation difference (in/out) (5) m 30
(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12kW, the ηsc / ηsh values is calculated based on EN 14825.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) The sound pressure of the units shows the value measured of the position 1,5m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(5) When installing the outdoor unit at a higher position than the indoor unit.
(6) For models 100~140PZH2E5(8), it is possible to operate the lowest -20°C in the computer rooms with the piping length of 30m or less.
*Recommended fuse for the indoor 3A.
** Above values are in the case of nanoe™ X OFF.