PACi with Water Heat Exchanger · R32

Previous capacity Next capacity

PACi with Water Heat Exchanger for chilled and hot water production

Introducing a highly-efficient Water Heat Exchanger for PACi Series.
This ground-breaking product provides further possibilities by adding hydronic options.

Specifications

See all
PACi with Water Heat Exchanger · R32
20.0 kW
Reference PAW-200W5APAC
Cooling capacity (1) kW 20,00
EER (1) W/W 3,03
Heating capacity (2) kW 23,00
COP (2) W/W 2,98
ηsh (LOT1) (3) % 178
Energy efficiency class (Scale A+++ to D) (4) A+++
Dimension (Height) mm 550
Dimension (Width) mm 455
Dimension (Depth) mm 205
Net weight kg 27
Water pipe connector Inch Male Thread 1  
Cooling water flow (∆T=5 K. 35°C) m³/h 3,45
Heating water flow (∆T=5 K. 35°C) L/min 4,15
Flow switch Included
Water filter Included
Outdoor unit U-200PZH2E8
Outdoor sound pressure (Cool -Hi) dB(A) 59
Outdoor sound pressure (Heat -Hi) dB(A) 61
Outdoor dimension (Height) mm 1500
Outdoor dimension (Width) mm 980
Outdoor dimension (Depth) mm 370
Outdoor net weight kg 117
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 1 (25,40)
Pipe length range m 5 ~ 90
Elevation difference (in/out) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 60
Water outlet temperature range (Cool - Min) °C +5
Water outlet temperature range (Cool - Max) °C +15
Water outlet temperature range (Heat - Max) °C +50
Operating range (Cool - Min) °C -15
Operating range (Cool - Max) °C +46
Operating range (Heat - Min) °C -20
Operating range (Heat - Max) °C +24

(1) Data refers to 7°C leaving chilled water temperature and 35°C ambient air temperature, according to EN14511 standard.
(2) Data refers to 35°C leaving warm water temperature and 7°C ambient air temperature according to EN14511 standard.
(3) Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps.
(4) Following COMMISSION REGULATION (EU) No 811/2013 for low-temperature heat pumps. Scale from A+++ to D.