Etherea Inverter+ Silver • R32

Etherea stylish and outstanding features.

Etherea with nanoe™ X technology: outstanding efficiency A+++, comfort (Super Quiet technology only 19 dB(A)) and healthy air combined in a breakthrough design.


Bedarfsgerechte Modellauswahl

Entdecken Sie die neusten Technologien für Raumklimageräte

Natürliches Klima für Ihr Zuhause

Eine zukunftsweisende Regelung für Klimageräte

Technische Daten

Alles anzeigen
Etherea Inverter+ Silver • R32
2.5 kW
Kit KIT-XZ25-VKE
Cooling capacity (Nominal) kW 2,50
Cooling capacity (Min) kW 0,85
Cooling capacity (Max) kW 3,20
EER (Nominal) (1) W/W 4,81
EER (Min) (1) W/W 3,54
EER (Max) (1) W/W 4,05
SEER (2) 8,50 A+++
Pdesign (cooling) kW 2,50
Input power cooling (Nominal) kW 0,52
Input power cooling (Min) kW 0,24
Input power cooling (Max) kW 0,79
Annual energy consumption cooling (3) kWh/a 103,00
Heating capacity (Nominal) kW 3,40
Heating capacity (Min) kW 0,80
Heating capacity (Max) kW 5,00
Heating capacity at -7°C kW 2,95
COP (Nominal) (1) W/W 4,79
COP (Min) (1) W/W 4,44
COP (Max) (1) W/W 3,97
SCOP (2) 5,10 A+++
Pdesign at -10°C kW 2,70
Input power heating (Nominal) kW 0,71
Input power heating (Min) kW 0,18
Input power heating (Max) kW 1,26
Annual energy consumption heating (3) kWh/a 741
Indoor unit CS-XZ25VKEW
Indoor power source V 230
Indoor recommended fuse A 16
Indoor connection indoor / outdoor mm² 4 x 1,5
Indoor air flow (Cool) m³/min 10,2
Indoor air flow (Heat) m³/min 11,2
Moisture removal volume L/h 1,5
Indoor sound pressure (Cool -Hi) (4) dB(A) 39
Indoor sound pressure (Cool -Lo) (4) dB(A) 25
Indoor sound pressure (Cool -Q-Lo) (4) dB(A) 19
Indoor sound pressure (Heat -Hi) (4) dB(A) 41
Indoor sound pressure (Heat -Lo) (4) dB(A) 27
Indoor sound pressure (Heat -Q-Lo) (4) dB(A) 19
Indoor dimension (Height) mm 295
Indoor dimension (Width) mm 919
Indoor dimension (Depth) mm 194
Indoor net weight kg 10
nanoe X Generator Mark 1
Outdoor unit CU-Z25VKE
Outdoor air flow (Cool) m³/min 28,7
Outdoor air flow (Heat) m³/min 27,2
Outdoor sound pressure (Cool -Hi) (4) dB(A) 46
Outdoor sound pressure (Heat -Hi) (4) dB(A) 47
Outdoor dimension (Height) (5) mm 542
Outdoor dimension (Width) (5) mm 780
Outdoor dimension (Depth) (5) mm 289
Outdoor net weight kg 31
Pipe diameter (Liquid) Inch (mm) 1/4 (6,35)
Pipe diameter (Gas) Inch (mm) 3/8 (9,52)
Pipe length range m 3 ~ 15
Elevation difference (in/out) (6) m 15
Pipe length for additional gas m 7,5
Additional gas amount g/m 10
Refrigerant (R32) / CO2 Eq. kg / T 0,85 / 0,574
Operating range (Cool - Min) °C -10
Operating range (Cool - Max) °C +43
Operating range (Heat - Min) °C -15
Operating range (Heat - Max) °C +24

(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) The sound pressure of the indoor unit shows the value measured of a position 1 m in front of the main body and 0,8 m below the unit. For outdoor unit 1 m in front and 1 m in rear side of main body. The sound pressure is measured in accordance with JIS C 9612. Q-Lo: Quiet mode. Lo: The lowest set fan speed.
(5) Add 70 mm for piping port.
(6) When installing the outdoor unit at a higher position than the indoor unit.