PACi Elite 90x90 Cassette • R32

Large capacity PACi. Trusted comfort and high efficiency.

Thanks to advances in design and technology such as the high performance turbo fan, more efficient and silent, the nanoe™ X air cleaner, the U2 Panasonic 4 way 90x90 cassette offers high energy saving, fresh air and comfort.

Bringing nature’s balance indoors

Specifications

See all
PACi Elite 90x90 Cassette • R32
12.5 kW
Kit KIT-125PU2ZH8
Remote controller CZ-RTC5B
Cooling capacity (Nominal) kW 12,5
Cooling capacity (Min) kW 3,2
Cooling capacity (Max) kW 14,0
EER (Nominal) (1) W/W 3,80
SEER (2) 7,6
Pdesign (cooling) kW 12,5
Input power cooling (Nominal) kW 3,29
Annual energy consumption cooling (3) kWh/a
Annual energy consumption cooling (3) kWh/a
Heating capacity (Nominal) kW 14,0
Heating capacity (Min) kW 3,2
Heating capacity (Max) kW 16,0
COP (Nominal) (1) W/W 4,61
SCOP (2) 4,7
Pdesign at -10°C kW 9,5
Input power heating (Nominal) kW 3,04
Annual energy consumption heating (3) kWh/a
Indoor unit S-125PU2E5B
Indoor air flow (Hi) m³/min 37,0
Indoor air flow (Med) m³/min 27,0
Indoor air flow (Lo) m³/min 19,0
Indoor sound pressure (Med) (4) dB(A) 39
Indoor sound pressure (Lo) (4) dB(A) 33
Indoor dimension (Height) mm 319
Indoor dimension (Width) mm 840
Indoor dimension (Depth) mm 840
Panel dimension (Height) mm 33,5
Panel dimension (Depth) mm 950
Indoor net weight kg 25
Panel net weight kg 5
nanoe X Generator Mark 1
Outdoor unit U-125PZH2E8
Outdoor power source V 380 - 400 - 415
Current in cooling (1p 220V / 3p 380) A 5,15
Current in cooling (1p 230V / 3p 400) A 4,90
Current in cooling (1p 240V / 3p 415) A 4,70
Current in heating (1p 220V / 3p 380) A 4,75
Current in heating (1p 230V / 3p 400) A 4,50
Current in heating (1p 240V / 3p 415) A 4,35
Outdoor air flow (Cool) m³/min 125
Outdoor air flow (Heat) m³/min 112
Outdoor sound pressure (Cool -Hi) dB(A) 53
Outdoor sound pressure (Heat -Hi) dB(A) 53
Outdoor sound power (Cool -Hi) dB(A) 70
Outdoor sound power (Heat -Hi) dB(A) 70
Outdoor dimension (Height) mm 1416
Outdoor dimension (Width) mm 940
Outdoor dimension (Depth) mm 340
Outdoor net weight kg 99
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88)
Pipe length range m 5 ~ 85
Elevation difference (in/out) (5) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 45
Refrigerant (R32) / CO2 Eq. kg / T 3,05 / 2,059
Operating range (Cool - Min) °C -20 (6)
Operating range (Cool - Max) °C 46
Operating range (Heat - Min) °C -20
Operating range (Heat - Max) °C 24

(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the SEER and SCOP is calculated based on values of EU/2281/2016.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) The sound pressure of the units shows the value measured of the position 1,5 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(5) When installing the outdoor unit at a higher position than the indoor unit.
(6) For models 100 ~ 140PZH2E5(8), it is possible to operate the lowest -20 °C in the computer rooms with the piping length of 30 m or less.
* Recommended fuse for the indoor 3 A.