„PACi Standard“ pritaikomas kanalinis blokas • PF3 - R32

Naujai suprojektuotas pritaikomas kanalinis blokas PF3, skirtas R32 „PACi“

2 galimi montavimo variantai (horizontaliai arba vertikaliai) esant aukštai išorinio statinio slėgio 150 Pa vertei suteikia galimybę lanksčiai įrengti.

Gamtos pusiausvyros užtikrinimas patalpose

Specifications

Rodyti viską
„PACi Standard“ pritaikomas kanalinis blokas • PF3 - R32 SINGLE PHASE THREE PHASE
6.0 kW 7.1 kW 10.0 kW 12.5 kW 14.0 kW 10.0 kW 12.5 kW 14.0 kW
Kit KIT-60PF3Z25 KIT-71PF3Z25 KIT-100PF3Z25 KIT-125PF3Z25 KIT-140PF3Z25 KIT-100PF3Z28 KIT-125PF3Z28 KIT-140PF3Z28
Remote controller CZ-RTC6 CZ-RTC6 CZ-RTC6 CZ-RTC6 CZ-RTC6 CZ-RTC6 CZ-RTC6 CZ-RTC6
Cooling capacity (Nominal) kW 5,7 6,8 9,5 12,1 13,4 9,5 9,5 13,4
Cooling capacity (Min) kW 2,0 2,2 3,1 3,2 3,3 3,0 3,0 3,3
Cooling capacity (Max) kW 6,3 7,8 11,4 13,5 15,0 11,4 11,4 15,0
EER (Nominal) (1) W/W 3,63 3,15 3,57 3,40 3,16 3,57 3,40 3,16
EER (Min) (1) W/W 4,76 4,76 6,00 5,93 5,08 6,00 5,93 5,08
EER (Max) (1) W/W 2,50 2,70 2,36 2,76 2,56 2,36 2,76 2,56
SEER/ηsc (2) % 7,1 A++ 6,7 A++ 6,6 A++ 257,5 252,6 6,5 A++ 256,5 251,7
Pdesign (cooling) kW 5,7 6,8 9,5 12,1 13,4 9,5 12,1 13,4
Input power cooling (Nominal) kW 1,57 2,16 2,66 3,56 4,24 2,66 3,56 4,24
Input power cooling (Min) kW 0,42 0,42 0,50 0,54 0,65 0,50 0,54 0,65
Input power cooling (Max) kW 2,52 2,85 4,84 4,90 5,86 4,84 4,90 5,86
Annual energy consumption cooling (3) kWh/a 281 354 502 508
Heating capacity (Nominal) kW 5,7 6,8 9,5 12,1 13,4 9,5 12,1 13,4
Heating capacity (Min) kW 1,8 1,8 3,0 3,3 3,4 3,0 3,3 3,4
Heating capacity (Max) kW 7,0 8,1 13,5 15,0 16,0 13,5 15,0 16,0
COP (Nominal) (1) W/W 4,22 3,93 4,09 3,56 3,76 4,09 3,56 3,76
COP (Min) (1) W/W 4,86 4,86 6,00 6,11 5,23 6,00 6,11 5,23
COP (Max) (1) W/W 2,83 3,82 3,00 3,16 3,03 3,00 3,16 3,03
SCOP/ηsc (2) % 4,7 A++ 4,2 A+ 3,9 A 144,2 140,8 3,9 A 144,1 140,8
Pdesign at -10°C kW 4,4 4,7 7,8 9,3 9,5 7,8 9,3 9,5
Input power heating (Nominal) kW 1,35 1,73 2,32 3,40 3,56 2,32 3,40 3,56
Input power heating (Min) kW 0,37 0,37 0,50 0,54 0,65 0,50 0,54 0,65
Input power heating (Max) kW 2,47 2,12 4,50 4,74 5,28 4,50 4,74 5,28
Annual energy consumption heating (3) kWh/a 1289 1565 2795 2795
Indoor unit S-6071PF3E S-6071PF3E S-1014PF3E S-1014PF3E S-1014PF3E S-1014PF3E S-1014PF3E S-1014PF3E
External static pressure (Nominal) (4) Pa 30 30 40 50 50 40 50 50
External static pressure (Min) (4) Pa 10 10 10 10 10 10 10 10
External static pressure (Max) (4) Pa 150 150 150 150 150 150 150 150
Moisture removal volume L/h 1,7 2,7 3,2 4,1 4,9 3,2 4,1 4,9
Indoor air flow (Hi) m³/min 21,0 21,0 32,0 34,0 36,0 32,0 34,0 36,0
Indoor air flow (Med) m³/min 19,0 19,0 26,0 29,0 32,0 26,0 29,0 32,0
Indoor air flow (Lo) m³/min 15,0 15,0 21,0 23,0 25,0 21,0 23,0 25,0
Indoor sound pressure (Hi) (5) dB(A) 30 30 33 35 39 33 35 39
Indoor sound pressure (Med) (5) dB(A) 26 26 29 31 35 29 31 35
Indoor sound pressure (Lo) (5) dB(A) 23 23 25 27 29 25 27 29
Indoor sound power (Hi) dB(A) 53 53 56 58 62 56 58 62
Indoor sound power (Med) dB(A) 49 49 52 54 58 52 54 58
Indoor sound power (Lo) dB(A) 46 46 48 50 52 48 50 52
Indoor dimension (Height) mm 250 250 250 250 250 250 250 250
Indoor dimension (Width) mm 1000 1000 1400 1400 1400 1400 1400 1400
Indoor dimension (Depth) mm 730 730 730 730 730 730 730 730
Indoor net weight kg 30 30 39 39 39 39 39 39
nanoe X Generator Mark 2 Mark 2 Mark 2 Mark 2 Mark 2 Mark 2 Mark 2 Mark 2
Outdoor unit U-60PZ2E5 U-71PZ2E5 U-100PZ2E5 U-125PZ2E5 U-140PZ2E5 U-100PZ2E8 U-125PZ2E8 U-140PZ2E8
Outdoor power source V 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415
Current in cooling (1p 220V / 3p 380) A 7,55 10,40 12,10 16,40 19,20 4,15 5,50 6,40
Current in cooling (1p 230V / 3p 400) A 7,20 9,95 11,60 15,70 18,40 3,95 5,25 6,10
Current in cooling (1p 240V / 3p 415) A 6,90 9,55 11,10 15,10 17,60 3,80 5,05 5,90
Current in heating (1p 220V / 3p 380) A 6,40 8,35 10,50 15,70 15,90 3,60 5,25 5,35
Current in heating (1p 230V / 3p 400) A 6,15 8,00 10,00 15,00 15,20 3,40 5,00 5,05
Current in heating (1p 240V / 3p 415) A 5,90 7,65 9,60 14,40 14,60 3,30 4,80 4,90
Outdoor air flow (Cool) m³/min 40 50 76 86 89 76 86 89
Outdoor air flow (Heat) m³/min 45 45 70 78 83 70 78 83
Outdoor sound pressure (Cool -Hi) dB(A) 46 49 52 55 56 52 55 56
Outdoor sound pressure (Heat -Hi) dB(A) 48 49 52 55 56 52 55 56
Outdoor sound power (Cool -Hi) dB(A) 65 69 70 73 74 70 73 74
Outdoor sound power (Heat -Hi) dB(A) 68 69 70 73 74 70 73 74
Outdoor dimension (Height) mm 695 695 996 996 996 996 996 996
Outdoor dimension (Width) mm 875 875 980 980 980 980 980 980
Outdoor dimension (Depth) mm 320 320 370 370 370 370 370 370
Outdoor net weight kg 44 44 90 94 94 90 94 94
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88)
Pipe length range m 3 ~ 40 3 ~ 40 5 ~ 50 5 ~ 50 5 ~ 50 5 ~ 50 5 ~ 50 5 ~ 50
Elevation difference (in/out) (6) m 30 30 30 30 30 30 30 30
Pipe length for additional gas m 30 30 30 30 30 30 30 30
Additional gas amount g/m 35 35 45 45 45 45 45 45
Refrigerant (R32) / CO2 Eq. kg / T 1,45 / 0,979 1,45 / 0,979 2,60 / 1,755 2,98 / 2,0115 2,98 / 2,0115 2,60 / 1,755 2,98 / 2,0115 2,98 / 2,0115
Operating range (Cool - Min) °C -10 -10 -10 -10 -10 -10 -10 -10
Operating range (Cool - Max) °C +43 +43 +43 +43 +43 +43 +43 +43
Operating range (Heat - Min) °C -15 -15 -15 -15 -15 -15 -15 -15
Operating range (Heat - Max) °C +24 +24 +24 +24 +24 +24 +24 +24
1) EER ir COP rodikliai apskaičiuoti pagal standartą EN14511.
2) Energijos etiketės skalė nuo A+++ iki D. 12 kW nesiekiančių modelių SEER ir SCOP apskaičiuoti pagal ES/626/2011 nurodytas vertes. 12 kW viršijančių modelių ηsc / ηsh vertės apskaičiuotos pagal EN 14825.
3) Metinės energijos sąnaudos apskaičiuotos pagal ES/626/2011.
4) Gamintojo nustatytas vidutinis išorinis statinis slėgis.
5) Blokų garso slėgio vertė buvo išmatuota 1,5 m atstumu nuo bloko apačios. Garso slėgis matuojamas pagal „Eurovent“ specifikaciją 6/C/006-97.
6) Kai lauko blokas įrengiamas aukščiau už vidaus bloką.
* Vidaus blokui rekomenduojamas 3 A saugiklis.
** Pirmiau pateiktos vertės tinka esant standartiniam įrengimui (horizontalusis įrengimas lubose, oro įleidimo anga galinėje pusėje), o „nanoe™ X“ funkcija yra išjungta.

Papildomi gaminiai